| 2007-11-21 13:32:40 | ** DENIED REVIEW ** |
| | |
| | ** THE BELOW COMMENTS WERE PREVIOUSLY GIVEN IN MEETINGS |
| | AND PHONE CONVERSATIONS. |
| | |
| | 1) NOTE:PLEASE SEE COVER SHEET WHICH REFLECTS BOTH |
| | THE 2002 NATIONAL ELECTRICAL CODE AND 2005 NATIONAL |
| | ELECTRICAL CODE. |
| | AS OF DECEMBER 8TH, 2006 THE STATE HAS ADOPTED THE |
| | 2005. |
| | PLEASE SEE THAT OTHER RELEVANT CODES SHALL BE ON |
| | PLANS. |
| | 2002 NFPA-72 |
| | 2002 NFPA-110 |
| | 2003 NFPA-20(IF IN DESIGN FOR BUILDING. |
| | |
| | 2) NOTE: PLEASE SUBMIT A COMPLETE ELECTRICAL GROUNDING |
| | ELECTRODE SYSTEM AND SIZING FOR MINIMUM ATTACHMENT |
| | LOCATIONS PER 250.50 |
| | |
| | 3) NOTE: PLEASE KNOW AS MENTIONED IN PREVIOUS MEETINGS |
| | THE LOCATION OF THE GENERATOR WITH AIR INTAKE AND |
| | EXHAUST ON ZERO LOT LINE NEEDS TO BE LOOKED AT FOR CODE |
| | COMPLIANCE. |
| | AS SHOWN THE LOCATION FOR BOTH OF THESE ITEMS MAY |
| | CHANGE STRUCTURAL COMPONENTS. |
| | |
| | 4) NOTE: PLEASE SEE NEC 680.26 FOR EQUAL-POTENTIAL |
| | BONDING OF POOL/SPA AREAS AND ALL STEEL AND OTHER METAL |
| | WITHIN 5 FT OF POOL. |
| | PLEASE KNOW AS SOME OF THESE STRUCTURAL ELEMENTS APPEAR |
| | TO BE DONE AT THIS TIME, PLEASE INCLUDE DETAILS FOR |
| | THIS. |
| | |
| | |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| | CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| | OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS |
| | INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT |
| | LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| | DELAYS. |
| | |