| 2007-11-26 15:36:18 | ** DENIED** |
| | |
| | |
| | |
| | 1) NOTE:PLEASE KNOW THAT ANY PERMIT APPLICATIONS |
| | WHICH ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES |
| | PROJECTS UNDER THE NEW CODES ADOPTED BY THE STATE. |
| | PLEASE SEE THAT THIS SHALL INCLUDE 2006/2007 REVISIONS |
| | TO THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70. |
| | PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH MAY |
| | AFFECT DESIGNS FOR ALL TRADES. |
| | PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS |
| | REVIEWER AT A MINIMUM. |
| | 2004 FBC W/ 2006/07 REVISIONS |
| | 2005 NFPA-70 |
| | 2002 NFPA-72 |
| | 2003 NFPA-101 |
| | |
| | ** ELECTRICAL PLAN NOTES MENTIONS *PALM BEACH COUNTY |
| | AMENDMENTS* HOWEVER THIS PROJECT IS LOCATED IN THE CITY |
| | OF WEST PALM BEACH.PLEASE ADJUST. |
| | |
| | 2) NOTE:PLEASE SEE ADDRESS OF LOCATION AS APPLIED IS |
| | 605 GLENRIDGE DR. |
| | PLEASE BE SURE TO ADJUST ALL PLANS, AND SUPPORTING |
| | DOCUMENTATION. |
| | PLEASE DO NOT ATTACH/STAPLE SUPPORTING DOCUMENTATION |
| | DOWN THE LEFT HAND SIDE OF PLANS. |
| | FBC 106.1.2, 106.3 |
| | |
| | 3) NOTE: PLEASE COMPLETE LOAD INFORMATION ON PANELS. |
| | THESE ARE CURRENTLY SHOWN WITH ASTERISK. |
| | NEC 220,408.4 |
| | FBC 106.3.5.1.2 |
| | |
| | 4) NOTE: PLEASE SEE PLANS MENTIONS NEW *INDUSTRIAL |
| | BUILDING* HOWEVER ENERGY CALCULATIONS AND OTHER PARTS |
| | OF PLANS MENTIONS NEW RETAIL/MERCANTILE OCCUPANCY. |
| | PLEASE SEE FOR OTHER EXAMPLE: LIGHT LEGEND ON |
| | ELECTRICAL PLANS INDICATE 175W AND 250W FIXTURES, AND |
| | THE HIGHEST WATTAGE OF FIXTURES ON THE IDR IS 75W. |
| | PLEASE CORRELATE. |
| | PLEASE CORRELATE ALL LIGHTING ON PLANS WITH THAT OF THE |
| | SUBMITTED ENERGY CALCULATIONS. FOR EXAMPLE: PLEASE SEE |
| | SITE LIGHTS WHICH ARE ON PLANS BUT NOT ON EXTERIOR |
| | LIGHTING IN THE INPUT DATA REPORT. |
| | PLEASE SEE THE LIGHTING POWER USAGE ON PLANS IS HIGHER |
| | THAN THAT IN THE IDR ALSO. |
| | PLEASE COORDINATE. |
| | 13-415.2, 13-415.1.A |
| | |
| | 5) NOTE: PLEASE SEE SIGN CIRCUIT VA IS REQUIRED TO BE A |
| | MINIMUM OF 1200VA. THE AMPERAGE LOAD ON PANEL SCHEDULE |
| | IS SHOWN LESS THAN THAT FOR THE MINIMUM VA. |
| | |
| | 6) NOTE: PLEASE SEE FOOTER STEEL IS REQUIRED FOR |
| | GROUNDING ELECTRODE SYSTEM. |
| | (SHOWS BUILDING STEEL WHICH IS SEPARATE). |
| | |
| | 7) NOTE: PLEASE SUBMIT WIND LOAD CALCULATIONS AND |
| | INFORMATION FOR NEW SITE POLE. |
| | PLEASE KNOW, STRUCTURAL REVIEW WILL BE DONE BY BUILDING |
| | REVIEWER. |
| | PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |