Plan Review Notes
Plan Review Notes For Permit 07100724
Permit Number 07100724
Review Stop E
Sequence Number 5
Notes
Date Text
2008-12-30 11:15:36** DENIED REVISIONS**
  
 1) NOTE: NOTES ON PLANS CALL FOR SPACES A AND B AS
 SHELL SPACES YET THE PLANS STILL SHOW ALL ELECTRICAL AS
 IT WAS BEING BUILT OUT. THIS IS CONFUSING.
 A MINIMUM EXIT AND EGRESS LIGHT IS REQUIRED HOWEVER NOT
 ALL AS SHOWN. IF DELETING THIS SCOPE OF WORK THEN
 PLEASE REVISE PLANS ACCORDINGLY AND REVISE PANEL
 SCHEDULES FOR THE UNITS.
 NEC 2005
 408.4,240.4,310.16, ETC AS COMMON ELECTRICAL CODE
 SECTIONS FOR REFLECTED PLANS.
 FBC 106.1.1,106.1.2, 106.5. FOR CLARITY, COORDINATION
 OF RECORD PLANS.
  
 2) NOTE: PLEASE REVISE METHOD OF ENERGY CALCULATIONS
 PER 13-101.1.6 FOR INCOMPLETE/SHELL BUILDINGS.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  