| | 1) NOTE: PLEASE SEE THAT PLANS ARE NOT COMPLETE AT THIS |
| | TIME WITH ALL INFORMATION FOR MINIMUM CODE REVIEW. |
| | PLEASE SEE THE BELOW COMMENTS FOR ITEMS WHICH ARE |
| | MISSING. |
| | **THERE MAY BE NEW COMMENTS ON THE FOLLOWING REVIEW |
| | WHICH CAN NOT BE MADE AT THIS TIME. |
| | |
| | 2) NOTE:PLEASE KNOW THAT ANY PERMIT APPLICATIONS |
| | WHICH ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES |
| | PROJECTS UNDER THE NEW CODES ADOPTED BY THE STATE. |
| | PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO |
| | THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70. |
| | PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH MAY |
| | AFFECT DESIGNS FOR ALL TRADES. |
| | PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS |
| | REVIEWER AT A MINIMUM. |
| | 2004 FBC W/ 2006 REVISIONS |
| | 2005 NFPA-70 |
| | 2002 NFPA-72 |
| | |
| | 3) NOTE: PLEASE SEE THE SEALS ON MANY OF THE SHEETS ARE |
| | NOT CLEAR AND VISIBLE AS REQUIRED PER FS 481.221. |
| | PLEASE BE SURE TO ADDRESS. |
| | |
| | 4) NOTE: PLEASE SEE ZONING COMMENTS AS THE SET BACK ON |
| | THE WEST SIDE OF THE DWELLING WILL HAVE AN AFFECT ON |
| | ALL TRADES AND THE DESIGN AS SET-FORTH. |
| | |
| | 5) NOTE: PLEASE SUBMIT COMPLETED ELECTRICAL PLANS. |
| | PLANS INDICATE A NEW SERVICE HOWEVER NO ELECTRICAL |
| | RISER DIAGRAM WAS SUBMITTED FOR REVIEW. |
| | PLEASE SUBMIT A COMPLETE ELECTRICAL RISER DIAGRAM. |
| | PLEASE SHOW ALL SERVICE ENTRANCE CONDUCTORS, FEEDERS, |
| | GROUNDING, SIZE OF EQUIPMENT, AIC RATINGS ETC. PLEASE |
| | SEE 215.5, 230.4, 310.16, 250.50, 250.122, 250.66, |
| | 110.9 ETC. |
| | FBC 106.3.5.4. |
| | |
| | 6) NOTE: PLEASE SUBMIT COMPLETE LOAD CALCULATIONS FOR |
| | NEW ADDITION AND EXISTING LOADS. |
| | PLEASE SEE 220.16A1 AND 220.87. |
| | PLEASE SEE THE CODE AS REFERENCED IN PARTIAL LOAD |
| | CALCULATIONS IS NO LONGER IN VALID. THE NEW CODE AS OF |
| | DECEMBER 06 IS THE 2005 NEC. |
| | PLEASE INDICATE ALL MINIMUM LOADS ALONG WITH NEW LOADS |
| | AND DEDICATED LOADS AS REQUIRED. |
| | FBC 106.3.5.4 |
| | |
| | 7) NOTE: PLEASE SEE FBC R313 AND NFPA-72 11.5.1.1.1. |
| | PLEASE SEE MISSING SMOKE ALARMS FOR NEW AREAS. PLEASE |
| | ALSO PROVIDE A COMPLETED FLOOR PLAN OF THE EXISTING |
| | DWELLING WHICH INDICATES SMOKE ALARMS EITHER EXISTING |
| | OR NEW TO BE INSTALLED. THESE SHALL MEET NFPA-72 |
| | 11.5.1.1, 11.8.3. |
| | |
| | 8) NOTE: PLEASE SEE THAT THE ELECTRICAL PLANS DO NOT |
| | CONTAIN ANY INFORMATION ON THE NEWA/C SYSTEM TO BE |
| | INSTALLED. PLEASE PROVIDE THE MINIMUM WIRING, OVER |
| | CURRENT PROTECTION, LOADS ETC ON PANEL SCHEDULE. PLEASE |
| | PROVIDE MINIMUM DISCONNECTS PER 440.11. PLEASE SEE |
| | 210.63 AND 210.8 FOR MINIMUM SERVICE RECEPTACLES |
| | REQUIRED. |
| | |
| | 9) NOTE: PLEASE PROVIDE A COMPLETED PANEL SCHEDULE |
| | SHOWING THE EXISTING CIRCUITS AND NEW TO BE INSTALLED. |
| | PLEASE SEE 408.4, 240.4, 310.16 ETC. |
| | |
| | 10) NOTE: PLEASE SEE 210.52D, 210.11C3 FOR MISSING |
| | REQUIRED DEDICATED BATH CIRCUIT(S). |
| | MUST BE 20AMP AND MUST BE #12. |
| | PLEASE SEE THE PARTIAL PANEL SCHEDULE SHOWN ONLY |
| | CONTAINS ONE 20AMP GFI CIRCUIT WHICH INDICATES THIS AS |
| | *OPTIONAL*?? |
| | PLEASE COMPLETE. |
| | |
| | 11) NOTE: PLEASE SEE MISSING ARC FAULT PROTECTED |
| | CIRCUITS PER 210.12. |
| | PLEASE LIST ON PANEL SCHEDULE TO BE PROVIDED. 210.12, |
| | 408.4. |
| | |
| | 12) NOTE: PLEASE SEE RECEPTACLES MISSING PER 210.52. |
| | PLEASE SEE NORTH WALL AND SOUTH WALLS OF NEW LIVING |
| | ROOM AREA. |
| | |
| | |
| | ** PLEASE KNOW AS SOME INFORMATION HAS NOT YET BEEN |
| | SUBMITTED FOR REVIEW, THERE MAY VERY WELL BE NEW |
| | COMMENTS ON THE NEXT REVIEW. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| | CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| | OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS |
| | INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT |
| | LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| | DELAYS. |
| | |