| 2007-11-09 15:38:40 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBCFLORIDA BUILDING CODE 2004 |
| | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING |
| | CODE |
| | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL |
| | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 |
| | |
| | FAC FLORIDA ADMINISTRATIVE CODE |
| | FSFLORIDA STATUTE |
| | |
| | 1.)INFORMATIONAL ONLY; SEPARATE PERMITS WILL BE |
| | REQUIRED. |
| | |
| | 2.)PROVIDE A SOILS INVESTIGATION REPORT, FBC1802.2. |
| | |
| | 3.)PRODUCT APPROVALS ARE TO BE APPROVED BY DESIGNER |
| | OF RECORD (SHOP DRAWING REVIEW STAMP OR LETTER), |
| | FBC*106.3.3. |
| | |
| | 4.)INCLUDE A CODE SUMMARY; BUILDING TYPE FBC6, |
| | BUILDING HEIGHT AND AREA FBC5, SPRINKLER INFORMATION, |
| | OCCUPANCY CLASSIFICATION FBC 3 AND AREA PER OCCUPANCY. |
| | |
| | 5.)IDENTIFY WHETHER THIS IS A SEPARATED USE, |
| | NONSEPARATED USE, ACCESSORY, INCIDENTAL?SEE FBC302. |
| | |
| | 6.)SPECIFY MAXIMUM SLOPE AND MINIMUM WIDTH FOR THE |
| | SIDEWALK (ACCESSIBLE ROUTE) SHOWN ON SHEET 1, |
| | FBC11-4.1.2. |
| | |
| | 7.)THERE IS A CONFLICT ON THE PARKING DETAIL FOR THE |
| | CONCRETE STOP LOCATION ON SHEET 1 PREPARED BY ARCHITECT |
| | (BELL) AND SHEET 1 PREPARED BY ENGINEER (MCCARTY). |
| | |
| | 8.)THIS APPEARS TO BE FOUR UNITS.SHOW REQUIRED |
| | TENANT SEPARATIONS FBC708.1(5).PROVIDE A DETAIL WITH |
| | EITHER TESTED ASSEMBLY OR CALCULATED FIRE RESISTANCE |
| | FBC 7. |
| | |
| | 9.)NO MECHANICAL PLANS WERE SUBMITTED, BUT ENERGY |
| | CALCS WERE SUBMITTED SHOWING AIR CONDITIONED SPACE. |
| | SHOW COMPLIANCE WITH FBC716. |
| | |
| | 10.)DECLARE OCCUPANT LOAD, FBC1004, FBC TABLE |
| | 1004.1.2. |
| | |
| | 11.)SHOW COMPLIANCE WITH FBC TABLE 601, FBC TABLE |
| | 602. PROVIDE A DETAIL FOR ALL FIRE RATED WALLS, EITHER |
| | TESTED ASSEMBLY OR CALCULATED FIRE RESISTANCE FBC 7. |
| | ALL FIRE RESISTANCE RATING REQUIREMENTS ARE TO BE |
| | INCLUDED ON THE FLOOR PLAN. |
| | |
| | 12.)BUILDING SIZE IS TO COMPLY WITH FBC503.ENGINEER |
| | STATES ON SHEET 1 THAT THIS IS A 44,448 SF BUILDING. |
| | PLEASE CORRELATE WITH OTHER INFORMATION (PLANS, ENERGY |
| | CALCS). |
| | |
| | 13.)NON IMPACT PRODUCT APPROVALS WERE SUBMITTED.USE |
| | OF REMOVABLE SHUTTERS ON COMMERCIAL PROPERTIES REQUIRES |
| | APPROVAL FROM THE BUILDING OFFICIAL.IF YOU ARE |
| | PROPOSING TO USE REMOVABLE SHUTTERS, SUBMIT A HURRICANE |
| | INSTALLATION PLAN, SEE ATTACHED POLICY, ITEM 13. |
| | PROVIDE PRODUCT APPROVALS AND COMPLETE AN INSTALLATION |
| | SCHEDULE.TO AVOID PERMIT DELAYS, SUBMIT THE |
| | INSTALLATION PLAN PRIOR TO RESUBMITTAL OF THE PLANS. |
| | THIS MAY BE DONE BY EITHER EMAIL OR SUBMITTED AT THE |
| | FRONT COUNTER. |
| | |
| | 14.)FOR THE FLAT DECK, SELECT THE APPROVED ASSEMBLY |
| | YOU ARE USING.THIS MAY BE DONE AT THE TIME OF ROOF |
| | PERMIT APPLICATION. |
| | |
| | 15 .)FOR THE FLAT DECK, SEE GENERAL LIMITATION #7. |
| | CALCULATIONS BY AN ARCHITECT, ENGINEER, OR REGISTERED |
| | ROOF CONSULTANT REQUIRED FOR ENHANCED FASTENING.THIS |
| | MAY BE DONE AT TIME OF ROOF PERMIT APPLICATION. |
| | |
| | 16.)DOCUMENTS PREPARED BY AN ENGINEER AND SUBMITTED |
| | FOR PUBLIC RECORD ARE TO BE SIGNED, SEALED, DATED |
| | ORIGINALS FS471.025 (DRAINAGE CALCS). |
| | |
| | 17.)THE BATHROOM DOOR APPEARS TO SWING INTO THE |
| | REQUIRED CLEAR FLOOR SPACE FOR THE WATER COOLER. |
| | PLEASE SHOW CLEAR FLOOR SPACE ON THE PLAN FBC FIGURE |
| | 11-27. |
| | |
| | 18.)SEE FBC1907.7.1 AND SHEET 5, ITEM 10, 1 ? INCH |
| | CONCRETE COVER REQUIRED AT EXTERIOR SLABS. |
| | |
| | 19.)ACCESSIBLE PARKING IS TO BE ON THE SHORTEST |
| | ROUTE, FBC11-4.6.2.THE PLANS SHOW THE LONGEST ROUTE |
| | FROM THIS LOCATION.PLEASE REVISE. |
| | |
| | 20.)FEES WILL BE DETERMINED AFTER OCCUPANCY |
| | CLASSIFICATION IS ESTABLISHED. |
| | |