Plan Review Notes
Plan Review Notes For Permit 07100688
Permit Number 07100688
Review Stop E
Sequence Number 1
Notes
Date Text
2007-10-27 08:23:212007-10-27 08:23:21
  
  
  
 *** DENIED ***
  
 1) NOTE: PLEASE SEE THAT PLANS ARE NOT COMPLETE AT THIS
 TIME WITH ALL INFORMATION FOR MINIMUM CODE REVIEW.
 PLEASE SEE THE BELOW COMMENTS FOR ITEMS WHICH ARE
 MISSING.
 **THERE MAY BE NEW COMMENTS ON THE FOLLOWING REVIEW
 WHICH CAN NOT BE MADE AT THIS TIME.
  
 2) NOTE:PLEASE KNOW THAT ANY PERMIT APPLICATIONS
 WHICH ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES
 PROJECTS UNDER THE NEW CODES ADOPTED BY THE STATE.
 PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO
 THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70.
 PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH MAY
 AFFECT DESIGNS FOR ALL TRADES.
 PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS
 REVIEWER AT A MINIMUM.
 2004 FBC W/ 2006 REVISIONS
 2005 NFPA-70
 2002 NFPA-72
  
 3) NOTE: PLEASE SEE THE SEALS ON MANY OF THE SHEETS ARE
 NOT CLEAR AND VISIBLE AS REQUIRED PER FS 481.221.
 PLEASE BE SURE TO ADDRESS.
  
 4) NOTE: PLEASE SEE ZONING COMMENTS AS THE SET BACK ON
 THE WEST SIDE OF THE DWELLING WILL HAVE AN AFFECT ON
 ALL TRADES AND THE DESIGN AS SET-FORTH.
  
 5) NOTE: PLEASE SUBMIT COMPLETED ELECTRICAL PLANS.
 PLANS INDICATE A NEW SERVICE HOWEVER NO ELECTRICAL
 RISER DIAGRAM WAS SUBMITTED FOR REVIEW.
 PLEASE SUBMIT A COMPLETE ELECTRICAL RISER DIAGRAM.
 PLEASE SHOW ALL SERVICE ENTRANCE CONDUCTORS, FEEDERS,
 GROUNDING, SIZE OF EQUIPMENT, AIC RATINGS ETC. PLEASE
 SEE 215.5, 230.4, 310.16, 250.50, 250.122, 250.66,
 110.9 ETC.
 FBC 106.3.5.4.
  
 6) NOTE: PLEASE SUBMIT COMPLETE LOAD CALCULATIONS FOR
 NEW ADDITION AND EXISTING LOADS.
 PLEASE SEE 220.16A1 AND 220.87.
 PLEASE SEE THE CODE AS REFERENCED IN PARTIAL LOAD
 CALCULATIONS IS NO LONGER IN VALID. THE NEW CODE AS OF
 DECEMBER 06 IS THE 2005 NEC.
 PLEASE INDICATE ALL MINIMUM LOADS ALONG WITH NEW LOADS
 AND DEDICATED LOADS AS REQUIRED.
 FBC 106.3.5.4
  
 7) NOTE: PLEASE SEE FBC R313 AND NFPA-72 11.5.1.1.1.
 PLEASE SEE MISSING SMOKE ALARMS FOR NEW AREAS. PLEASE
 ALSO PROVIDE A COMPLETED FLOOR PLAN OF THE EXISTING
 DWELLING WHICH INDICATES SMOKE ALARMS EITHER EXISTING
 OR NEW TO BE INSTALLED. THESE SHALL MEET NFPA-72
 11.5.1.1, 11.8.3.
  
 8) NOTE: PLEASE SEE THAT THE ELECTRICAL PLANS DO NOT
 CONTAIN ANY INFORMATION ON THE NEWA/C SYSTEM TO BE
 INSTALLED. PLEASE PROVIDE THE MINIMUM WIRING, OVER
 CURRENT PROTECTION, LOADS ETC ON PANEL SCHEDULE. PLEASE
 PROVIDE MINIMUM DISCONNECTS PER 440.11. PLEASE SEE
 210.63 AND 210.8 FOR MINIMUM SERVICE RECEPTACLES
 REQUIRED.
  
 9) NOTE: PLEASE PROVIDE A COMPLETED PANEL SCHEDULE
 SHOWING THE EXISTING CIRCUITS AND NEW TO BE INSTALLED.
 PLEASE SEE 408.4, 240.4, 310.16 ETC.
  
 10) NOTE: PLEASE SEE 210.52D, 210.11C3 FOR MISSING
 REQUIRED DEDICATED BATH CIRCUIT(S).
 MUST BE 20AMP AND MUST BE #12.
 PLEASE SEE THE PARTIAL PANEL SCHEDULE SHOWN ONLY
 CONTAINS ONE 20AMP GFI CIRCUIT WHICH INDICATES THIS AS
 *OPTIONAL*??
 PLEASE COMPLETE.
  
 11) NOTE: PLEASE SEE MISSING ARC FAULT PROTECTED
 CIRCUITS PER 210.12.
 PLEASE LIST ON PANEL SCHEDULE TO BE PROVIDED. 210.12,
 408.4.
  
 12) NOTE: PLEASE SEE RECEPTACLES MISSING PER 210.52.
 PLEASE SEE NORTH WALL AND SOUTH WALLS OF NEW LIVING
 ROOM AREA.
  
  
 ** PLEASE KNOW AS SOME INFORMATION HAS NOT YET BEEN
 SUBMITTED FOR REVIEW, THERE MAY VERY WELL BE NEW
 COMMENTS ON THE NEXT REVIEW.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]