| 2008-03-06 16:47:15 | ** DENIED 2NDREVIEW ** |
| | |
| | ** PLEASE SEE THERE ARE SEVERAL COMMENTS FROM THE |
| | PREVIOUS REVIEW WHICH ARE STILL IN NEED OF ADDRESSING. |
| | MANY OF THESE COMMENTS BELOW ARE THE SAME AS PREVIOUS. |
| | |
| | ** PLEASE SEE THERE ARE SEVERAL NEW COMMENTS ALSO AS |
| | SOME ITEMS ARE NOW ONLY BEING SUBMITTED FOR THE FIRST |
| | TIME FOR REVIEW. |
| | |
| | ** PLEASE ALSO KNOW THERE ARE ITEMS STILL NOT SHOWN ON |
| | PLANS WHICH SIMPLY CAN NOT BE REVIEWED IF NOT SHOWN OR |
| | SUBMITTED. |
| | |
| | 1) NOTE: PLEASE SEE THE FOLLOWING CODES ARE REQUIRED ON |
| | THE ELECTRICAL PLANS. |
| | 2004 FBC W2007 REVISIONS. |
| | 2005 NFPA-70 |
| | 2002 NFPA-72 |
| | ** PLANS STILL ONLY STATE PER LOCAL CODES BUT DONOT |
| | PROVIDE WHAT CODES THIS DESIGNED TO AS REQUIRED. |
| | |
| | 2) NOTE: PLEASE SEE PLANS ARE NOW SHOWING A NEW RISER |
| | WHICH NOW CONTAINS SEVERAL COMMENTS. |
| | A) PLEASE SEE THE RISER NOW SHOWS NEW MAIN AND THEN |
| | STATES *IF REQUIRED* ??? HOW CAN THIS SAY *IF REQUIRED* |
| | WHEN A MAIN IS REQUIRED. |
| | B) PLEASE SEE THE RISER SHOWS A 125AMP MAIN FEEDING A |
| | 100AMP PANEL WHICH IS NOT PERMITTED. THE PANEL AS SHOWN |
| | ON PLANS (PANEL SCHEDULE) SHOWS 125AMP. PLEASE |
| | COORDINATE. |
| | C) HOW CAN THIS BE A 100AMP PANEL WHEN THE LOAD SHOWN |
| | AT 114AMPS EXCEEDS THAT RATING? |
| | D) PLEASE SEE THE RISER STILL DOES NOT SHOW OTHER |
| | STRUCTURE ON PROPERTY, LOAD ETC?? |
| | E) PLEASE INDICATE THE REQUIRED AIC RATING OF |
| | MAINS/EQUIPMENT. |
| | 230.70, 230.71, 230.72, 230.2, 110.9 ETC |
| | |
| | 3) NOTE: PLEASE COMPLETE PANEL SCHEDULES MEETING NEC |
| | 408.4, 240.4, 310.16 ETC |
| | PLEASE SEE THE ROOMS ARE AREAS ON PANEL SCHEDULE NEED |
| | TO BE SPECIFIC. |
| | PLEASE SEE THE PANEL SCHEDULE SHOWS FOR EXAMPLE #8 ON |
| | 20AMP BREAKER, THIS IS NOT POSSIBLE. |
| | |
| | 4) NOTE: PLEASE SEE 210.52B1, 210.11C1, 210.52 AS ONE |
| | OR MORE OF THE SMALL APPLIANCE AND LAUNDRY CIRCUITS |
| | SHALL MEET THESE SECTIONS FOR LOADS AND HOW THEY ARE |
| | FIGURED INTO CALCULATIONS. |
| | PLEASE SEE THE MINIMUM PER CIRCUIT SHALL BE 1500VA |
| | EACH. |
| | HOW DO 4 CIRCUITS WHICH ARE SUPPOSED TO BE 1500VA |
| | MINIMUM ADD UP TO 3500VA. (SEE CIRCUITS 10-13) |
| | |
| | 5) NOTE: PLANS MENTIONS PANELS AND SERVICE TO BE |
| | RELOCATED HOWEVER BASED ON PLANS AND RISER THE PLANS |
| | ARE NOT CLEAR WHERE ALL EQUIPMENT IS BEING INSTALLED. |
| | PLEASE CLEAR THIS UP. |
| | 110.26, 240.24 |
| | |
| | 6) NOTE: PLEASE SEE 220.83B FOR LOAD CALCULATIONS ON |
| | EXISTING SERVICES; PLEASE SEE THE REST OF 220 FOR NEW |
| | SERVICES. |
| | |
| | 7) NOTE: PLEASE SEE THE WATER HEATER IS SHOWING 7.5KW |
| | AND THE OVER CURRENT PROTECTION AND CONDUCTOR SIZES ARE |
| | SMALLER THAN REQUIRED. |
| | PLEASE SEE 422.13 |
| | |
| | 8)NOTE: PLEASE SEE THE PLANS INDICATE ARC FAULT |
| | PROTECTION ONLY FOR RECEPTACLES HOWEVER UNDER THE 2002 |
| | AND 2005 NEC 210.12 REQUIRES AFCI PROTECTION FOR ALL |
| | OUTLETS. SEE THIS CODE SECTION FOR REQUIREMENTS |
| | |
| | 9) NOTE: PLEASE SEE FS 553.80(2)(B) WITH RESPECT TO |
| | REPEAT COMMENTS FOR CODE COMPLIANCE. |
| | PLEASE KNOW THIS IS ONLY A NOTICE GIVEN AT THIS TIME. |
| | |
| | ** PLEASE KNOW AS THERE ARE SEVERAL ITEMS NOT YET |
| | SUBMITTED AND INCLUDED ON PLANS THERE MAY VERY WELL BE |
| | NEW COMMENTS ON THE FOLLOWING REVIEW WHICH CAN NOT BE |
| | MADE AT THIS TIME. |
| | |
| | ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY |
| | COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE |
| | DO NOT HESITATE IN CONTACTING THIS OFFICE. |
| | PLEASE SEE BELOW FOR CONTACT INFORMATION. |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| | CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| | OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS |
| | INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT |
| | LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| | TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| | DELAYS. |
| | |