| 2007-11-07 16:58:37 | RESIDENTIAL ADDITION BUILDING REVIEW CHECKLIST. |
| | REVIEW UNDER EXISTING BUILDING CODE 2004, FLORIDA |
| | RESIDENTIAL CODE 2004 AND FBC 2004 WITH 2007 |
| | REVISIONS. |
| | |
| | 1- NEED RECORDED NOTICE OF COMMENCEMENT. SEC. 713.13 |
| | FLORIDA STATUTE. |
| | |
| | 2- BRING PLANS TO PALM BEACH COUNTY (2300 N. JOG RD) TO |
| | PAY IMPACT FEES. BRING BACK STAMPED PLANS AND COPY OF |
| | PAID RECEIPT IF FEES ARE DUE. |
| | |
| | 3- VALUE DECLARED IN THE PERMIT APPLICATION IS TOO LOW. |
| | OWES $799.04 FOR UPDATED VALUATION AND RADON FEES AS |
| | REQUIRED BY SEC. 108.3 CITY AMENDMENTS TO FBC 2004. |
| | |
| | 4- SPECIFY THE CALCULATED DESIGN PRESSURES FOR ALL |
| | EXTERIOR OPENINGS AS REQUIRED BYSEC. R301 AND TABLE |
| | R301.2(2) OF 2004 FLORIDA RESIDENTIAL CODE. |
| | |
| | 5- MASONRY GABLE END TO COMPLY WITH SEC. R609.4 OF 2004 |
| | FLORIDA RESIDENTIAL CODE. PROVIDE DETAILS AND |
| | SPECIFICATIONS SHOWING COMPLIANCE WITH ABOVE MENTIONED |
| | SECTION. |
| | SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004. |
| | |
| | 6- PROVIDE PRODUCT APPROVAL AS REQUIRED BY DCA RULE |
| | 9B-72 FOR: |
| | A) AWNING WINDOW. |
| | |
| | B) FRENCH DOORS. DRAWINGS IN PRODUCT APPROVAL FL8795 |
| | SUBMITTED ARE NOT LEGIBLE. NEED LEGIBLE DRAWINGS. |
| | |
| | C) STORM SHUTTERS. AND PROVIDE COMPLETE INSTALLATION |
| | SCHEDULE. SEE ATTACHED SAMPLE. |
| | |
| | D) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON |
| | PLANS AND DETAILS. |
| | ***NOTE: PROVIDE PRODUCT APPROVAL COVER PAGE AND PAGE |
| | SHOWING THE CONNECTOR ONLY. |
| | |
| | E) PRECAST LINTELS. |
| | |
| | 7- ARCHITECT TO REVIEW AND APPROVE IN WRITING(NOT |
| | SIGNING AND SEALING)ALL PRODUCT APPROVALS AS REQUIRED |
| | BY SEC. 106.3.3 CITY AMENDMENTS TO FBC 2004. |
| | |
| | 8- SPECIFY ONE HOUR FIRE RATED WALL ASSEMBLY FOR EAST |
| | WALL INCLUDING THE PROJECTION AS REQUIRED BY SEC. |
| | R302.1 OF 2004 FLORIDA RESIDENTIAL CODE. |
| | |
| | 9- PROJECTION ON EAST WALL IS NOT ALLOWED BECAUSE IT |
| | DOESN'T COMPLY WITH SEC. R302.1 OF 2004 FLORIDA |
| | RESIDENTIAL CODE. |
| | |
| | 10- OPENINGS ON EAST WALL ARE NOT ALLOWED BY SEC. |
| | R302.2 OF 2004 FLORIDA RESIDENTIAL CODE. |
| | |
| | 11-A) SURVEY TO SPECIFY SIDE SETBACK AND DISTANCE |
| | FROM PROPOSED ADDITION TO EXISTING 1 STORY BUILDING TO |
| | VERIFY COMPLIANCE WITH SEC. R302 OF 2004 FLORIDA |
| | RESIDENTIAL CODE. |
| | |
| | B) SURVEY TO HAVE SURVEYOR ORIGINAL SIGNATURE AS |
| | REQUIRED BY SEC. 472 FLORIDA STATUTE. |
| | |
| | 12- ENERGY CALCULATIONS: |
| | A) PROVIDE CORRECT NAME OF BULDERAND COMPLETE |
| | ALL-INFORMATION ON TOP OF FORM INCLUDING THE ADDRESS OF |
| | THIS PROJECT. |
| | |
| | B) CONDITIONED FLOOR AREA DOESN'T MATCH AREA SHOWN |
| | ON PLANS FOR THE ADDITION. REVISE AS REQUIRED. |
| | |
| | C) MAKE SURE UNDER ATTIC AREA ON ITEM 10(A) IS |
| | COORDINATED WITH ITEM 6. |
| | |
| | D) UNDER ATTIC R-VALUE DOESN'T MATCH R-VALUE |
| | SPECIFIED ON ARCHITECTURAL PLANS. REVISE AS REQUIRED. |
| | |
| | 13- SOIL TEST REPORT ENGINEER TO PROVIDE HIS LICENSE |
| | NUMBER AS REQUIRED BY SEC. 61G15-23.002OF FLORIDA |
| | ADMINISTRATIVE CODE AND CHAPTER 471 FLORIDA STATUTE. |
| | |
| | 14- TRUSS PACKAGE: |
| | A) LOADS DON'TMATCH LOADS SPECIFIED BY THE |
| | ARCHITECT OF RECORD. |
| | ***NOTE: COORDINATE WITH ARCHITECT FOR SPECIFIED LOADS |
| | TO AVOID CONFLICTS. |
| | |
| | B) IF ENGINEER WANTS TO COMPLY WITH SEC. |
| | 61G15-31.003, THEN NEEDS TO PROVIDE THE DESIGNEROF |
| | RECORD NAME AND ALL SHEETS NEED TO BE NUMBERED SO THEY |
| | CAN BE REFERENCED BACK IN THE INDEX SHEET. |
| | |
| | C) TRUSS LAYOUT NEEDS TO BE SIGNED, SEALED, DATED |
| | AND WITH THE ENGINEER'S COMPLETE INFORMATION AS |
| | REQUIRED BY SEC. 61G15-23.002 OF FLORIDA ADMINISTRATIVE |
| | CODE AND CHAPTER 471 FLORIDA STATUTE. |
| | |
| | D) ARCHITECTURAL PLANS CALL FOR DOUBLE GABLE END |
| | TRUSSES. COORDINATE FRAMING LAYOUT WITH ARCHITECT PRIOR |
| | TO SUBMITTAL TO AVOID CONFLICTS. |
| | |
| | 15- SHEET SP-1: |
| | A) REVISE CONCRETE BLOCK ALLOWABLE STRESS SHOWN ON |
| | TYPICAL PRIVACY WALL SECTION. SEE SEC. R606.4 OF 2004 |
| | FLORIDA RESIDENTIAL CODE AND REVISE AS REQUIRED. |
| | |
| | B) NORTH ARROW IS INCORRECT. SEE SURVEY AND REVISE. |
| | |
| | C) TITLE BLOCK IS MISSING ARCHITECT'S LICENSE NUMBER |
| | AS REQUIRED BY SEC. 61G1-16.004 OF FLORIDA |
| | ADMINISTRATIVE CODE. |
| | |
| | 16- SHEET A-1: |
| | A) UPDATE ALL REFERENCE STANDARDS SHOWN ON |
| | FOUNDATION NOTES. SEE CHAPTER 43 OF 2004 FLORIDA |
| | RESIDENTIAL CODE FOR CORRECT STANDARDS AND YEAR ADOPTED |
| | BY THIS CODE AND REVISE AS REQUIRED. |
| | |
| | B) CLARIFY THICKNESS OF CONCRETE SLAB.WALL |
| | SECTIONS ON SHEET A-4 CALL FOR 6" CONCRETE SLAB, WHILE |
| | FOUNDATION PLAN CALLS FOR 4". REVISE AS REQUIRED. |
| | |
| | C) DETAIL SECTIONS 3 AND 6 DON'T MATCH THOSE KEYED |
| | ON TYPICAL OPENING DETAIL #4.REVISE AS REQUIRED. |
| | |
| | 17- SHEET A-2:SPECIFY SIZE OF TREADS AND RISERS AT |
| | STEPS BY FRENCH DOORS TO VERIFY COMPLIANCE WITH SEC. |
| | R311.5.3 OF 2004 FLORIDA RESIDENTIAL CODE. |
| | ALSO, STEPS ARE NOT DRAWN TO SCALE. THEY ARE SHOWN AS |
| | 6"WIDE TREADS. REVISE AS REQUIRED. |
| | |
| | 18- SHEET A-3:REAR ELEVATION CALLS FOR NEW 2X8 KNEE |
| | WALL. THIS DOESN'T MATCH INFORMATION SHOWN ON TYPICAL |
| | WALL SECTION 1/A-4 AND BUILDING SECTION 2/A-4. REVISE |
| | AS REQUIRED TO MATCH. |
| | |
| | 18- SHEET A4: |
| | A) ROOF FRAMING PLAN IS MISSING THE RIDGE LINE AND |
| | DOESN'T MATCH TRUSS LAYOUT.COORDINATE WITH TRUSS |
| | ENGINEER AND REVISE AS REQUIRED. |
| | |
| | B) CLEARLY SPECIFY ALLDEAD AND LIVE LOADS |
| | INCLUDING THE ATTIC LIVE LOAD AS REQUIRED BYSEC. R301 |
| | AND TABLE R301.5 OF 2004 FLORIDA RESIDENTIAL CODE. |
| | ***NOTE: COORDINATE THESE LOADSWITH TRUSS ENGINEER. |
| | |
| | C) LOADS SPECIFIED ON ITEM #3 OF ROOF FRAMING NOTES |
| | DON'T MATCH WITH THOSE LOADS SPECIFIED ON TYPICAL END |
| | DETAIL. REVISE AS REQUIRED. |
| | |
| | D) ROOF NAILING NOTE AND SPECIFICATIONS FOR ROOF |
| | SHEATHING FASTENING ON WALL SECTIONS 1 AND 2 DON'T |
| | MATCH.SEE SEC. R803.2.3.1 OF 2004 FLORIDA |
| | RESIDENTIAL CODE FOR MINIMUM TYPE OF NAIL AND FASTENER |
| | SPACING REQUIRED INCLUDING FOR ROOF ZONE 3 AND REVISE |
| | AS REQUIRED. |
| | |
| | E) SECTIONS 1,2 AND 4 NEED TO SPECIFY ALL |
| | FASTENERS FOR GABLE END TRUSSES, GABLE END RAFTERS AND |
| | TOP AND BOTTOM OF2X8 KNEE WALL. SEC. 106.1.2 CITY |
| | AMENDMENTS TO FBC 2004 TO VERIFY COMPLIANCE WITH |
| | CALCULATED UPLIFT LOADS PERSEC. R301OF 2004 FLORIDA |
| | RESIDENTIAL CODE. SEE SIMPSON CATALOG AND SPECIFY |
| | CONNECTORACCORDING TO APPLICATION WOOD TO WOOD |
| | CONNECTOR OR WOOD TO MASONRY CONNECTOR. |
| | |
| | F) REVISE ROOF FRAMING NOTE #6. IT'S THE ARCHITECT |
| | RESPONSIBILITY TO SPECIFY CONNECTIONS, NOT THE FBC. |
| | |
| | 19- DETAILS 3 AND 4DON'T MATCH THE DETAIL SECTION AS |
| | KEYED ON THE ROOF FRAMING PLAN. REVISE AS REQUIRED. |
| | |
| | JULIO GOMEZ |
| | BUILDING PLANS EXAMINER |
| | (561)805-6712 |