Plan Review Notes
Plan Review Notes For Permit 07100724
Permit Number 07100724
Review Stop B
Sequence Number 1
Notes
Date Text
2007-11-09 15:38:40****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.)INFORMATIONAL ONLY; SEPARATE PERMITS WILL BE
 REQUIRED.
  
 2.)PROVIDE A SOILS INVESTIGATION REPORT, FBC1802.2.
  
 3.)PRODUCT APPROVALS ARE TO BE APPROVED BY DESIGNER
 OF RECORD (SHOP DRAWING REVIEW STAMP OR LETTER),
 FBC*106.3.3.
  
 4.)INCLUDE A CODE SUMMARY; BUILDING TYPE FBC6,
 BUILDING HEIGHT AND AREA FBC5, SPRINKLER INFORMATION,
 OCCUPANCY CLASSIFICATION FBC 3 AND AREA PER OCCUPANCY.
  
 5.)IDENTIFY WHETHER THIS IS A SEPARATED USE,
 NONSEPARATED USE, ACCESSORY, INCIDENTAL?SEE FBC302.
  
 6.)SPECIFY MAXIMUM SLOPE AND MINIMUM WIDTH FOR THE
 SIDEWALK (ACCESSIBLE ROUTE) SHOWN ON SHEET 1,
 FBC11-4.1.2.
  
 7.)THERE IS A CONFLICT ON THE PARKING DETAIL FOR THE
 CONCRETE STOP LOCATION ON SHEET 1 PREPARED BY ARCHITECT
 (BELL) AND SHEET 1 PREPARED BY ENGINEER (MCCARTY).
  
 8.)THIS APPEARS TO BE FOUR UNITS.SHOW REQUIRED
 TENANT SEPARATIONS FBC708.1(5).PROVIDE A DETAIL WITH
 EITHER TESTED ASSEMBLY OR CALCULATED FIRE RESISTANCE
 FBC 7.
  
 9.)NO MECHANICAL PLANS WERE SUBMITTED, BUT ENERGY
 CALCS WERE SUBMITTED SHOWING AIR CONDITIONED SPACE.
 SHOW COMPLIANCE WITH FBC716.
  
 10.)DECLARE OCCUPANT LOAD, FBC1004, FBC TABLE
 1004.1.2.
  
 11.)SHOW COMPLIANCE WITH FBC TABLE 601, FBC TABLE
 602. PROVIDE A DETAIL FOR ALL FIRE RATED WALLS, EITHER
 TESTED ASSEMBLY OR CALCULATED FIRE RESISTANCE FBC 7.
 ALL FIRE RESISTANCE RATING REQUIREMENTS ARE TO BE
 INCLUDED ON THE FLOOR PLAN.
  
 12.)BUILDING SIZE IS TO COMPLY WITH FBC503.ENGINEER
 STATES ON SHEET 1 THAT THIS IS A 44,448 SF BUILDING.
 PLEASE CORRELATE WITH OTHER INFORMATION (PLANS, ENERGY
 CALCS).
  
 13.)NON IMPACT PRODUCT APPROVALS WERE SUBMITTED.USE
 OF REMOVABLE SHUTTERS ON COMMERCIAL PROPERTIES REQUIRES
 APPROVAL FROM THE BUILDING OFFICIAL.IF YOU ARE
 PROPOSING TO USE REMOVABLE SHUTTERS, SUBMIT A HURRICANE
 INSTALLATION PLAN, SEE ATTACHED POLICY, ITEM 13.
 PROVIDE PRODUCT APPROVALS AND COMPLETE AN INSTALLATION
 SCHEDULE.TO AVOID PERMIT DELAYS, SUBMIT THE
 INSTALLATION PLAN PRIOR TO RESUBMITTAL OF THE PLANS.
 THIS MAY BE DONE BY EITHER EMAIL OR SUBMITTED AT THE
 FRONT COUNTER.
  
 14.)FOR THE FLAT DECK, SELECT THE APPROVED ASSEMBLY
 YOU ARE USING.THIS MAY BE DONE AT THE TIME OF ROOF
 PERMIT APPLICATION.
  
 15 .)FOR THE FLAT DECK, SEE GENERAL LIMITATION #7.
 CALCULATIONS BY AN ARCHITECT, ENGINEER, OR REGISTERED
 ROOF CONSULTANT REQUIRED FOR ENHANCED FASTENING.THIS
 MAY BE DONE AT TIME OF ROOF PERMIT APPLICATION.
  
 16.)DOCUMENTS PREPARED BY AN ENGINEER AND SUBMITTED
 FOR PUBLIC RECORD ARE TO BE SIGNED, SEALED, DATED
 ORIGINALS FS471.025 (DRAINAGE CALCS).
  
 17.)THE BATHROOM DOOR APPEARS TO SWING INTO THE
 REQUIRED CLEAR FLOOR SPACE FOR THE WATER COOLER.
 PLEASE SHOW CLEAR FLOOR SPACE ON THE PLAN FBC FIGURE
 11-27.
  
 18.)SEE FBC1907.7.1 AND SHEET 5, ITEM 10, 1 ? INCH
 CONCRETE COVER REQUIRED AT EXTERIOR SLABS.
  
 19.)ACCESSIBLE PARKING IS TO BE ON THE SHORTEST
 ROUTE, FBC11-4.6.2.THE PLANS SHOW THE LONGEST ROUTE
 FROM THIS LOCATION.PLEASE REVISE.
  
 20.)FEES WILL BE DETERMINED AFTER OCCUPANCY
 CLASSIFICATION IS ESTABLISHED.
  