| Date |
Text |
| 2007-11-06 16:25:17 | DENIED |
| | REFERENCE: |
| | ** FBC-2004 WITH 05 & 06 REVISIONS, SECTIONS 424.2 & |
| | R4101 SWIMMING POOLS. |
| | ** FBC-2004 WITH 05 & 06 REVISIONS, PLUMBING. |
| | ** FBC-2004 CHAPTER 1, THE CITY OF |
| | WEST PALM BEACH AMENDMENTS. |
| | ** FLORIDA ADMINISTRATIVE CODE (FAC). |
| | ** FLORIDA STATUTES (FS). |
| | |
| | THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR |
| | PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE: |
| | |
| | 1. THE EXPIRED PERMIT #06061300 DID NOT HAVE THE 4 HP |
| | BADU JET PUMP SYSTEM APPROVED AS A REVISION. PLEASE |
| | PROVIDE THE FOLLOWING INFORMATION FOR THIS SYSTEM. |
| | |
| | A} PROVIDE A DETAIL OF THE 4 HP BADU JET PUMP SYSTEM |
| | ON THE RESUBMITTED PLANS WITH ITEMS "B" THRU "E" |
| | INDICATED ON THE DETAIL. ALSO SUBMIT TWO COPIES OF |
| | MANUFACTURER'S SPECIFICATIONS OF THE PROPOSED 4 HP BADU |
| | JET PUMP SYSTEM. |
| | |
| | B} FBC-2004 SEC 424.2.6.6, OR FBCR-2004 |
| | SEC R4101.6.6 ENTRAPMENT PROTECTION FOR |
| | SUCTION INLETS. (DETAIL REQUIRED). |
| | |
| | C} FBC-2004 424.2.6.6.2, OR FBCR-2004 |
| | SEC R4101.6.6.2 SHOW COMPLIANCE WITH |
| | ANSI/ASME A112.19.8M. PROVIDE MODEL |
| | NUMBER AND MANUF INFO FOR VAC LOCK. |
| | (GIVE DETAIL, SUBMITTAL OR ADD TO NOTES). |
| | |
| | D} FBC-2004424.2.6.6.3, OR FBCR-2004 |
| | SEC R4101.6.6.3 (1,2,3) ENTRAPMENT |
| | AVOIDANCE. (DETAIL REQUIRED). |
| | |
| | E} FBC-2004 SEC.424.2.6.6.4, OR |
| | FBCR-2004 SEC. R4101.6.6.4 MINIMUM OF |
| | TWO SUCTION INLETS SHALL BE PROVIDED FOR |
| | EACH PUMP. SEPARATED BY A MINIMUM OF 3 |
| | FEET OR LOCATED ON TWO DIFFERENT PLANES. |
| | (DETAIL REQUIRED). |
| | |
| | 2. TWO COPIES OF THE 400,000 BTU POOL HEATER ARE |
| | REQUIRED ON THE RESUBMITTAL WITH THE FOLLOWING |
| | INFORMATION. |
| | |
| | A} FBC-2004 SEC. 424.2.14.1, OR |
| | FBCR-2004 SEC. R4101.14.1 SWIMMING POOL |
| | WATER HEATERS SHALL BEAR THE LABEL OF A |
| | RECOGNIZED TESTING AGENCY. (MANUFACTURE |
| | SHEETS REQUIRED, PLEASE SUBMIT) |
| | |
| | B} FBC-2004 SEC. 424.2.14.2, OR |
| | FBCR-2004 SEC. R4101.14.2 WATER |
| | RETENTION, PROVIDE A POSITIVE MEANS OF |
| | RETAINING WATER IN THE HEATER WHEN PUMP |
| | IS SHUT OFF.(MANUFACTURE SHEETS |
| | REQUIRED, PLEASE SUBMIT) |
| | |
| | 3. THE VALUE ON THIS PERMIT APPLICATION IS TO LOW THE |
| | EXPIRED PERMIT APPLICATION VALUE WAS $37,100 AND THATS |
| | NOT EVEN ADDING THE ADDED COST OF THE 4 HP BADU JET |
| | PUMP SYSTEM PER FBC-2004, CHAPTER 1, SECTION |
| | 108.3, BUILDING PERMIT VALUATION: IF IN |
| | THE OPINION OF THE BUILDING OFFICIAL, |
| | THE CLAIMED VALUATION OF THE BUILDING, |
| | ALTERATION, STRUCTURE, ELECTRICAL, GAS |
| | MECHANICAL OR PLUMBING SYSTEMS APPEARS |
| | TO BE UNDERESTIMATED ON THE APPLICATION, |
| | THE PERMIT SHALL BE DENIED. FOR |
| | PERMITTING PURPOSES, VALUATION OF |
| | BUILDINGS AND SYSTEMS SHALL BE TOTAL |
| | REPLACEMENT VALUE TO INCLUDE STRUCTURAL, |
| | ELECTRIC, PLUMBING, MECHANICAL, INTERIOR |
| | FINISH, NORMAL SITE WORK (EXCAVATION AND |
| | BACKFILL FOR BUILDINGS), ARCHITECTURAL |
| | AND DESIGN FEES, MARKETING COSTS, |
| | OVERHEAD AND PROFIT; EXCLUDING ONLY LAND |
| | VALUE. VALUATION REFERENCES MAY INCLUDE |
| | THE LATEST PUBLISHED DATA OF NATIONAL |
| | CONSTRUCTION COST ANALYSIS SERVICES (MARSHALL-SWIFT, |
| | MEANS ECT.) WITH |
| | REGIONAL ADJUSTMENTS FOR LOCATION AS |
| | PUBLISHED BY INTERNATIONAL CODE |
| | CONGRESS. |
| | **NOTE: CORRECT THE VALUE ON THE PERMIT APPLICATION AND |
| | PAY THE DIFFERENCE PRIOR TO RESUBMITTING. |
| | |
| | END OF COMMENTS: |
| | |
| | REVIEW BY: MIKE PERSON |
| | PLUMBING PLANS EXAMINER |
| | (561) 805-6730 |
| | FAX (561) 805-6731 |
| | E-MAIL: [email protected] |