| 2008-01-15 10:50:46 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBCFLORIDA BUILDING CODE 2004 |
| | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING |
| | CODE |
| | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC* |
| | CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 |
| | |
| | FAC FLORIDA ADMINISTRATIVE CODE |
| | FSFLORIDA STATUTE |
| | |
| | 1.THE MIAMIDADE NOA PROVIDED IS INCOMPLETE AND IS |
| | ILLEGIBLE.PRODUCT APPROVALS MAY BE AVAILABLE AT |
| | WWW.BUILDINGCODEONLINE.COM OR WWW.FLORIDABUILDING.ORG. |
| | |
| | 2.THE ANCHOR PROPOSED IS NOT INCLUDED IN THE PRODUCT |
| | APPROVAL PROVIDED, WEATHERGUARD BUILDING PRODUCTS. SPEC |
| | SHEETS WERE PROVIDED BUT THEY ARE FOR A DIFFERENT |
| | PRODUCT, POMA CORPORATION.SEE PAGE 4 OF 5 OF THE |
| | PRODUCT APPROVAL.THE INSTALLATION SCHEDULE REFERS TO |
| | A WINDOW PRODUCT APPROVAL.IT IS NOT CLEAR WHAT |
| | PRODUCT YOU ARE INSTALLING; THEREFORE, CODE COMPLIANCE |
| | CANNOT BE DETERMINED. |
| | |
| | 3.SEE SHEET 4.SOME ANCHORS ARE NOT PERMITTED FOR |
| | THE WEATHERGUARD PRODUCT INTO A CONCRETE BLOCK |
| | SUBSTRATE.ANCHOR SPACING SHOULD BE COMPLIANT WITH |
| | THIS SHEET, NOT WITH A SPEC SHEET FROM ANOTHER |
| | PRODUCT. |
| | |
| | 4.WHEN REFERRING TO THE SHUTTER CONNECTION MOUNTING |
| | TYPE, COLUMN 4, PLASE REFER TO C1 THROUGH C5 TO |
| | CORRELATE WITH THE ANCHOR SCHEDULE.IT APPEARS THAT |
| | YOU ARE USING A C1 CONNECTION; THEREFORE, "C1" SHOULD |
| | BE STATED AS THIS COLUMN (RATHER THAN "WALL MOUNT"). |
| | |
| | 5.ANCHOR SIZE ON TH CHART IS NOTED AS 7/8" IN LENGTH. |
| | PLEASE NOTE THAT THIS IS AN EMBEDMENT REQUIREMENT; |
| | THEREFORE AN ANCHOR OF THIS LENGTH WILL NOT MEET THE |
| | EMBEDMENT REQUIREMENT IF THE BUILDING HAS STUCCO. |
| | |