Plan Review Notes
Plan Review Notes For Permit 07100688
Permit Number 07100688
Review Stop E
Sequence Number 3
Notes
Date Text
2008-06-03 13:57:08** DENIED 3RD REVIEW **
  
  
 ** PLEASE SEE SOME ITEMS FROM PREVIOUS REVIEWS ARE
 STILL IN NEED OF ADDRESSING.
 **PLEASE SEE SOME ITEMS BROUGHT UP IN MEETING HELD
 BEFORE PLANS WERE RESUBMITTED ARE STILL IN NEED OF
 ADDRESSING.
 **PLEASE SEE SOME NEW ITEMS ARE NOW NOTED AS ITEMS
 CHANGED OR REVISED SINCE LAST REVIEW. THESE ITEMS WERE
 GONE OVER IN MEETING HOWEVER NOT CORRECTED ON PLANS.
  
 1) NOTE: PLEASE SEE THE MINIMUM CODES ARE STILL NOT
 STATED ON PLANS. THIS HAS BEEN REQUESTED THREE TIMES
 AND YET STILL NOT DONE.
 2005 NFPA-70
 2002 NFPA-72
 2004 FBC/ RESIDENTIAL/ EXISTING W/ 2007 REVISIONS.
  
 2) NOTE: PLEASE SEE SMALL APPLIANCE CIRCUITS ARE NOW
 BEING SHOWN WITH 30AMP 1-POLE BREAKERS WHICH IS NOT
 PERMITTED.
 210.20
  
 3) NOTE: PLEASE SEE AHU IS NOW SHOWING 60AMP OVER
 CURRENT PROTECTION ON 7.5KW/8KW HEAT FOR AHU WHICH IS
 TOO HIGH.
 424.3B (125% MIN, 424.11E 150% MAXIMUM)
  
 4) NOTE: PLEASE SEE #6 CONDUCTORS NOW BEING SHOWN ON
 30AMP BREAKER FOR WATER HEATER WHICH IS NOT POSSIBLE.
 THE BREAKER IS NOT RATED NOR WILL IT ACCEPT #6 AWG. NEC
 110.3
  
 5) NOTE: PLEASE SEE THE RISER STILL SHOWS A #6/0 FOR
 EQUIPMENT GROUNDING. THERE IS NO SUCH CONDUCTOR SIZE.
 PLEASE SEE 250.122 FOR SIZING OF EQUIPMENT GROUNDING
 CONDUCTORS.
 BROUGHT UP IN MEETING.
  
 6) NOTE: PLEASE SEE RISER SHOWS EQUIPMENT GROUNDING
 AFTER METER AND BEFORE FIRST MEANS OF DISCONNECT WHICH
 IS NOT PERMITTED PER 250.6, 250.24
 THIS CREATES OBJECTIONABLE CURRENTS WHICH IS NOT
 PERMITTED.
 ** PREVIOUS NOTES AND MEETING
  
 7) NOTE: PLEASE PROVIDE AN ACCURATE AND CODE COMPLIANT
 RISER DIAGRAM AND COORDINATEWITH PLANS.
 THE PLANS SHOWS EXISTING METERS AT REAR BUILDING AND
 RISER EVEN CONTAINS A NOTE WHICH STATES THIS HOWEVER IF
 THIS IS THE CASE, NO MAIN IS SHOWN AT REAR BUILDING FOR
 GROUPING PER 230.72
 PLEASE KNOW IF SERVICE IS AT MAIN HOUSE, THEN NO FEEDS
 ARE SHOWN TO REAR BUILDING. AT MEETING IT WAS
 DETERMINED THE WATER HEATER ETC MAY HAVE BEEN FED FROM
 REAR BUILDING WHICH IS ON ANOTHER SERVICE.
 PLEASE STILL SHOW THE MAIN HOUSE CONTAINING A SERVICE
 AND IT IS SHOWN TO BE RELOCATED.
 HOW IS ANY OF THIS CODE COMPLIANT PER 215.5, 240.4,
 310.16, 230.70, 230.2, 230.71, 230.72, 230.76, 230.79.
 PLEASE SEE 225.31-225.9 FOR BRANCH CIRCUITS AND FEEDERS
 AT DETACHED BUILDINGS.
 PLEASE SUBMIT COMPLETE PLANS SHOWING ALL ELECTRICAL
 EQUIPMENT, SERVICE, DISCONNECTS, GROUNDING ETC. PLEASE
 SEE 2005 NATIONAL ELECTRICAL CODE/ NFPA-70. FBC
 106.3.5.4, 106.1.2
 ** PREVIOUS NOTES AND MEETING**
  
 8) NOTE: PLEASE SEE 250.32, 250.50 WITH RESPECT TO
 GROUNDING ELECTRODE SYSTEMS AT DETACHED BUILDINGS. AS
 THE ACTUAL SERVICE, LOCATION, MAINS, SERVICE ETC HAS
 NOT BEEN CLEARLY SHOWN OR DETERMINED, THE GROUNDING
 ELECTRODE SYSTEM CAN NO BE REVIEWED AT LAST POSSIBLE
 SCENARIO FOR CODE COMPLIANCE.
 ** PREVIOUS NOTES AND MEETING*
  
 9) NOTE: PLEASE SEE NO AIC RATING IS STILL SHOWN.110.9
 ** PREVIOUS NOTES AND MEETING**.
  
 10) NOTE: PLEASE SEE 210.12 AS AFCI PROTECTION WAS GONE
 OVER IN MEETING HELD BEFORE PLANS WERE RESUBMITTED
 ALONG WITH PREVIOUS REVIEW COMMENTS.
 PLEASE SEE RISER STILL NOTES AFCI PROTECTION FOR
 RECEPTACLES ONLY. THE NOTES ON THE RIGHT HAND SIDE OF
 PLANS DO NOTE AFCI FOR BRANCH CIRCUITS IN BEDROOMS
 WHICH IS OK.
 PLEASE REMOVE NOTE ABOVE THE PANEL.
  
 11) NOTE: PLANS/RISER STILL SHOWS A NOTE WHICH MENTIONS
 SUB PANEL TO BE USED FOR CONDENSING UNIT, SPRINKLER
 TIME CLOCK ETC AS ALTERNATIVE. THERE IS NO OTHER SUB
 PANEL SHOWN ON PLANS. PLANS ONLY SHOW ONE PANEL. ??
  
 12) NOTE: PLEASE SEE ELECTRICAL PLANS DO NOT SHOW NEW
 CONDENSING UNIT, DISCONNECT, WP GFI REQUIRED ETC.
 PLEASE SEE 440.11 FOR MISSING DISCONNECT.
 PLEASE SEE 210.63 FOR RECEPTACLE AND 210.8A FOR GFI
 PROTECTION.
  
 13) NOTE: PLEASE SEE ELECTRICAL PLANS DO NOT SHOW ANY
 NEW ELECTRICAL FOR NEW AHU LOCATED AT FRONT OF EXISTING
 HOUSE.
 440.11, 210.63, 210.70
  
 14) NOTE: R313 OF THE 2004 RESIDENTIAL CODE SHALL BE
 REDLINED ON PLANS ONCE ALL OTHER ITEMS ARE ADDRESSED.
  
 15) NOTE: PLEASE KNOW IF PLANS COME BACK WITH OUT
 MINIMUM CODE COMPLIANCE FOR ELECTRICAL THIS OFFICE MAY
 HAVE NO CHOICE BUT TO RETAIN PLANS AND POSSIBLY FORWARD
 TO THE STATE BOARD OF ARCHITECTS.
  
  
 ** IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW. IF
 THERE ARE ANY QUESTIONS OR COMMENTS PLEASE DO NOT
 HESITATE IN CONTACTING THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]