| Date |
Text |
| 2008-03-11 11:04:47 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | FBCFLORIDA BUILDING CODE 2004 |
| | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING |
| | CODE |
| | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC* |
| | CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 FAC |
| | FLORIDA ADMINISTRATIVE CODE |
| | FSFLORIDA STATUTE |
| | |
| | FROM PREVIOUS LIST: |
| | |
| | 1.)INFORMATIONAL ONLY; SEPARATE PERMITS WILL BE |
| | REQUIRED.(THIS INCLUDES THE LIGHT POLE, |
| | |
| | 2.)ADDRESSED.PLEASE KEEP THE ORIGINAL SOILS REPORTS |
| | IN THE PERMIT PACKAGE WHEN RESUBMITTING. |
| | |
| | 3.)PRODUCT APPROVALS ARE TO BE APPROVED BY DESIGNER |
| | OF RECORD (SHOP DRAWING REVIEW STAMP OR LETTER), |
| | FBC*106.3.3. |
| | |
| | SEE OTHER COMMENTS; NEW PRODUCT APPROVALS WILL BE |
| | REQUIRED.PLEASE HAVE DOR REVIEW PRIOR TO |
| | RESUBMITTAL. |
| | |
| | |
| | 4.)INCLUDE A CODE SUMMARY; BUILDING TYPE FBC6, |
| | BUILDING HEIGHT AND AREA FBC5, SPRINKLER INFORMATION, |
| | OCCUPANCY CLASSIFICATION FBC 3 AND AREA PER OCCUPANCY. |
| | |
| | THE RESPONSE LETTER STATES THAT THIS IS ON SHEET 1, |
| | MISC. DATA.THIS IS NOT ON SHEET 1.SEE FBC106.3.5.1, |
| | MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS. DECLARE |
| | BUILDING TYPE FBC6, SPRINKLER INFORMATION (SPRINKLERED |
| | OR UNSPRINKLERED), OCCUPANCY CLASSIFICATION FBC CHAPTER |
| | 3, AREA PER OCCUPANCY. |
| | |
| | ALSO PLEASE NOTE THAT SHEET 1 IS DATED JAN 23, 2007, SO |
| | IS THE SAME SHEET AS SUBMITTED FIRST REVIEW. |
| | |
| | ZONING SITE DATA ON SHEET 1 STATES INDUSTRIAL, A NOTE |
| | ON THE BUILDING FLOOR PLAN STATES INDUSTRIAL BUILDING |
| | AND ALSO WAREHOUSE AND SHOWROOM.NOTE THAT INDUSTRIAL |
| | WOULD BE FACTORY FBC3065, WAREHOUSE IS STORAGE |
| | OCCUPANCY.PLEASE DECLARE OCCUPANCY CLASSIFICATION AND |
| | ALSO SUBCLASSIFICATION IF APPLICABLE AS PER FBC CHAPTER |
| | 3.NOTE THAT THE ENERGY CALCS ARE TO CORRELATE WITH |
| | THE PLANS.THE ENERGY CALCS STATE THAT TYPE IS RETAIL, |
| | WHICH WOULD BE MERCANTILE. |
| | |
| | 5.)IDENTIFY WHETHER THIS IS A SEPARATED USE, |
| | NONSEPARATED USE, ACCESSORY, INCIDENTAL?SEE FBC302. |
| | |
| | RESPONSE LETTER STATES THAT THIS IS SEPARATED USE |
| | CLASSIFICATION, BUT NO OCCUPANCY SEPARATIONS SHOWN. SEE |
| | FBC302.3.2 REGARDING SEPARATED USES.IF THIS IS A |
| | SEPARATED USE, BOTH HORIZONTAL AND VERTICAL SEPARATION |
| | WOULD BE REQUIRED BETWEEN SHOWROOM (MERCANTILE) AND THE |
| | OTHER AREA (F OR S). |
| | |
| | ALL FIRE RATINGS ARE TO BE SHOWN ON THE PLAN. |
| | |
| | 6.)SPECIFY MAXIMUM SLOPE AND MINIMUM WIDTH FOR THE |
| | SIDEWALK (ACCESSIBLE ROUTE) SHOWN ON SHEET 1, |
| | FBC11-4.1.2. |
| | |
| | PLEASE PUT INFORMATION ON THE RESPONSE LETTER ONTO THE |
| | PLAN.THE RESPONSE LETTER IS DISCARDED AND IS NOT TO |
| | BE USED TO SHOW CODE COMPLIANCE.ALL CODE REQUIREMENTS |
| | ARE TO BE SPECIFIC AND ARE TO BE ON THE PLAN, |
| | FBC*106.1.1. |
| | |
| | 7.)SHEET 1, SEE ATTACHED PARKING DETAIL.THE 2FT |
| | DIMENSION IS TO BE TO THE BACK OF THE WHEEL STOP, NOT |
| | THE FRONT.PLEASE REVISE. |
| | |
| | 8.)THIS APPEARS TO BE FOUR UNITS.SHOW REQUIRED |
| | TENANT SEPARATIONS FBC708.1(5).PROVIDE A DETAIL WITH |
| | EITHER TESTED ASSEMBLY OR CALCULATED FIRE RESISTANCE |
| | FBC 7. |
| | |
| | ALL INFORMATION REQUIRED TO SHOW CODE COMPLIANCE IS TO |
| | BE ON THE PLAN.PLEASE INCORPORATE THE INFORMATION ON |
| | THE RESPONSE LETTER INTO THE PLAN.PROVIDE THE UL |
| | ASSEMBLY DETAIL ON THE PLAN.THE FLOOR PLAN IS TO SHOW |
| | ALL REQUIRED FIRE RESISTANCE RATED WALLS SO THAT OTHER |
| | TRADES WILL BE AWARE OF THESE REQUIREMENTS WITHOUT |
| | REFERRING TO CORRESPONDING WALL DETAILS. |
| | |
| | 9.)NO MECHANICAL PLANS WERE SUBMITTED, BUT ENERGY |
| | CALCS WERE SUBMITTED SHOWING AIR CONDITIONED SPACE. |
| | SHOW COMPLIANCE WITH FBC716. |
| | |
| | ARCHITECT'S RESPONSE STATES THAT THIS COMMENT SEEMS NOT |
| | TO BE APPLICABLE.MY APOLOGIES FOR ANY CONFUSION. |
| | PENETRATIONS THROUGH RATED WALLS WILL REQUIRE FIRE |
| | DAMPERS, REQUIREMENT INCLUDED IN THE CODE SECTION |
| | REFERENCED. FLOOR PLAN IS TO SHOW ALL REQUIRED FIRE |
| | RESISTANCE RATINGS, PARTIALLY SO THAT THE MECHANICAL |
| | CONTRACTOR AND INSPECTORS KNOW WHERE FIRE DAMPERS WILL |
| | BE REQUIRED. |
| | |
| | 10.)DECLARE OCCUPANT LOAD, FBC1004, FBC TABLE |
| | 1004.1.2. |
| | |
| | RESPONSE LETTER STATES TO SEE MISC DATA, SHEET 1.SAME |
| | SHEET SUBMITTED, COMMENT NOT ADDRESSED. |
| | |
| | 11.)SHOW COMPLIANCE WITH FBC TABLE 601, FBC TABLE |
| | 602. PROVIDE A DETAIL FOR ALL FIRE RATED WALLS, EITHER |
| | TESTED ASSEMBLY OR CALCULATED FIRE RESISTANCE FBC 7. |
| | ALL FIRE RESISTANCE RATING REQUIREMENTS ARE TO BE |
| | INCLUDED ON THE FLOOR PLAN. |
| | |
| | 12.)ADDRESSED. |
| | |
| | 13.)NON IMPACT PRODUCT APPROVALS WERE SUBMITTED.USE |
| | OF REMOVABLE SHUTTERS ON COMMERCIAL PROPERTIES REQUIRES |
| | APPROVAL FROM THE BUILDING OFFICIAL.IF YOU ARE |
| | PROPOSING TO USE REMOVABLE SHUTTERS, SUBMIT A HURRICANE |
| | INSTALLATION PLAN, SEE ATTACHED POLICY, ITEM 13. |
| | PROVIDE PRODUCT APPROVALS AND COMPLETE AN INSTALLATION |
| | SCHEDULE.TO AVOID PERMIT DELAYS, SUBMIT THE |
| | INSTALLATION PLAN PRIOR TO RESUBMITTAL OF THE PLANS. |
| | THIS MAY BE DONE BY EITHER EMAIL OR SUBMITTED AT THE |
| | FRONT COUNTER. |
| | |
| | **COMMENT REVISED 3/20 - FIXED IMPACT PROTECTION IS TO |
| | BE TESTED AS SUCH.PLEASE ADDRESS.** |
| | |
| | |
| | 14.)FOR THE FLAT DECK, SELECT THE APPROVED ASSEMBLY |
| | YOU ARE USING.THIS MAY BE DONE AT THE TIME OF ROOF |
| | PERMIT APPLICATION. |
| | |
| | 15 .)FOR THE FLAT DECK, SEE GENERAL LIMITATION #7. |
| | CALCULATIONS BY AN ARCHITECT, ENGINEER, OR REGISTERED |
| | ROOF CONSULTANT REQUIRED FOR ENHANCED FASTENING.THIS |
| | MAY BE DONE AT TIME OF ROOF PERMIT APPLICATION. |
| | |
| | 16-17.)ADDRESSED. |
| | |
| | 18.)SEE FBC1907.7.1 AND SHEET 5, ITEM 10, 1.5 INCH |
| | CONCRETE COVER REQUIRED AT EXTERIOR SLABS. |
| | |
| | PLEASE REVISE.THERE WAS A TYPO DUE TO TRANSFER OF |
| | DATA ON THE ORIGINAL LIST.PLEASE SEE FBC1907.7.1 AND |
| | REVISE SHEET 5.THE SLUMP REQUIREMENT WAS CHANGED, |
| | PLEASE CHECK ALL CONCRETE COVERAGE REQUIREMENTS AND |
| | REVISE AS NECESSARY. |
| | |
| | 19.)ACCESSIBLE PARKING IS TO BE ON THE SHORTEST |
| | ROUTE, FBC11-4.6.2.THE PLANS SHOW THE LONGEST ROUTE |
| | FROM THIS LOCATION.PLEASE REVISE. |
| | |
| | ARCHITECT?S RESPONSE IS NOTED.PLEASE SHOW PARKING LOT |
| | SLOPE, FBC11-4.6.2.THE CODE REQUIRES THE SHORTEST |
| | SAFELY ACCESSIBLE ROUTE, WHICH WOULD BE THE REAR |
| | ENTRANCES.THIS CAN BE SATISFIED BY THE MAXIMUM CROSS |
| | SLOPE NOTED ON THE PLAN. |
| | |
| | 20.)FEES WILL BE DETERMINED AFTER OCCUPANCY |
| | CLASSIFICATION IS ESTABLISHED. |
| | |
| | NEW COMMENTS: |
| | |
| | 21.IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY. THE |
| | PLANS MUST BE STAMPED AND THE RECEIPT ATTACHED TO THE |
| | APPLICATION.PLEASE CALL 233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | 22.SEE FBC11-4.29.5, DETECTABLE WARNINGS AT HAZARDOUS |
| | VEHICULAR AREAS.PLEASE SHOW LOCATION ON THE SITE |
| | PLAN, DRIVEWAY APPROACH. |
| | |
| | 23.SEE ELECTRIC COMMENTS REGARDING THE ADDRESS. |
| | PLEASE INCLUDE CORRECT ADDRESS ON THE PLANS, FBC106*. |
| | |
| | 24.SEE ATTACHED FS553.80(2)(B). |