| 2007-12-04 16:11:07 | *****DENIED***** |
| | |
| | 01.THE PROJECT SITE ADDRESS SHALL BE IN THE TITLE |
| | BLOCK OF EACH SUBMITTED PLAN SHEET.ALSO, SOME PLAN |
| | SHEET LIST LAKEVIEW AS A DRIVE, SHOULD BE LISTED AS AN |
| | AVENUE. |
| | |
| | 02.ON SHEET G-000 UNDER BUILDING INFORMATION AND |
| | CODES, PLEASE EXPLAIN REFERENCE TO NFPA 2002. |
| | |
| | 03.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR |
| | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241. |
| | |
| | 04.THE PROJECTED SCOPE OF WORK SHALL NOT INTERFERE OR |
| | HINDER EMERGENCY RESPONSE ACCESS TO THE SAID PROPERTY |
| | OR THE VICINITY THEREOF (INCLUDING ROADWAYS, ALLEYS, |
| | FIRE LANES). |
| | |
| | 05.IN ALL BUILDINGS OVER ONE STORY IN HEIGHT, AT |
| | LEAST ONE STAIRWAY SHALL BE PROVIDE IN AN USABLE |
| | CONDITION AT ALL TIMES. |
| | |
| | 06.A TEMPORARY STANDPIPE SYSTEM IS REQUIRED WHEN THE |
| | BUILDING REACHES THREE STORIES OR THIRTY FEET IN |
| | HEIGHT.THE STANDPIPES SHALL BE PROVIDED WITH |
| | CONSPICUOUSLY MARKED AND READILY ACCESSIBLE FIRE |
| | DEPARTMENT CONNECTIONS ON THE OUTSIDE OF THE BUILDING |
| | AT THE STREET LEVEL AND HAVE AT LEAST ONE STANDARD HOSE |
| | OULET AT EACH FLOOR. |
| | |
| | 07.ILLUSTRATE FIRE HYDRANT LOCATIONS ON SITE PLAN. |
| | |
| | 08.WHERE/IF UNDERGROUND WATER MAINS AND FIRE HYDRANTS |
| | ARE TO BE PROVIDED, THEY SHALL BE INSTALLED, COMPLETED, |
| | AND IS SERVICE PRIOR TO CONSTRUCTION WORK. |
| | |
| | 09.THERE SHALL BE NO DELAY IN THE INSTALLATION OF |
| | FIRE PROTECTION EQUIPMENT. |
| | |
| | 10.THE INSTALLATION OF THE SPRINKLER SYSTEM SHALL BE |
| | PLACED IN SERVICE AS SOON AS PRACTICABLE. |
| | |
| | 11.THE PROJECT SITE ADDRESS SHALL BE TEMPORARILY |
| | POSTED PRIOR TO, AND DURING CONSTRUCTION, OR UNTIL SUCH |
| | TIME THAT THE PERMANANT NUMERICAL ADDRESS IS DISPLAYED |
| | ON THE EXTERIOR ELEVATION WHICH FRONTS LAKEVIEW |
| | AVENUE. |
| | |
| | |
| | |
| | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE |
| | LETTER INDICATING WHERE EACH ITEM WAS ADDRESSED |
| | |
| | |
| | CAPT. MICHAEL A. WILLIAMS |
| | FIRE PLAN REVIEW |
| | 561-805-6722 |