Plan Review Notes
Plan Review Notes For Permit 07100792
Permit Number 07100792
Review Stop B
Sequence Number 1
Notes
Date Text
2007-11-08 16:58:082004 FBC W/2007 REVISIONS
 TWO STORY ADDITION
  
 DENIED BY BUILDING
  
 1) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 2) A RECORDED COPY OF THE NOTICE OF COMMENCEMENT
 MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED. NOTE: WORK ON THE PROJECT MUST
 START WITHIN 90 DAYS OF THE DATE THE NOC IS RECORDED.
  
 3)SUBMIT A SITE PLAN/SURVEY SHOWING THE LOCATION OF
 THE ADDITION AND THE DISTANCE TO PROPERTY LINES. FBC
 106.3.5* CITY AMENDMENTS.
  
 4) SHOW COMPLIANCE WITH R302.1 EXTERIOR WALLS. EXTERIOR
 WALLS SEPARATED BY LESS THAN 6 FEET (1828 MM) SHALL
 HAVE NOT LESS THAN A ONE-HOUR FIRE-RESISTIVE RATING
 WITH EXPOSURE FROM BOTH SIDES. PROJECTIONS SHALL NOT
 EXTEND TO A POINT CLOSER THAN 4 FEET (1220 MM) FROM AN
 ADJACENT PROJECTION OR WALL.
 IF THE DISTANCE FROM THE ADDITION TO THE PROPERTY LINE
 IS LESS THAN 6 FEET, SPECIFY THE DISTANCE TO STRUCTURES
 ON ADJACENT PROPERTY.
  
 5)SUBMIT ENERGY CALCULATIONS FOR THE ADDITION. THE
 FORMS ARE REQUIRED TO BE SIGNED BY THE OWNER/AGENT. SEE
 FBC CHAPTER 13.
  
 6) SUBMIT THE MANUFACTURER'S SPECIFICATIONS, FLOOR
 FRAMING PLAN AND SHOP DRAWINGS FOR THE HAMBRO FLOOR
 SYSTEM. FBC 106.1.2* CITY AMENDMENTS
  
 7) SHOP DRAWINGS WILL BE REQUIRED FOR THE GUARD RAILS
 AT THE BALCONY SHOWING COMPLIANCE WITH R312. FBC
 106.1.2* CITY AMENDMENTS
  
 8) SPECIFY THE WIND EXPOSURE CATEGORY ON THE PLANS.
 R301.2.1.4
  
 9) THE WINDLOAD SCHEDULE ON SHEET 2 LISTS THE SAME
 PRESSURES FOR ROOF ZONES 2 AND 3. PLEASE CORRECT. SEE
 TABLE R301.2(2).
  
 10)THE ROOF ZONE DIAGRAM ON SHEET 2 DOES NOT INDICATE
 ROOF ZONE 3 AT THE ROOF CORNERS. PLEASE CORRECT. SEE
 FIGURE R301.2(8)ASCE7-02 ALLOWS ROOF ZONE 3 TO BE
 TREATED AS ZONE 2 IF A PARAPET EQUAL TO OR GREATER THAN
 3 FEET IS PROVIDED AROUND THE PERIMETER OF THE ROOF.
 THIS IS NOT SHOWN ON THE PLANS.
  
 11) SPECIFY THE ROOF SHEATHING NAIL SPACING FOR ROOF
 ZONE 3 0N THE SCHEDULE ON SHEET 2.ROOF SHEATHING IS
 REQUIRED TO BE FASTENED IN ACCORDANCE WITH SECTION
 R803.2.3.1 OF 2006 REVISIONS TO 2004 FBC RESIDENTIAL
 CODE. WOOD STRUCTURAL PANEL SHEATHING SHALL BE FASTENED
 TO ROOF FRAMING WITH 8D RING-SHANK NAILS AT 6 INCHES ON
 CENTER AT EDGES AND 6 INCHES ON CENTER AT INTERMEDIATE
 FRAMING. SPACING OF RING-SHANK FASTENERS SHALL BE 4
 INCHES ON CENTER IN NAILING ZONE 3 FOR 130 MPH OR
 GREATER DESIGN WIND SPEEDS IN ACCORDANCE WITH FIGURE
 R803.2.3.1.
  
 12) SPECIFY THE ROOF PITCH OF THE NEW SLOPED ROOF AREA.
 FBC 106.1* CITY AMENDMENTS
  
 13) SPECIFY THE SIZE AND LOCATIONS OF THE ROOF SCUPPERS
 AND OVERFLOW SCUPPERS. R903.4 AND R903.4.1
  
 14) SHOW COMPLIANCE WITH R320.7 PROTECTION AGAINST
 DECAY AND TERMITES.
 CONDENSATE LINES AND ROOF DOWNSPOUTS SHALL DISCHARGE AT
 LEAST 1 FOOT (305 MM) AWAY FROM THE STRUCTURE SIDEWALL,
 WHETHER BY UNDERGROUND PIPING, TAIL EXTENSIONS OR
 SPLASH BLOCKS. GUTTERS WITH DOWNSPOUTS ARE REQUIRED ON
 ALL BUILDINGS WITH EAVES OF LESS THAN 6 INCHES (152 MM)
 HORIZONTAL PROJECTION EXCEPT FOR GABLE END RAKES OR ON
 A ROOF ABOVE ANOTHER ROOF.
  
 15) THE WALL SECTION DETAIL 'A' ON SHEET 3 AT THE ROOF
 PARAPET DOES NOT CORRESPOND WITH THE ROOF FRAMING PLAN
 OR THE ELEVATIONS. PLEASE CORRECT.
  
 16) PROVIDE STRUCTURAL DETAILS FOR THE SLOPED AND FLAT
 ROOF OVER THE NEW MASTER BEDROOM. FBC 106.1* CITY
 AMENDMENTS
  
 17) FIREBLOCKING IS REQUIRED WHERE THE SECOND FLOOR
 WALLS AND CEILING MEET. PLEASE INDICATE ON THE WALL
 DETAIL 'A'.R602.1.2 FIREBLOCKING REQUIRED.
 FIREBLOCKING SHALL BE PROVIDED TO CUT OFF ALL CONCEALED
 DRAFT OPENINGS (BOTH VERTICAL AND HORIZONTAL) AND TO
 FORM AN EFFECTIVE FIRE BARRIER BETWEEN STORIES, AND
 BETWEEN A TOP STORY AND THE ROOF SPACE.
  
 18) SPECIFY THE ATTACHMENT METHOD THAT WILL BE USED TO
 INSTALL THE ROOF TILES. FBC 106.1* CITY AMENDMENTS AND
 R905.1
  
 19) SHOW COMPLIANCE WITH R806.1 VENTILATION REQUIRED.
 ENCLOSED ATTICS AND ENCLOSED RAFTER SPACES FORMED WHERE
 CEILINGS ARE APPLIED DIRECTLY TO THE UNDERSIDE OF ROOF
 RAFTERS SHALL HAVE CROSS VENTILATION FOR EACH SEPARATE
 SPACE BY VENTILATING OPENINGS PROTECTED AGAINST THE
 ENTRANCE OF RAIN. VENTILATING OPENINGS SHALL BE
 PROVIDED WITH CORROSION-RESISTANT WIRE MESH, WITH 1 / 8
 INCH (3.2 MM) MINIMUM TO 1/4 INCH (6.4 MM) MAXIMUM
 OPENINGS.
  
 20)PRODUCT APPROVALS SUBMITTED WITH PERMIT
 APPLICATION AFTER OCTOBER 1, 2003 ARE REQUIRED TO
 COMPLY WITH THE FLORIDA PRODUCT APPROVAL SYSTEM. FOR
 INFORMATION PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH STATEWIDE
 APPROVAL ARE REQUIRED TO BE SUBMITTED WITH A COVER
 SHEET THAT LISTS THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE STATEWIDE APPROVAL,
 SUBMIT AN APPLICATION FOR LOCAL PRODUCT APPROVAL OR
 SITE SPECIFIC FORM PER RULE 9B-72.
  
 21) 106.3* PRODUCT APPROVALS. THOSE PRODUCT WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 22) SUBMIT PRODUCT APPROVALS FOR THE TILE AND FLAT ROOF
 COVERINGS, STRUCTURAL WINDOW MULLIONS, IN-SWING GLAZED
 FRENCH DOORS, IN-SWING PANEL DOOR AND STORM PANELS. FAC
 RULE 9B-72
  
 23) SUBMIT A KEY PLAN AND INSTALLATION SCHEDULE FOR THE
 STORM PANELS. SPECIFY THE MOUNT TYPE, ANCHOR TYPE,
 ANCHOR SPACING, EDGE DISTANCE, ETC. SEE ATTACHED
 SAMPLE. FBC R301.2.1.2
  
 24) THE INFORMATION SUBMITTED FOR THE CENTURY SPECIALTY
 WINDOWS IS NOT ACCEPTABLE. SEE FAC RULE 9B-72. THE
 DESIGN PRESSURES FOR THIS WINDOW ARE TOO LOW. SEE PLANS
 FOR REQUIRED COMPONENT AND CLADDING PRESSURES. FBC
 TABLE R301.2(2)
  
 - ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]
  
  