| 2008-04-02 16:18:52 | ** DENIED3RD REVIEW ** |
| | |
| | ** PLEASE SEE SOME ITEMS FROM PREVIOUS REVIEWS ARE |
| | STILL IN NEED OF ADDRESSING. |
| | |
| | 1) NOTE: ADDRESS IS STILL PENDING. THE TITLE BLOCKS DO |
| | SHOW THE APPLIED ADDRESS AND ANY CHANGES FORTHCOMING |
| | MAY BE CHANGED. THE FINAL DETERMINATION HAS NOT YET |
| | BEEN MADE. INFORMATION SENT TO ADDRESSING REVIEWER. |
| | |
| | 2) NOTE: PLEASE SEE THE ENERGY CALCULATIONS SUBMITTED |
| | ONCE AGAIN DO NOT COORDINATE WITH PLANS. PLEASE SEE THE |
| | INPUT DATA REPORT WILL BE NOTED BELOW AS IDR. PLEASE |
| | SEE PREVIOUS REVIEWS GAVE SOME SPECIFIC EXAMPLES OF |
| | LIGHTING ON PLANS AND THE IDR WHICH DID NOT CORRELATE. |
| | THE NOTES EVEN STATED * THOSE EXAMPLES WERE NOT THE |
| | ONLY ONES. |
| | PLEASE SEE THE FOLLOWING EXAMPLES WILL BE GIVEN ONCE |
| | AGAIN. |
| | EXAMPLE: |
| | PLANS SHOW 10-250W LOW BAY FIXTURES, YET THE IDR ONLY |
| | SHOWS 5. |
| | PLANS SHOW 6-96W FIXTURES, YET THE IDR ONLY SHOWS 3. |
| | PLANS SHOW 4-32W FIXTURES, YET THE IDR ONLY SHOWS 3. |
| | PLEASE SEE 13-415.1.A, 13-415.2, 13-415.2.ABC.1. ** |
| | SHEET STATES RETAIL? PLANS STATE INDUSTRIAL.?? *** IF |
| | THERE ARE QUESTIONS, PLEASE CALL. THE LIGHTING ON PLANS |
| | IS OK, AS THIS COMMENT IS NOT FOR CHANE ENGINEERING. |
| | |
| | 3) NOTE: PLEASE SEE PREVIOUS REVIEW NOTE # 5 GAVE |
| | NOTICE TO FS 553.80(2)(B) WITH RESPECTTO REPEAT |
| | COMMENTS FOR CODE COMPLIANCE. |
| | PLEASE SEE THAT CODE SECTIONS FOR ENERGY CALCULATIONS |
| | COMPLIANCE WERE GIVEN THREE TIMES FOR THE SAME ITEMS. |
| | AS REQUIRED BY FLORIDA STATUTES NOTED ABOVE A FEE HAS |
| | NOW BEEN ASSESSED AS REQUIRED AND IS REQUIRED TO BE |
| | PAID BEFORE PLANS ARE PERMITTED TO BE RESUBMITTED. THE |
| | FEE IS $5,146.80 WILL BE DUE BEFORE RESUBMISSION OF |
| | PLANS. THE 10% RE-SUB FEE WILL NOT BE CHARGED PER |
| | BUILDING OFFICIAL. |
| | ***DOCUMENTS ARE BEING RETAINED. |
| | |
| | |
| | ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY |
| | COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE |
| | DO NOT HESITATE IN CONTACTING THIS OFFICE. |
| | PLEASE SEE BELOW FOR CONTACT INFORMATION. |
| | |
| | ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| | CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| | OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS |
| | INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT |
| | LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| | TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| | DELAYS. |
| | |