| 2008-07-28 08:36:27 | |
| | ** DENIED4TH REVIEW ** |
| | |
| | *** SOME NOTES FROM PREVIOUS REVIEW ARE STILL THE SAME. |
| | SOME ARE NOW NEW DUE TO REVISED PLANS. |
| | |
| | 1) NOTE: PLEASE SEE EQUIPMENT GROUNDING CONDUCTOR IS |
| | STILL MISSING AFTER THE FIRST MEANS OF DISCONNECT TO |
| | THE 150 AMP SUB PANEL. |
| | 250.110,250.122 |
| | |
| | 2) NOTE: PLEASE SEE THE RISER STILL DOES NOT SHOW ANY |
| | GROUNDING ELECTRODE SYSTEM AT THE MAIN HOUSE AS |
| | REQUIRED PER 250.50,250.32 |
| | |
| | 3) NOTE: THE RISER HAS BEEN REVISED HOWEVER THE |
| | EXISTING PANEL IN THE MAIN HOUSE IS NOT SHOWN. HOW IS |
| | THIS PANEL FED? WHERE IS THE OVER CURRENT PROTECTION? |
| | THE NEW PANEL SCHEDULE DOES NOT INDICATE ANY BREAKER OR |
| | FEED TO THIS EXISTING PANEL WHICH IS SHOWN TO REMAIN. |
| | PLAN SHOWS TWO PANELS AT MAIN HOUSE YET NO PANEL |
| | SCHEDULES ETC ARE SHOWN |
| | NO FEEDERS, ETC. |
| | 215.5,220, 240, 310.16, ETC |
| | FBC106.3.5.4 |
| | |
| | 4) NOTE: THE RISER HAS BEEN REVISED AND NOW SHOWS NEW |
| | 150AMP COMING FROM WHAT IS BEING CALLED AN EXISTING |
| | 2-GANG METER. WHAT SIZE IS THIS EXISTING SERVICE AND |
| | WHAT IS THE AMPERAGE OF THE 2-GANG METER CAN? |
| | ADDING NEW 150AMP MAIN AND INCREASING THE LOAD ON THE |
| | SERVICE YET NO LOAD CALCULATIONS ON THE SERVICE OR SIZE |
| | OF THE EXISTING SERVICE ARE SHOWN. |
| | 230.70, 230.71, 240,220 ETC |
| | FBC 106.3.5.4 |
| | |
| | 5) NOTE: PLEASE SEE THE OVER CURRENT PROTECTION ON THE |
| | AHU IS STILL NOT CORRECT. THE PREVIOUS PLANS WAS TOO |
| | HIGH AND DID NOT MEET 424.11E AND NOW THE OVER CURRENT |
| | PROTECTION IS NOT LARGE ENOUGH PER 424.3B. PLEASE |
| | ADJUST. |
| | |
| | 6) NOTE: PLEASE SEE THERE ARE STILL NO DISCONNECTS ETC |
| | SHOWN FOR NEW AC SYSTEM. 440.11,210.63,210.70. |
| | |
| | *** PLEASE SUBMIT ELECTRICAL PLANS MEETING THE |
| | *MINIMUM* PER THE NATIONAL ELECTRICAL CODE. |
| | |
| | |
| | |
| | IMPORTANT** |
| | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| | TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| | ANY DELAYS. |
| | |