| 2008-06-03 13:57:08 | ** DENIED 3RD REVIEW ** |
| | |
| | |
| | ** PLEASE SEE SOME ITEMS FROM PREVIOUS REVIEWS ARE |
| | STILL IN NEED OF ADDRESSING. |
| | **PLEASE SEE SOME ITEMS BROUGHT UP IN MEETING HELD |
| | BEFORE PLANS WERE RESUBMITTED ARE STILL IN NEED OF |
| | ADDRESSING. |
| | **PLEASE SEE SOME NEW ITEMS ARE NOW NOTED AS ITEMS |
| | CHANGED OR REVISED SINCE LAST REVIEW. THESE ITEMS WERE |
| | GONE OVER IN MEETING HOWEVER NOT CORRECTED ON PLANS. |
| | |
| | 1) NOTE: PLEASE SEE THE MINIMUM CODES ARE STILL NOT |
| | STATED ON PLANS. THIS HAS BEEN REQUESTED THREE TIMES |
| | AND YET STILL NOT DONE. |
| | 2005 NFPA-70 |
| | 2002 NFPA-72 |
| | 2004 FBC/ RESIDENTIAL/ EXISTING W/ 2007 REVISIONS. |
| | |
| | 2) NOTE: PLEASE SEE SMALL APPLIANCE CIRCUITS ARE NOW |
| | BEING SHOWN WITH 30AMP 1-POLE BREAKERS WHICH IS NOT |
| | PERMITTED. |
| | 210.20 |
| | |
| | 3) NOTE: PLEASE SEE AHU IS NOW SHOWING 60AMP OVER |
| | CURRENT PROTECTION ON 7.5KW/8KW HEAT FOR AHU WHICH IS |
| | TOO HIGH. |
| | 424.3B (125% MIN, 424.11E 150% MAXIMUM) |
| | |
| | 4) NOTE: PLEASE SEE #6 CONDUCTORS NOW BEING SHOWN ON |
| | 30AMP BREAKER FOR WATER HEATER WHICH IS NOT POSSIBLE. |
| | THE BREAKER IS NOT RATED NOR WILL IT ACCEPT #6 AWG. NEC |
| | 110.3 |
| | |
| | 5) NOTE: PLEASE SEE THE RISER STILL SHOWS A #6/0 FOR |
| | EQUIPMENT GROUNDING. THERE IS NO SUCH CONDUCTOR SIZE. |
| | PLEASE SEE 250.122 FOR SIZING OF EQUIPMENT GROUNDING |
| | CONDUCTORS. |
| | BROUGHT UP IN MEETING. |
| | |
| | 6) NOTE: PLEASE SEE RISER SHOWS EQUIPMENT GROUNDING |
| | AFTER METER AND BEFORE FIRST MEANS OF DISCONNECT WHICH |
| | IS NOT PERMITTED PER 250.6, 250.24 |
| | THIS CREATES OBJECTIONABLE CURRENTS WHICH IS NOT |
| | PERMITTED. |
| | ** PREVIOUS NOTES AND MEETING |
| | |
| | 7) NOTE: PLEASE PROVIDE AN ACCURATE AND CODE COMPLIANT |
| | RISER DIAGRAM AND COORDINATEWITH PLANS. |
| | THE PLANS SHOWS EXISTING METERS AT REAR BUILDING AND |
| | RISER EVEN CONTAINS A NOTE WHICH STATES THIS HOWEVER IF |
| | THIS IS THE CASE, NO MAIN IS SHOWN AT REAR BUILDING FOR |
| | GROUPING PER 230.72 |
| | PLEASE KNOW IF SERVICE IS AT MAIN HOUSE, THEN NO FEEDS |
| | ARE SHOWN TO REAR BUILDING. AT MEETING IT WAS |
| | DETERMINED THE WATER HEATER ETC MAY HAVE BEEN FED FROM |
| | REAR BUILDING WHICH IS ON ANOTHER SERVICE. |
| | PLEASE STILL SHOW THE MAIN HOUSE CONTAINING A SERVICE |
| | AND IT IS SHOWN TO BE RELOCATED. |
| | HOW IS ANY OF THIS CODE COMPLIANT PER 215.5, 240.4, |
| | 310.16, 230.70, 230.2, 230.71, 230.72, 230.76, 230.79. |
| | PLEASE SEE 225.31-225.9 FOR BRANCH CIRCUITS AND FEEDERS |
| | AT DETACHED BUILDINGS. |
| | PLEASE SUBMIT COMPLETE PLANS SHOWING ALL ELECTRICAL |
| | EQUIPMENT, SERVICE, DISCONNECTS, GROUNDING ETC. PLEASE |
| | SEE 2005 NATIONAL ELECTRICAL CODE/ NFPA-70. FBC |
| | 106.3.5.4, 106.1.2 |
| | ** PREVIOUS NOTES AND MEETING** |
| | |
| | 8) NOTE: PLEASE SEE 250.32, 250.50 WITH RESPECT TO |
| | GROUNDING ELECTRODE SYSTEMS AT DETACHED BUILDINGS. AS |
| | THE ACTUAL SERVICE, LOCATION, MAINS, SERVICE ETC HAS |
| | NOT BEEN CLEARLY SHOWN OR DETERMINED, THE GROUNDING |
| | ELECTRODE SYSTEM CAN NO BE REVIEWED AT LAST POSSIBLE |
| | SCENARIO FOR CODE COMPLIANCE. |
| | ** PREVIOUS NOTES AND MEETING* |
| | |
| | 9) NOTE: PLEASE SEE NO AIC RATING IS STILL SHOWN.110.9 |
| | ** PREVIOUS NOTES AND MEETING**. |
| | |
| | 10) NOTE: PLEASE SEE 210.12 AS AFCI PROTECTION WAS GONE |
| | OVER IN MEETING HELD BEFORE PLANS WERE RESUBMITTED |
| | ALONG WITH PREVIOUS REVIEW COMMENTS. |
| | PLEASE SEE RISER STILL NOTES AFCI PROTECTION FOR |
| | RECEPTACLES ONLY. THE NOTES ON THE RIGHT HAND SIDE OF |
| | PLANS DO NOTE AFCI FOR BRANCH CIRCUITS IN BEDROOMS |
| | WHICH IS OK. |
| | PLEASE REMOVE NOTE ABOVE THE PANEL. |
| | |
| | 11) NOTE: PLANS/RISER STILL SHOWS A NOTE WHICH MENTIONS |
| | SUB PANEL TO BE USED FOR CONDENSING UNIT, SPRINKLER |
| | TIME CLOCK ETC AS ALTERNATIVE. THERE IS NO OTHER SUB |
| | PANEL SHOWN ON PLANS. PLANS ONLY SHOW ONE PANEL. ?? |
| | |
| | 12) NOTE: PLEASE SEE ELECTRICAL PLANS DO NOT SHOW NEW |
| | CONDENSING UNIT, DISCONNECT, WP GFI REQUIRED ETC. |
| | PLEASE SEE 440.11 FOR MISSING DISCONNECT. |
| | PLEASE SEE 210.63 FOR RECEPTACLE AND 210.8A FOR GFI |
| | PROTECTION. |
| | |
| | 13) NOTE: PLEASE SEE ELECTRICAL PLANS DO NOT SHOW ANY |
| | NEW ELECTRICAL FOR NEW AHU LOCATED AT FRONT OF EXISTING |
| | HOUSE. |
| | 440.11, 210.63, 210.70 |
| | |
| | 14) NOTE: R313 OF THE 2004 RESIDENTIAL CODE SHALL BE |
| | REDLINED ON PLANS ONCE ALL OTHER ITEMS ARE ADDRESSED. |
| | |
| | 15) NOTE: PLEASE KNOW IF PLANS COME BACK WITH OUT |
| | MINIMUM CODE COMPLIANCE FOR ELECTRICAL THIS OFFICE MAY |
| | HAVE NO CHOICE BUT TO RETAIN PLANS AND POSSIBLY FORWARD |
| | TO THE STATE BOARD OF ARCHITECTS. |
| | |
| | |
| | ** IMPORTANT** |
| | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| | TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| | ANY DELAYS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW. IF |
| | THERE ARE ANY QUESTIONS OR COMMENTS PLEASE DO NOT |
| | HESITATE IN CONTACTING THIS OFFICE. |
| | |