Plan Review Notes
Plan Review Notes For Permit 07100724
Permit Number 07100724
Review Stop P
Sequence Number 1
Notes
Date Text
2007-12-07 17:56:38DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. INDICATE CODE REFERENCE BY WHICH PLANS WERE
 DESIGNED. SECTION 106.1.1.
  
 2. INDICATE OCCUPANCE OF BUILDING. SECTION 106.1.1.
  
 3. SUBMIT CALCULATIONS FOR THE ROOF DRAINAGE. SHOW THE
 SQUARE FOOTAGE OF THE ROOF AND SHOW 1/2 AREA OF ALL
 VERTICAL WALLS INCLUDING PARAPTES ADDED TO ROOF AREA.
 SECTION 1106.
  
 4. TABLE 403.1 REQUIRES A SERVICE SINK IN EACH SPACE.
 PLEASE INDICATE THE LOCATION OF THE SERVICE SINK.
  
 5. SUBMIT A DETAIL FOR THE DRINKING FOUNTAINS SHOWING
 COMPLIANCE WITH SECTION 11-4.15 WITH ALL SUBSECTION AS
 WELL AS SECTION 11-4.1.3(10)(A) PROVISIONS FOR THOSE
 WHO HAVE TROUBLE BENDING OR STOOPING.
  
 6. SHT 4 SHOW THE GUTTER & DOWNSPOUT SIZES PER TABLES
 1106.3 & 1106.6. INDICATE THE SLOPE OF THE GUTTER AND
 SHOW THE HIGH POINT OF THE GUTTER.
  
 7. SHT 4 SHOWS 1/4"/FT SLOPE, BUT THE TOTAL DROP OVER
 53' WOULD REQUIRED 13.25". ONLY 12" DROP IS SHOWN.
 PLEASE CLAIRFY. SECTION 106.1.1.
  
 8. SHT 8A SERVICE SINK WIL BE REQUIRED TO BE SHOWN ON
 THE SANITARY ISOMETRIC AND ON THE WATER ISOMETRIC. HOT
 WATER WILL BE REQUIRED TO THE SERVICE SINK PER SECTION
 607.1. PLEASE SHOW ON RISERS. SECTION 106.3.5.1.3.
  
 9. SHT 8 WATER ISOMETRIC ENTERS THE BUILDING AS 1", BUT
 IS SHOWN AS 1/2" AT THE TOP OF THE FIRST RISER, THEN
 BACK TO 3/4". PLEASE CLARIFY. SECTION 106.1.1.
  
 10. SHT 8 AN RPZV BACKFLOW IS REQUIRED ON THE WATER
 SERVICE TO THE BUILDING. SECTION 608.13.2.
  
 11. SHT 1 OF 1 THE ENGINEER SHALL LEGIBLY INDICATE
 THEIR LICENSE NUMBER ON THE SHEET. FAC 61G15-23.002(2)
 & FS 471.025.
  
 12. AN IRRIGATION PERMIT AND PLANS WILL BE REQUIRED.
 SECTION 105.1.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID
 SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY
 ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved