Plan Review Notes
Plan Review Notes For Permit 07100724
Permit Number 07100724
Review Stop E
Sequence Number 1
Notes
Date Text
2007-11-26 15:36:18** DENIED**
  
  
  
 1) NOTE:PLEASE KNOW THAT ANY PERMIT APPLICATIONS
 WHICH ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES
 PROJECTS UNDER THE NEW CODES ADOPTED BY THE STATE.
 PLEASE SEE THAT THIS SHALL INCLUDE 2006/2007 REVISIONS
 TO THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70.
 PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH MAY
 AFFECT DESIGNS FOR ALL TRADES.
 PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS
 REVIEWER AT A MINIMUM.
 2004 FBC W/ 2006/07 REVISIONS
 2005 NFPA-70
 2002 NFPA-72
 2003 NFPA-101
  
 ** ELECTRICAL PLAN NOTES MENTIONS *PALM BEACH COUNTY
 AMENDMENTS* HOWEVER THIS PROJECT IS LOCATED IN THE CITY
 OF WEST PALM BEACH.PLEASE ADJUST.
  
 2) NOTE:PLEASE SEE ADDRESS OF LOCATION AS APPLIED IS
 605 GLENRIDGE DR.
 PLEASE BE SURE TO ADJUST ALL PLANS, AND SUPPORTING
 DOCUMENTATION.
 PLEASE DO NOT ATTACH/STAPLE SUPPORTING DOCUMENTATION
 DOWN THE LEFT HAND SIDE OF PLANS.
 FBC 106.1.2, 106.3
  
 3) NOTE: PLEASE COMPLETE LOAD INFORMATION ON PANELS.
 THESE ARE CURRENTLY SHOWN WITH ASTERISK.
 NEC 220,408.4
 FBC 106.3.5.1.2
  
 4) NOTE: PLEASE SEE PLANS MENTIONS NEW *INDUSTRIAL
 BUILDING* HOWEVER ENERGY CALCULATIONS AND OTHER PARTS
 OF PLANS MENTIONS NEW RETAIL/MERCANTILE OCCUPANCY.
 PLEASE SEE FOR OTHER EXAMPLE: LIGHT LEGEND ON
 ELECTRICAL PLANS INDICATE 175W AND 250W FIXTURES, AND
 THE HIGHEST WATTAGE OF FIXTURES ON THE IDR IS 75W.
 PLEASE CORRELATE.
 PLEASE CORRELATE ALL LIGHTING ON PLANS WITH THAT OF THE
 SUBMITTED ENERGY CALCULATIONS. FOR EXAMPLE: PLEASE SEE
 SITE LIGHTS WHICH ARE ON PLANS BUT NOT ON EXTERIOR
 LIGHTING IN THE INPUT DATA REPORT.
 PLEASE SEE THE LIGHTING POWER USAGE ON PLANS IS HIGHER
 THAN THAT IN THE IDR ALSO.
 PLEASE COORDINATE.
 13-415.2, 13-415.1.A
  
 5) NOTE: PLEASE SEE SIGN CIRCUIT VA IS REQUIRED TO BE A
 MINIMUM OF 1200VA. THE AMPERAGE LOAD ON PANEL SCHEDULE
 IS SHOWN LESS THAN THAT FOR THE MINIMUM VA.
  
 6) NOTE: PLEASE SEE FOOTER STEEL IS REQUIRED FOR
 GROUNDING ELECTRODE SYSTEM.
 (SHOWS BUILDING STEEL WHICH IS SEPARATE).
  
 7) NOTE: PLEASE SUBMIT WIND LOAD CALCULATIONS AND
 INFORMATION FOR NEW SITE POLE.
 PLEASE KNOW, STRUCTURAL REVIEW WILL BE DONE BY BUILDING
 REVIEWER.
 PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]