| 2008-01-04 15:46:54 | HYATT PLACE |
| | |
| | BUILDING PLAN REVIEW |
| | PERMIT: 07100733 / STRUCTURAL PERMIT ONLY |
| | ADD: 295 LAKEVIEW DRIVE |
| | CONT: KAST CONSTRUCTION |
| | TEL: (561)# 718-6141 |
| | |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | W/ 2007 FBC REVISIONS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 2NDREVIEW |
| | ACTION: DENIED |
| | |
| | 1A)--- VERY IMPORTANT STATEMENT --- |
| | PLEASE DO NOT IGNORE! |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL |
| | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH |
| | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE |
| | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE |
| | FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR |
| | YOUR ANTICIPATED COOPERATION. |
| | |
| | 1B) INFORMATIONAL, PLEASE SUBMIT 2 OF ALL SURVEYS, |
| | PLANS, REPORTS, REVISIONS , PRODUCT APPROVALS AND OR |
| | SUBMITTALS FOR REVIEW FOR PERMIT. IF YOUR PROJECT WILL |
| | REQUIRE A RESIDENT INSPECTOR OR IF YOUR PROJECT IS A |
| | THRESHOLD BUILDING REQUIRING A THRESHOLD INSPECTOR THEN |
| | (3) THREE SETS OF ALL SAID DOCUMENTS WILL BE REQUIRED |
| | FOR PERMIT ISSUANCE. 106.1* /2004 SUBMITTAL DOCUMENTS |
| | WEST PALM BEACH ADMINISTRATIVE CODE. |
| | |
| | 1C)INFORMATIONAL, 106.1.1* W.P.B. ADMINISTRATIVE |
| | CODE/2004 DRAWINGS & SPECIFICATIONS SHALL CONTAIN |
| | INFORMATION, IN THE FORM OF NOTES OR OTHERWISE, AS TO |
| | THE QUALITY OF MATERIALS, WHERE QUALITY IS ESSENTIAL TO |
| | CONFORMITY WITH THE TECHNICAL CODES. SUCH INFORMATION |
| | SHALL BE SPECIFIC TO THE TECHNICAL CODES "SHALL NOT BE |
| | CITED AS A WHOLE OR IN PART, NOR THE TERM "LEGAL" OR |
| | ITS EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC |
| | INFORMATION". CONSTRUCTION DOCUMENTS SHALL BE |
| | SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND |
| | EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT |
| | WILL CONFORM TO THE PROVISIONS OF THIS CODE AND |
| | RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS |
| | DETERMINED BY THE BUILDING OFFICIAL. |
| | |
| | 1D ) INFORMATIONAL,PLANS SUBMITTED FOR PERMIT (FIRST |
| | TIME REVIEW) AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO |
| | THE 2004 FBC BUILDING WITH THE2007 REVISIONS. |
| | |
| | 1E) CONFIRMED/ COMPLIED. |
| | |
| | 2) WPB AMENDMENT 105.13.6. W.P.B. CONSTRUCTION |
| | SERVICES DEPARTMENT REQUEST FOR THRESHOLD BUILDINGS A |
| | SPECIAL INSPECTOR AS REQUIRED BY FL S S 553.79(5) |
| | FLORIDA STATUTES TO THE MINIMUM INSPECTIONS REQUIRED BY |
| | THIS CODE. CONTACT HAROLD PISKURA MANAGER OF THE |
| | SPECIAL INSPECTOR PROGRAM AT (561)805-6711 FOR FURTHER |
| | INFORMATION BEFORE THE PERMIT MAY BE ISSUED. |
| | |
| | 3) COMPLIED |
| | |
| | 4) BUILDING PROVISO: 109.3.10* IMPACT OF CONSTRUCTION. |
| | |
| | 5) BUILDING PROVISO: 109.3.10.1 HURRICANE PROTECTION. |
| | I |
| | |
| | 6) BUILDING PROVISO:105.13. SPECIAL STRUCTURAL ONLY |
| | PERMIT WHEN APPLICATION FOR A PERMIT TO ERECT OR |
| | ENLARGE A BUILDING HAS BEEN FILED, & PENDING ISSUANCE |
| | OF SUCH PERMIT, THE BUILDING OFFICIAL MAY, AT HIS/ HER |
| | DISCRETION, ISSUE A SPECIAL PERMIT FOR THE FOUNDATION |
| | OR STRUCTURAL ONLY PERMIT, UPON WRITTEN REQUEST OF THE |
| | OWNER AND CONTRACTOR. THE HOLDER OF SUCH A SPECIAL |
| | PERMIT IS PROCEEDING AT HIS OR HER OWN RISK AND WITHOUT |
| | ASSURANCE THAT A PERMIT FOR THE REMAINDER OF THE WORK |
| | WILL BE GRANTED AND THAT CORRECTIONS WILL NOT BE |
| | REQUIRED IN ORDER TO MEET THE PROVISIONS OF THE |
| | TECHNICAL CODE. |
| | |
| | NEW COMMENTS: |
| | 7) REVISION # 4 INDICATES ON THE ARCHITECTURAL SHEET |
| | A-101A COLUMN LINE A: 11.9 INDICATING A SINGLE COLUMN |
| | VERSES STRURTURAL SHEET S-101.A NOT PICKING UP THE |
| | REVISION INDICATING COLUMNS C-73 & C-93, PLEASE |
| | CORRELATE. |
| | |
| | 8) PROVISO: NOTE THIS WILL NOT EFFECT THE STRUCTURAL |
| | PERMIT BUT WILL EFFECT THE BUILDING PERMIT. ON THE EAST |
| | SIDE OF THE BUILDING PLAN A-100 & A-101B BOTH INDICATE |
| | THE GENERATOR ROOM VENTING (INTAKE) ON THE EAST SIDE OF |
| | THE BUILDING . THE PROPERTY LINE IS APPROXIMATELY 1'0" |
| | AWAY. TABLE 704.8 ALLOWABLE OPENINGS DOES NOT ALLOW ANY |
| | OPENINGS WITHIN 3'-0" OF THE PROPERTY LINE. PLEASE ALSO |
| | NOTE THERE IS NO EXHAUST FOR THE GENERATOR INDICATED, |
| | THESE ITEMS WILL NEED TO BE ADDRESSED UNDERTHE BUILDING |
| | PERMIT. |
| | |
| | |
| | |
| | JIM WITMER C. B. O. |
| | BUILDING PLAN REVIEW II |
| | |
| | TEL: (561)805-6715 |
| | FAX: (561)659-8026 |
| | E-MAIL: [email protected] |
| | |
| | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| | THE PUBLIC UPON REQUEST. YOUR E-MAILCOMMUNICATIONS ARE |
| | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |