2008-03-06 16:47:15** DENIED 2NDREVIEW **
  
 ** PLEASE SEE THERE ARE SEVERAL COMMENTS FROM THE
 PREVIOUS REVIEW WHICH ARE STILL IN NEED OF ADDRESSING.
 MANY OF THESE COMMENTS BELOW ARE THE SAME AS PREVIOUS.
  
 ** PLEASE SEE THERE ARE SEVERAL NEW COMMENTS ALSO AS
 SOME ITEMS ARE NOW ONLY BEING SUBMITTED FOR THE FIRST
 TIME FOR REVIEW.
  
 ** PLEASE ALSO KNOW THERE ARE ITEMS STILL NOT SHOWN ON
 PLANS WHICH SIMPLY CAN NOT BE REVIEWED IF NOT SHOWN OR
 SUBMITTED.
  
 1) NOTE: PLEASE SEE THE FOLLOWING CODES ARE REQUIRED ON
 THE ELECTRICAL PLANS.
 2004 FBC W2007 REVISIONS.
 2005 NFPA-70
 2002 NFPA-72
 ** PLANS STILL ONLY STATE PER LOCAL CODES BUT DONOT
 PROVIDE WHAT CODES THIS DESIGNED TO AS REQUIRED.
  
 2) NOTE: PLEASE SEE PLANS ARE NOW SHOWING A NEW RISER
 WHICH NOW CONTAINS SEVERAL COMMENTS.
 A) PLEASE SEE THE RISER NOW SHOWS NEW MAIN AND THEN
 STATES *IF REQUIRED* ??? HOW CAN THIS SAY *IF REQUIRED*
 WHEN A MAIN IS REQUIRED.
 B) PLEASE SEE THE RISER SHOWS A 125AMP MAIN FEEDING A
 100AMP PANEL WHICH IS NOT PERMITTED. THE PANEL AS SHOWN
 ON PLANS (PANEL SCHEDULE) SHOWS 125AMP. PLEASE
 COORDINATE.
 C) HOW CAN THIS BE A 100AMP PANEL WHEN THE LOAD SHOWN
 AT 114AMPS EXCEEDS THAT RATING?
 D) PLEASE SEE THE RISER STILL DOES NOT SHOW OTHER
 STRUCTURE ON PROPERTY, LOAD ETC??
 E) PLEASE INDICATE THE REQUIRED AIC RATING OF
 MAINS/EQUIPMENT.
 230.70, 230.71, 230.72, 230.2, 110.9 ETC
  
 3) NOTE: PLEASE COMPLETE PANEL SCHEDULES MEETING NEC
 408.4, 240.4, 310.16 ETC
 PLEASE SEE THE ROOMS ARE AREAS ON PANEL SCHEDULE NEED
 TO BE SPECIFIC.
 PLEASE SEE THE PANEL SCHEDULE SHOWS FOR EXAMPLE #8 ON
 20AMP BREAKER, THIS IS NOT POSSIBLE.
  
 4) NOTE: PLEASE SEE 210.52B1, 210.11C1, 210.52 AS ONE
 OR MORE OF THE SMALL APPLIANCE AND LAUNDRY CIRCUITS
 SHALL MEET THESE SECTIONS FOR LOADS AND HOW THEY ARE
 FIGURED INTO CALCULATIONS.
 PLEASE SEE THE MINIMUM PER CIRCUIT SHALL BE 1500VA
 EACH.
 HOW DO 4 CIRCUITS WHICH ARE SUPPOSED TO BE 1500VA
 MINIMUM ADD UP TO 3500VA. (SEE CIRCUITS 10-13)
  
 5) NOTE: PLANS MENTIONS PANELS AND SERVICE TO BE
 RELOCATED HOWEVER BASED ON PLANS AND RISER THE PLANS
 ARE NOT CLEAR WHERE ALL EQUIPMENT IS BEING INSTALLED.
 PLEASE CLEAR THIS UP.
 110.26, 240.24
  
 6) NOTE: PLEASE SEE 220.83B FOR LOAD CALCULATIONS ON
 EXISTING SERVICES; PLEASE SEE THE REST OF 220 FOR NEW
 SERVICES.
  
 7) NOTE: PLEASE SEE THE WATER HEATER IS SHOWING 7.5KW
 AND THE OVER CURRENT PROTECTION AND CONDUCTOR SIZES ARE
 SMALLER THAN REQUIRED.
 PLEASE SEE 422.13
  
 8)NOTE: PLEASE SEE THE PLANS INDICATE ARC FAULT
 PROTECTION ONLY FOR RECEPTACLES HOWEVER UNDER THE 2002
 AND 2005 NEC 210.12 REQUIRES AFCI PROTECTION FOR ALL
 OUTLETS. SEE THIS CODE SECTION FOR REQUIREMENTS
  
 9) NOTE: PLEASE SEE FS 553.80(2)(B) WITH RESPECT TO
 REPEAT COMMENTS FOR CODE COMPLIANCE.
 PLEASE KNOW THIS IS ONLY A NOTICE GIVEN AT THIS TIME.
  
 ** PLEASE KNOW AS THERE ARE SEVERAL ITEMS NOT YET
 SUBMITTED AND INCLUDED ON PLANS THERE MAY VERY WELL BE
 NEW COMMENTS ON THE FOLLOWING REVIEW WHICH CAN NOT BE
 MADE AT THIS TIME.
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]