2008-03-15 13:04:40DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 ****FROM PREVIOUS REVIEW:
  
 1. INDICATE CODE REFERENCE BY WHICH PLANS WERE
 DESIGNED. SECTION 106.1.1.
 ****RESPONSE NOTED, COMMENT NOT ADDRESSED.
  
 2. OK
  
 3. SUBMIT CALCULATIONS FOR THE ROOF DRAINAGE. SHOW THE
 SQUARE FOOTAGE OF THE ROOF AND SHOW 1/2 AREA OF ALL
 VERTICAL WALLS INCLUDING PARAPTES ADDED TO ROOF AREA.
 SECTION 1106.
 ****RESPONSE NOTED, BUT COMMENT NOT ADDRESSED. THE
 CALCULATIONS ARE REQUIRED IN ORDER TO VERIFY THE SIZE
 OF THE GUTTERS AND THE DOWNSPOUTS PER TABLES 1106.2 &
 1106.6.
  
 4. OK
  
 5. SUBMIT A DETAIL FOR THE DRINKING FOUNTAINS SHOWING
 COMPLIANCE WITH SECTION 11-4.15 WITH ALL SUBSECTION AS
 WELL AS SECTION 11-4.1.3(10)(A) PROVISIONS FOR THOSE
 WHO HAVE TROUBLE BENDING OR STOOPING.
 ****RESPONSE NOTED, BUT SECTION 11-4.1.3(10)(A) HAS NOT
 BEEN ADDRESSED.
  
 6. SHT 4 SHOW THE GUTTER & DOWNSPOUT SIZES PER TABLES
 1106.3 & 1106.6. INDICATE THE SLOPE OF THE GUTTER AND
 SHOW THE HIGH POINT OF THE GUTTER.
 ****RESPONSE NOTED, BUT THE SLOPE OF THE GUTTER AND THE
 HIGH POINT OF THE GUTTER HAS NOT BEEN ADDRESSED.
  
 7. SHT 4 SHOWS 1/4"/FT SLOPE, BUT THE TOTAL DROP OVER
 53' WOULD REQUIRED 13.25". ONLY 12" DROP IS SHOWN.
 PLEASE CLAIRFY. SECTION 106.1.1.
 ****RESPONSE NOTED, BUT THE WEST SIDE, (DETAIL 5/4),
 INDICATES THE TOP OF THE TIE BEAM AT 18'10" AND THE
 EAST SIDE, (DETAIL 6/4), INDICATES THE TOP OF THE TIE
 BEAM AT 19'10-3/4". PER 1507.10.1 SLOPE.
 BUILT-UP ROOFS SHALL HAVE A DESIGN SLOPE OF A MINIMUM
 OF ONE-FOURTH UNIT VERTICAL IN 12 UNITS HORIZONTAL
 (2-PERCENT SLOPE) FOR DRAINAGE, EXCEPT FOR COAL-TAR
 BUILT-UP ROOFS THAT SHALL HAVE A DESIGN SLOPE OF A
 MINIMUM ONE-EIGHTH UNIT VERTICAL IN 12 UNITS HORIZONTAL
 (1-PERCENT SLOPE). PLEASE CLARIFY.
  
 8. OK
 9. OK
 10. OK
 11. DELETED
 12. OK
  
 **********NEW COMMENT**********
  
 1B. SHT 8, THE WATER ISOMETRIC RISER DIAGRAM DOES NOT
 REFLECT THE FLOOR PLAN AT THE DRINKING FOUNTAINS. THE
 DRINKING FOUNTAIN IS SHOWN ON THE SAME WALL WITH THE
 SERVICE SINK ON THE FLOOR PLAN, BUT IS SHOWN ACROSS THE
 ROOM FROM THE LAV ON THE RISER DIAGRAM. PLEASE
 CORRELATE. SECTION 106.1.1.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID
 SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY
 ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS