Plan Review Notes
Plan Review Notes For Permit 07100688
Permit Number 07100688
Review Stop P
Sequence Number 3
Notes
Date Text
2008-06-04 09:26:24****************PROVISO****************
 A} THE SHOWER WASTE PIPE MINIMUM SIZE SHALL BE 1-1/2"
 IN DIAMETER. PER FBC-2004 PLUMBING SECTION 417.3 SHOWER
 WASTE OUTLETS.
  
 B} A CLEANOUT IS REQUIRED AT THE BASE OF THE LAVATORY
 WASTE STACK DUE TO INDICATING THAT AN 1-1/4" TRAP IS
 BEING USED. PER FBC-2004 PLUMBING SECTION 708.3.4 BASE
 OF STACK AND SECTION 708.7 MINIMUM SIZE, EXCEPTIONS
 (1).
  
 C} NOTE: IF SANITARY SYSTEM IS NOT INSTALLED PER SHEET
 A-1 APPROVED PLUMBING RISER A REVISION WILL BE
 REQUIRED.
  