| 2008-03-15 13:04:40 | DENIED |
| | REFERENCE: FBC-2004 PLUMBING |
| | FBC-2004 CHAPTER 1 |
| | FBC-2004 CHAPTER 11 |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | |
| | ****FROM PREVIOUS REVIEW: |
| | |
| | 1. INDICATE CODE REFERENCE BY WHICH PLANS WERE |
| | DESIGNED. SECTION 106.1.1. |
| | ****RESPONSE NOTED, COMMENT NOT ADDRESSED. |
| | |
| | 2. OK |
| | |
| | 3. SUBMIT CALCULATIONS FOR THE ROOF DRAINAGE. SHOW THE |
| | SQUARE FOOTAGE OF THE ROOF AND SHOW 1/2 AREA OF ALL |
| | VERTICAL WALLS INCLUDING PARAPTES ADDED TO ROOF AREA. |
| | SECTION 1106. |
| | ****RESPONSE NOTED, BUT COMMENT NOT ADDRESSED. THE |
| | CALCULATIONS ARE REQUIRED IN ORDER TO VERIFY THE SIZE |
| | OF THE GUTTERS AND THE DOWNSPOUTS PER TABLES 1106.2 & |
| | 1106.6. |
| | |
| | 4. OK |
| | |
| | 5. SUBMIT A DETAIL FOR THE DRINKING FOUNTAINS SHOWING |
| | COMPLIANCE WITH SECTION 11-4.15 WITH ALL SUBSECTION AS |
| | WELL AS SECTION 11-4.1.3(10)(A) PROVISIONS FOR THOSE |
| | WHO HAVE TROUBLE BENDING OR STOOPING. |
| | ****RESPONSE NOTED, BUT SECTION 11-4.1.3(10)(A) HAS NOT |
| | BEEN ADDRESSED. |
| | |
| | 6. SHT 4 SHOW THE GUTTER & DOWNSPOUT SIZES PER TABLES |
| | 1106.3 & 1106.6. INDICATE THE SLOPE OF THE GUTTER AND |
| | SHOW THE HIGH POINT OF THE GUTTER. |
| | ****RESPONSE NOTED, BUT THE SLOPE OF THE GUTTER AND THE |
| | HIGH POINT OF THE GUTTER HAS NOT BEEN ADDRESSED. |
| | |
| | 7. SHT 4 SHOWS 1/4"/FT SLOPE, BUT THE TOTAL DROP OVER |
| | 53' WOULD REQUIRED 13.25". ONLY 12" DROP IS SHOWN. |
| | PLEASE CLAIRFY. SECTION 106.1.1. |
| | ****RESPONSE NOTED, BUT THE WEST SIDE, (DETAIL 5/4), |
| | INDICATES THE TOP OF THE TIE BEAM AT 18'10" AND THE |
| | EAST SIDE, (DETAIL 6/4), INDICATES THE TOP OF THE TIE |
| | BEAM AT 19'10-3/4". PER 1507.10.1 SLOPE. |
| | BUILT-UP ROOFS SHALL HAVE A DESIGN SLOPE OF A MINIMUM |
| | OF ONE-FOURTH UNIT VERTICAL IN 12 UNITS HORIZONTAL |
| | (2-PERCENT SLOPE) FOR DRAINAGE, EXCEPT FOR COAL-TAR |
| | BUILT-UP ROOFS THAT SHALL HAVE A DESIGN SLOPE OF A |
| | MINIMUM ONE-EIGHTH UNIT VERTICAL IN 12 UNITS HORIZONTAL |
| | (1-PERCENT SLOPE). PLEASE CLARIFY. |
| | |
| | 8. OK |
| | 9. OK |
| | 10. OK |
| | 11. DELETED |
| | 12. OK |
| | |
| | **********NEW COMMENT********** |
| | |
| | 1B. SHT 8, THE WATER ISOMETRIC RISER DIAGRAM DOES NOT |
| | REFLECT THE FLOOR PLAN AT THE DRINKING FOUNTAINS. THE |
| | DRINKING FOUNTAIN IS SHOWN ON THE SAME WALL WITH THE |
| | SERVICE SINK ON THE FLOOR PLAN, BUT IS SHOWN ACROSS THE |
| | ROOM FROM THE LAV ON THE RISER DIAGRAM. PLEASE |
| | CORRELATE. SECTION 106.1.1. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| | WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID |
| | SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY |
| | ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU |
| | FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 805-6731 |
| | E-MAIL [email protected] |