| Date |
Text |
| 2007-11-08 16:58:08 | 2004 FBC W/2007 REVISIONS |
| | TWO STORY ADDITION |
| | |
| | DENIED BY BUILDING |
| | |
| | 1) IMPACT FEES MUST BE PAID TO PALM |
| | BEACH COUNTY, PLANS STAMPED BY THEM AND |
| | COPY OF RECEIPT SUBMITTED TO CITY OF |
| | WEST PALM BEACH BUILDING DEPARTMENT, |
| | BEFORE A BUILDING PERMIT CAN BE ISSUED. |
| | |
| | 2) A RECORDED COPY OF THE NOTICE OF COMMENCEMENT |
| | MUST BE SUBMITTED BEFORE A |
| | PERMIT CAN BE ISSUED. NOTE: WORK ON THE PROJECT MUST |
| | START WITHIN 90 DAYS OF THE DATE THE NOC IS RECORDED. |
| | |
| | 3)SUBMIT A SITE PLAN/SURVEY SHOWING THE LOCATION OF |
| | THE ADDITION AND THE DISTANCE TO PROPERTY LINES. FBC |
| | 106.3.5* CITY AMENDMENTS. |
| | |
| | 4) SHOW COMPLIANCE WITH R302.1 EXTERIOR WALLS. EXTERIOR |
| | WALLS SEPARATED BY LESS THAN 6 FEET (1828 MM) SHALL |
| | HAVE NOT LESS THAN A ONE-HOUR FIRE-RESISTIVE RATING |
| | WITH EXPOSURE FROM BOTH SIDES. PROJECTIONS SHALL NOT |
| | EXTEND TO A POINT CLOSER THAN 4 FEET (1220 MM) FROM AN |
| | ADJACENT PROJECTION OR WALL. |
| | IF THE DISTANCE FROM THE ADDITION TO THE PROPERTY LINE |
| | IS LESS THAN 6 FEET, SPECIFY THE DISTANCE TO STRUCTURES |
| | ON ADJACENT PROPERTY. |
| | |
| | 5)SUBMIT ENERGY CALCULATIONS FOR THE ADDITION. THE |
| | FORMS ARE REQUIRED TO BE SIGNED BY THE OWNER/AGENT. SEE |
| | FBC CHAPTER 13. |
| | |
| | 6) SUBMIT THE MANUFACTURER'S SPECIFICATIONS, FLOOR |
| | FRAMING PLAN AND SHOP DRAWINGS FOR THE HAMBRO FLOOR |
| | SYSTEM. FBC 106.1.2* CITY AMENDMENTS |
| | |
| | 7) SHOP DRAWINGS WILL BE REQUIRED FOR THE GUARD RAILS |
| | AT THE BALCONY SHOWING COMPLIANCE WITH R312. FBC |
| | 106.1.2* CITY AMENDMENTS |
| | |
| | 8) SPECIFY THE WIND EXPOSURE CATEGORY ON THE PLANS. |
| | R301.2.1.4 |
| | |
| | 9) THE WINDLOAD SCHEDULE ON SHEET 2 LISTS THE SAME |
| | PRESSURES FOR ROOF ZONES 2 AND 3. PLEASE CORRECT. SEE |
| | TABLE R301.2(2). |
| | |
| | 10)THE ROOF ZONE DIAGRAM ON SHEET 2 DOES NOT INDICATE |
| | ROOF ZONE 3 AT THE ROOF CORNERS. PLEASE CORRECT. SEE |
| | FIGURE R301.2(8)ASCE7-02 ALLOWS ROOF ZONE 3 TO BE |
| | TREATED AS ZONE 2 IF A PARAPET EQUAL TO OR GREATER THAN |
| | 3 FEET IS PROVIDED AROUND THE PERIMETER OF THE ROOF. |
| | THIS IS NOT SHOWN ON THE PLANS. |
| | |
| | 11) SPECIFY THE ROOF SHEATHING NAIL SPACING FOR ROOF |
| | ZONE 3 0N THE SCHEDULE ON SHEET 2.ROOF SHEATHING IS |
| | REQUIRED TO BE FASTENED IN ACCORDANCE WITH SECTION |
| | R803.2.3.1 OF 2006 REVISIONS TO 2004 FBC RESIDENTIAL |
| | CODE. WOOD STRUCTURAL PANEL SHEATHING SHALL BE FASTENED |
| | TO ROOF FRAMING WITH 8D RING-SHANK NAILS AT 6 INCHES ON |
| | CENTER AT EDGES AND 6 INCHES ON CENTER AT INTERMEDIATE |
| | FRAMING. SPACING OF RING-SHANK FASTENERS SHALL BE 4 |
| | INCHES ON CENTER IN NAILING ZONE 3 FOR 130 MPH OR |
| | GREATER DESIGN WIND SPEEDS IN ACCORDANCE WITH FIGURE |
| | R803.2.3.1. |
| | |
| | 12) SPECIFY THE ROOF PITCH OF THE NEW SLOPED ROOF AREA. |
| | FBC 106.1* CITY AMENDMENTS |
| | |
| | 13) SPECIFY THE SIZE AND LOCATIONS OF THE ROOF SCUPPERS |
| | AND OVERFLOW SCUPPERS. R903.4 AND R903.4.1 |
| | |
| | 14) SHOW COMPLIANCE WITH R320.7 PROTECTION AGAINST |
| | DECAY AND TERMITES. |
| | CONDENSATE LINES AND ROOF DOWNSPOUTS SHALL DISCHARGE AT |
| | LEAST 1 FOOT (305 MM) AWAY FROM THE STRUCTURE SIDEWALL, |
| | WHETHER BY UNDERGROUND PIPING, TAIL EXTENSIONS OR |
| | SPLASH BLOCKS. GUTTERS WITH DOWNSPOUTS ARE REQUIRED ON |
| | ALL BUILDINGS WITH EAVES OF LESS THAN 6 INCHES (152 MM) |
| | HORIZONTAL PROJECTION EXCEPT FOR GABLE END RAKES OR ON |
| | A ROOF ABOVE ANOTHER ROOF. |
| | |
| | 15) THE WALL SECTION DETAIL 'A' ON SHEET 3 AT THE ROOF |
| | PARAPET DOES NOT CORRESPOND WITH THE ROOF FRAMING PLAN |
| | OR THE ELEVATIONS. PLEASE CORRECT. |
| | |
| | 16) PROVIDE STRUCTURAL DETAILS FOR THE SLOPED AND FLAT |
| | ROOF OVER THE NEW MASTER BEDROOM. FBC 106.1* CITY |
| | AMENDMENTS |
| | |
| | 17) FIREBLOCKING IS REQUIRED WHERE THE SECOND FLOOR |
| | WALLS AND CEILING MEET. PLEASE INDICATE ON THE WALL |
| | DETAIL 'A'.R602.1.2 FIREBLOCKING REQUIRED. |
| | FIREBLOCKING SHALL BE PROVIDED TO CUT OFF ALL CONCEALED |
| | DRAFT OPENINGS (BOTH VERTICAL AND HORIZONTAL) AND TO |
| | FORM AN EFFECTIVE FIRE BARRIER BETWEEN STORIES, AND |
| | BETWEEN A TOP STORY AND THE ROOF SPACE. |
| | |
| | 18) SPECIFY THE ATTACHMENT METHOD THAT WILL BE USED TO |
| | INSTALL THE ROOF TILES. FBC 106.1* CITY AMENDMENTS AND |
| | R905.1 |
| | |
| | 19) SHOW COMPLIANCE WITH R806.1 VENTILATION REQUIRED. |
| | ENCLOSED ATTICS AND ENCLOSED RAFTER SPACES FORMED WHERE |
| | CEILINGS ARE APPLIED DIRECTLY TO THE UNDERSIDE OF ROOF |
| | RAFTERS SHALL HAVE CROSS VENTILATION FOR EACH SEPARATE |
| | SPACE BY VENTILATING OPENINGS PROTECTED AGAINST THE |
| | ENTRANCE OF RAIN. VENTILATING OPENINGS SHALL BE |
| | PROVIDED WITH CORROSION-RESISTANT WIRE MESH, WITH 1 / 8 |
| | INCH (3.2 MM) MINIMUM TO 1/4 INCH (6.4 MM) MAXIMUM |
| | OPENINGS. |
| | |
| | 20)PRODUCT APPROVALS SUBMITTED WITH PERMIT |
| | APPLICATION AFTER OCTOBER 1, 2003 ARE REQUIRED TO |
| | COMPLY WITH THE FLORIDA PRODUCT APPROVAL SYSTEM. FOR |
| | INFORMATION PLEASE SEE THE STATE WEBSITE AT |
| | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH STATEWIDE |
| | APPROVAL ARE REQUIRED TO BE SUBMITTED WITH A COVER |
| | SHEET THAT LISTS THE PRODUCT IDENTITY NUMBER FROM THE |
| | STATE. IF THE PRODUCT DOES NOT HAVE STATEWIDE APPROVAL, |
| | SUBMIT AN APPLICATION FOR LOCAL PRODUCT APPROVAL OR |
| | SITE SPECIFIC FORM PER RULE 9B-72. |
| | |
| | 21) 106.3* PRODUCT APPROVALS. THOSE PRODUCT WHICH ARE |
| | REGULATED BY DCA RULE 9B-72 SHALL BE REVIEWED AND |
| | APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO |
| | SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | |
| | 22) SUBMIT PRODUCT APPROVALS FOR THE TILE AND FLAT ROOF |
| | COVERINGS, STRUCTURAL WINDOW MULLIONS, IN-SWING GLAZED |
| | FRENCH DOORS, IN-SWING PANEL DOOR AND STORM PANELS. FAC |
| | RULE 9B-72 |
| | |
| | 23) SUBMIT A KEY PLAN AND INSTALLATION SCHEDULE FOR THE |
| | STORM PANELS. SPECIFY THE MOUNT TYPE, ANCHOR TYPE, |
| | ANCHOR SPACING, EDGE DISTANCE, ETC. SEE ATTACHED |
| | SAMPLE. FBC R301.2.1.2 |
| | |
| | 24) THE INFORMATION SUBMITTED FOR THE CENTURY SPECIALTY |
| | WINDOWS IS NOT ACCEPTABLE. SEE FAC RULE 9B-72. THE |
| | DESIGN PRESSURES FOR THIS WINDOW ARE TOO LOW. SEE PLANS |
| | FOR REQUIRED COMPONENT AND CLADDING PRESSURES. FBC |
| | TABLE R301.2(2) |
| | |
| | - ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |
| | (561)805-6714 |
| | [email protected] |
| | |
| | |