2008-07-28 09:22:20PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) THE EQUIPMENT SCHEDULE IS NOW MISSING FROM THE NEW
 MECHANICAL PLAN. PLEASE ADD AN EQUIPMENT SCHEDULE TO
 THE MECHANICAL PLANS SHOW THE MANUFACTURE, MODEL
 NUMBER, SEER, ETC. AND ALL OTHER PERTINENT INFORMATION,
 SEE WPB AMEND. 106.3.5.4.
  
 2) PLEASE SHOW THE BATHROOM EXHAUST FANS ON THE
 MECHANICAL PLAN AS THEY ARE ON THE ELECTRICAL PLAN AND
 PER 2004 FBC/R M1506.1 THE MASTER BATHROOM SHOWER AREA
 IS REQUIRED.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]