Plan Review Notes
Plan Review Notes For Permit 07100724
Permit Number 07100724
Review Stop E
Sequence Number 3
Notes
Date Text
2008-04-02 16:18:52** DENIED3RD REVIEW **
  
 ** PLEASE SEE SOME ITEMS FROM PREVIOUS REVIEWS ARE
 STILL IN NEED OF ADDRESSING.
  
 1) NOTE: ADDRESS IS STILL PENDING. THE TITLE BLOCKS DO
 SHOW THE APPLIED ADDRESS AND ANY CHANGES FORTHCOMING
 MAY BE CHANGED. THE FINAL DETERMINATION HAS NOT YET
 BEEN MADE. INFORMATION SENT TO ADDRESSING REVIEWER.
  
 2) NOTE: PLEASE SEE THE ENERGY CALCULATIONS SUBMITTED
 ONCE AGAIN DO NOT COORDINATE WITH PLANS. PLEASE SEE THE
 INPUT DATA REPORT WILL BE NOTED BELOW AS IDR. PLEASE
 SEE PREVIOUS REVIEWS GAVE SOME SPECIFIC EXAMPLES OF
 LIGHTING ON PLANS AND THE IDR WHICH DID NOT CORRELATE.
 THE NOTES EVEN STATED * THOSE EXAMPLES WERE NOT THE
 ONLY ONES.
 PLEASE SEE THE FOLLOWING EXAMPLES WILL BE GIVEN ONCE
 AGAIN.
 EXAMPLE:
 PLANS SHOW 10-250W LOW BAY FIXTURES, YET THE IDR ONLY
 SHOWS 5.
 PLANS SHOW 6-96W FIXTURES, YET THE IDR ONLY SHOWS 3.
 PLANS SHOW 4-32W FIXTURES, YET THE IDR ONLY SHOWS 3.
 PLEASE SEE 13-415.1.A, 13-415.2, 13-415.2.ABC.1. **
 SHEET STATES RETAIL? PLANS STATE INDUSTRIAL.?? *** IF
 THERE ARE QUESTIONS, PLEASE CALL. THE LIGHTING ON PLANS
 IS OK, AS THIS COMMENT IS NOT FOR CHANE ENGINEERING.
  
 3) NOTE: PLEASE SEE PREVIOUS REVIEW NOTE # 5 GAVE
 NOTICE TO FS 553.80(2)(B) WITH RESPECTTO REPEAT
 COMMENTS FOR CODE COMPLIANCE.
 PLEASE SEE THAT CODE SECTIONS FOR ENERGY CALCULATIONS
 COMPLIANCE WERE GIVEN THREE TIMES FOR THE SAME ITEMS.
 AS REQUIRED BY FLORIDA STATUTES NOTED ABOVE A FEE HAS
 NOW BEEN ASSESSED AS REQUIRED AND IS REQUIRED TO BE
 PAID BEFORE PLANS ARE PERMITTED TO BE RESUBMITTED. THE
 FEE IS $5,146.80 WILL BE DUE BEFORE RESUBMISSION OF
 PLANS. THE 10% RE-SUB FEE WILL NOT BE CHARGED PER
 BUILDING OFFICIAL.
 ***DOCUMENTS ARE BEING RETAINED.
  
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  