2009-05-01 16:50:23DENIED
 REFERENCE:
 FBC-2004 PLUMBING
  
 1. SHT 8 SHOWS A REVISION CHANGING THE WATER SERVICE
 FROM 1" TO 3/4". PER SECTION 603.1 THE WATER SERVICE
 SHALL BE SIZED IN ACCORDANCE WITH TABLE 603.1 OR OTHER
 APPROVED METHODS.
 TABLE 603.1 INDICATES 1" REQUIRED FOR 30 FIXTURE UNITS
 FLUSH TANK W/C. PER TABLE 709.1 THERE ARE 30 FIXTURE
 UNITS. MINIMUM 1" WATER SERVICE IS REQUIRED.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  