| 2008-02-15 13:06:30 | *** DENIED2ND REVIEW*** |
| | |
| | ** PLEASE SEE SOME OF THE SAME COMMENTS FROM PREVIOUS |
| | REVIEW ARE STILL IN NEED OF ADDRESSING. PLEASE ALSO SEE |
| | THERE ARE SOME NEW COMMENTS BASED ON SUBMITTING OF NEW |
| | DOCUMENTS NOT ON PREVIOUS SUBMISSION. |
| | |
| | 1) NOTE: PLEASE SEE PREVIOUS REVIEW WHICH STATED THE |
| | ADDRESS ON THE PROJECT NEEDED COORDINATION WITH THE |
| | DETERMINED ADDRESS YET THE PLANS STILL SHOW ONLY |
| | *GEORGIA AVE* AND NO REFERENCE TO ACTUAL APPLIED |
| | ADDRESS LOCATION OF 605 GLENRIDGE. |
| | PLEASE BE SURE PLANS ARE UPDATED WITH THE ADDRESS AS |
| | APPLIED AND LOCATED. IF APPLICATION IS GOING TO BE MADE |
| | FOR CHANGES OF ADDRESS PLEASE CONTACT THE ADDRESSING |
| | REVIEWER. |
| | FBC 106.1.2, 106.5 |
| | FAC 61G1-16.004, 61G15-23.002 |
| | |
| | 2) NOTE: PLEASE SEE THE SUBMITTED ENERGY CALCULATIONS |
| | DO NOT COORDINATE WITH ALL OF THE LIGHTING FIXTURES ON |
| | PLANS FOR INTERIOR LIGHTING. |
| | PLEASE ALSO SEE VERSION SUBMITTED IS NOT ADOPTED IN THE |
| | FBC 13-400.3.A EVEN UNDER THE 2006 REVISIONS. PLEASE |
| | ADJUST. THE INPUT DATA REPORT WILL BE NOTED AS IDR. |
| | PLEASE SEE ONE EXAMPLE: PLANS SHOWS A TOTAL OF 10 TOTAL |
| | 250W INTERIOR LOW BAY FIXTURES YET THE INPUT DATA |
| | REPORT ONLY SHOWS 6? |
| | PLEASE ALSO SEE OTHER INTERIOR FIXTURES WHICH DO NOT |
| | CORRELATE WITH THE TOTAL NUMBER OF FIXTURES. THE LOW |
| | BAY 250VA FIXTURES ARE NOT THE ONLY ONES. |
| | PLEASE COORDINATE SPACES ON IDR WITH PLANS. |
| | PLEASE SEE 13-415.2.ABC.1, 13-415.2, 13-415.1.A FOR |
| | INTERIOR LOADS TO BE USED. PLEASE DETERMINE THE VA |
| | RATINGS OF BALLAST WITH ACTUAL OUTPUT AND USAGE BASED |
| | ON THE FIXTURE WHICH HAS BEEN NOTED BY CHANE |
| | ENGINEERING. |
| | PLEASE ALSO COORDINATE EXTERIOR LIGHTING PER |
| | 13-415.2.ABC.1.3. FOR EXAMPLE: PLANS SHOWS TWO FIXTURES |
| | ON LIGHT POLE AT REAR OF BUILDING YET THE IDR ONLY |
| | SHOWS ONE FIXTURE BEING FIGURED INTO CALCULATIONS. |
| | PLEASE SEE THE ENERGY CALCULATIONS STILL SHOW GEORGIA |
| | AVE, (SEE NOTE ABOVE WITH RESPECT TO ADDRESS) |
| | PLEASE SEE SPACE STILL SHOWN AS *RETAIL*. |
| | |
| | ** THE LIGHTING CALCULATIONS ON SHEET 7 SHOWS A HIGHER |
| | WATTAGE THAN ON ENERGY CALCULATIONS. (PLANS ARE OK) |
| | |
| | 3) NOTE: PLEASE SEE PLANS STILL INDICATE IN TITLE |
| | BLOCKS A *NEW INDUSTRIAL BUILDING* YET THE USE ON PLANS |
| | AND ENERGY CALCULATIONS DO NOT APPEAR TO SHOW THIS SAME |
| | OCCUPANCY. |
| | PLEASE COORDINATE WITH ALL DOCUMENTS AND ONCE FINAL |
| | OCCUPANCY USAGE IS DETERMINED, PLEASE ADJUST DESIGNS |
| | ACCORDINGLY. |
| | FBC 106.1 |
| | |
| | 4) NOTE: PLEASE VERIFY THE MAINS SHOWN ON RISER. SHOWS |
| | 2-POLE 200AMP MAINS/125AMP. THESE APPEAR THEY ARE |
| | 200AMP DISCONNECTS WITH 2-POLE 125AMP MAINS. |
| | THIS IS ONLY A MISPRINT OF DESIGNATION. |
| | 230, |
| | FBC 106.1.2 FOR COORDINATION. |
| | |
| | 5) NOTE: PLEASE SEE AS SOME OF THE COMMENTS WITH |
| | RESPECT TO REPEAT COMMENTS FOR CODE COMPLIANCE WERE |
| | ACTUALLY THE SAME CODE SECTIONS AND ITEMS FROM PREVIOUS |
| | REVIEW PLEASE SEE A NOTICE ONLY IS BEING GIVEN FOR FS |
| | 553.80(2)(B). |
| | THIS IS ONLY A NOTICE AT THIS TIME. |
| | |
| | ** PLEASE BE SURE TO ADDRESS COMMENTS. IF THERE ARE ANY |
| | QUESTIONS, ANY COMMENTS NOT TYPED IN A CLEAR MANOR OR |
| | NOT UNDERSTOOD IN ANYWAY PLEASE DO NOT HESITATE IN |
| | CONTACTING THIS REVIEWER. |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| | CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| | OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS |
| | INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT |
| | LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| | TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| | DELAYS. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |