Plan Review Notes
Plan Review Notes For Permit 07100743
Permit Number 07100743
Review Stop G
Sequence Number 1
Notes
Date Text
2007-12-07 19:01:43DENIED
 REFERENCE: FBC-2004 FUEL GAS
 FBC-2004 CHAPTER 1
  
 1. MORE INFORMATION IS REQUIRED. PLEASE INDICATE WHAT
 OUTLET PRESSURE IS THE PIPING DESIGNED FOR DOWNSTREAM
 OF THE COMPRESSOR.--PLEASE INDICATE THE METHOD OF
 PIPING THE DIFFERENT SKID EQUIPMENT, SUCH AS THE
 COMPRESSOR, DRYER, FLARE ETC. IF THE METHOD IS WELD
 PIPE, THEN THE WELDING PROCEDURE AND WELDING
 CERTIFICATIONS WILL BE REQUIRED PRIOR TO ISSUING THE
 PERMIT. A PICTURE IDENTIFICATION WILL BE REQUIRED ALONG
 WITH THE CERTIFICATIONS. SECTION 106.1.2.
  
 2. PLEASE PROVIDE MANUF. SPECIFICATION SHEETS FOR THE
 COMPRESSOR, DRYER, ETC. SECTION 106.1.2.
  
 3. THE ADDRESS ON THE APPLICATION DOES NOT REFLECT THE
 ADDRESS IN OUR SYSTEM. ONCE THE CORRECT ADDRESS IS
 DETERMINED, ALL PLAN TITLE BLOCKS AND SHALL SHOW THE
 CORRECT ADDRESS PER SECTION 106.1.1.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved