Plan Review Notes
Plan Review Notes For Permit 07100688
Permit Number 07100688
Review Stop E
Sequence Number 4
Notes
Date Text
2008-07-28 08:36:27 
 ** DENIED4TH REVIEW **
  
 *** SOME NOTES FROM PREVIOUS REVIEW ARE STILL THE SAME.
 SOME ARE NOW NEW DUE TO REVISED PLANS.
  
 1) NOTE: PLEASE SEE EQUIPMENT GROUNDING CONDUCTOR IS
 STILL MISSING AFTER THE FIRST MEANS OF DISCONNECT TO
 THE 150 AMP SUB PANEL.
 250.110,250.122
  
 2) NOTE: PLEASE SEE THE RISER STILL DOES NOT SHOW ANY
 GROUNDING ELECTRODE SYSTEM AT THE MAIN HOUSE AS
 REQUIRED PER 250.50,250.32
  
 3) NOTE: THE RISER HAS BEEN REVISED HOWEVER THE
 EXISTING PANEL IN THE MAIN HOUSE IS NOT SHOWN. HOW IS
 THIS PANEL FED? WHERE IS THE OVER CURRENT PROTECTION?
 THE NEW PANEL SCHEDULE DOES NOT INDICATE ANY BREAKER OR
 FEED TO THIS EXISTING PANEL WHICH IS SHOWN TO REMAIN.
 PLAN SHOWS TWO PANELS AT MAIN HOUSE YET NO PANEL
 SCHEDULES ETC ARE SHOWN
 NO FEEDERS, ETC.
 215.5,220, 240, 310.16, ETC
 FBC106.3.5.4
  
 4) NOTE: THE RISER HAS BEEN REVISED AND NOW SHOWS NEW
 150AMP COMING FROM WHAT IS BEING CALLED AN EXISTING
 2-GANG METER. WHAT SIZE IS THIS EXISTING SERVICE AND
 WHAT IS THE AMPERAGE OF THE 2-GANG METER CAN?
 ADDING NEW 150AMP MAIN AND INCREASING THE LOAD ON THE
 SERVICE YET NO LOAD CALCULATIONS ON THE SERVICE OR SIZE
 OF THE EXISTING SERVICE ARE SHOWN.
 230.70, 230.71, 240,220 ETC
 FBC 106.3.5.4
  
 5) NOTE: PLEASE SEE THE OVER CURRENT PROTECTION ON THE
 AHU IS STILL NOT CORRECT. THE PREVIOUS PLANS WAS TOO
 HIGH AND DID NOT MEET 424.11E AND NOW THE OVER CURRENT
 PROTECTION IS NOT LARGE ENOUGH PER 424.3B. PLEASE
 ADJUST.
  
 6) NOTE: PLEASE SEE THERE ARE STILL NO DISCONNECTS ETC
 SHOWN FOR NEW AC SYSTEM. 440.11,210.63,210.70.
  
 *** PLEASE SUBMIT ELECTRICAL PLANS MEETING THE
 *MINIMUM* PER THE NATIONAL ELECTRICAL CODE.
  
  
  
 IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]