| 2007-12-11 10:48:36 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBCFLORIDA BUILDING CODE 2004 |
| | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING |
| | CODE |
| | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL |
| | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 |
| | FAC FLORIDA ADMINISTRATIVE CODE |
| | FSFLORIDA STATUTE |
| | |
| | COMMENTS FROM PREVIOUS LIST, NOT ADDRESSED: |
| | |
| | 1.PROVIDE A REASONABLE VALUATION FOR THIS JOB. |
| | |
| | 2.COMPLETE THE ATTACHED INSTALLATION SCHEDULE OR |
| | PROVIDE ALL INFORMATION TO SHOW CODE COMPLIANCE IN |
| | ANOTHER FORMAT, FBC*106.TWO SETS REQUIRED. |
| | |
| | 3.PRESTORM SHUTTER INSTALLATION PLAN PENDING. |
| | |
| | 4-5.ADDRESSED. |
| | |
| | 6.PLEASE ADDRESS THE USE OF THE WORDS "ARCHITECTURE" |
| | AND "INTERIOR DESIGN".AN INDIVIDUAL LICENSE IS |
| | REQUIRED, FS481.A SET HAS BEEN RETAINED AND MAY BE |
| | FILED WITH A COMPLAINT TO FBPE AND FLORIDA BOARD OF |
| | ARCHITECTS.DOCUMENTS PREPARED BY AN ARCHITECT OR |
| | INTERIOR DESIGNER AND SUBMITTED FOR PUBLIC RECORD ARE |
| | TO BE SIGNED, SEALED, DATED ORIGINALS FS481. |
| | |
| | IT APPEARS THAT, DESPITE WARNINGS FROM AND |
| | CONVERSATIONS WITH TWO DIFFERENT REVIEWERS ON TWO |
| | SEPARATE PROJECTS REGARDING THIS ISSUE, CONTRACTOR IS |
| | STILL USING "ARCHITECTURE" AND "INTERIOR DESIGN" |
| | WITHOUT A LICENSE.CONTRACTOR STILL SHOWS THIS NAME |
| | WITH THE DBPR WEBSITE, HAS USED THIS NAME ON |
| | LETTERHEAD, AND MAINTAINS AN ACTIVE CORPORATION. |
| | CONTRACTOR'S AGREEMENT WITH THE PLAN REVIEWERS WAS TO |
| | DISCONTINUE USE OF THE TERMINOLOGY OR THE MATTER WOULD |
| | BE FORWARDED TO FLORIDA BOARD OF ARCHITECTS.THIS |
| | COMMENT DOES NOT APPEAR TO HAVE BEEN ADDRESSED. |
| | |
| | 7.ADDRESSED. |
| | |
| | 8.SEE FBC1025.4.1 AND SHOW COMPLIANCE ON THE PLAN. |
| | |
| | THE ENGINEER HAS A STATEMENT ON THE PLAN, "2 EXIT DOORS |
| | IN EACH ROOM, NO EGRESS WINDOWS REQUIRED".THE "EXIT |
| | DOORS" DO NOT QUALIFY AS EXITS, SEE FBC1002 |
| | DEFINITIONS.SEE FBC EB 505, YOU CANNOT REDUCE THE |
| | LEVEL OF SAFETY FOR MEANS OF EGRESS UNLESS IT COMPLIES |
| | WITH FBC CHAPTER 10.AS WINDOWS FOR EMERGENCY RESCUE |
| | IS REQUIRED, FBC1033.6 AND FBC1025.4.1, YOU ARE |
| | REDUCING THE LEVEL OF SAFETY BY INSTALLING HURRICANE |
| | SHUTTERS. |
| | |
| | 9--10.ADDRESSED. |
| | |
| | 11. FLORIDA STATE OR LOCAL PRODUCT APPROVAL REQUIRED IN |
| | ADDITION TO THE NOAS SUBMITTED, FAC9B72, |
| | WWW.FLORIDABUILDING.ORG. |