Plan Review Notes
Plan Review Notes For Permit 07100724
Permit Number 07100724
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2007-11-14 10:49:521. BUILDING ADDRESS REQUIRED ON PROPER ELEVATION. A
 MINIMUM OF AT LEAST 6" HIGH NUMBERS WITH 1" WIDE
 NUMBERS ARE REQUIRED.
  
 2. PLEASE PROVIDE HOURLY RATING ON TENANT DEMISING
 PARTITION SECTION 2/4 ON PAGE 4.
  
 3. ARE THERE ANY EMERGENCY LIGHT CONTAINED WITHIN THE
 SPACES.
  
 4. ARE THERE ANY PORTABLE FIRE EXTINGUISHERS LOCATED
 WITHIN THE TENANT SPACES.
  
 5. IS THERE ANY FIRE RATING BETWEEN THE WAREHOUSE AREA
 AND THE SHOWROOMS.
  
 6. IS ANY STORAGE OF FLAMMABLE,COMBUSTIBLE,TOXIC,
 CORROSIVE, OR POISONOUS SOLIDS, LIQUIDS, OR GASES
 PLANNED AT THE SITE.
  
 7. PLEASE INDICATE INTERIOR FINISH CLASSIFICATIONS FOR
 WALLS AND CEILINGS.
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION
 804-4709 PHONE
 804-4774 FAX