2007-11-07 16:58:37RESIDENTIAL ADDITION BUILDING REVIEW CHECKLIST.
 REVIEW UNDER EXISTING BUILDING CODE 2004, FLORIDA
 RESIDENTIAL CODE 2004 AND FBC 2004 WITH 2007
 REVISIONS.
  
 1- NEED RECORDED NOTICE OF COMMENCEMENT. SEC. 713.13
 FLORIDA STATUTE.
  
 2- BRING PLANS TO PALM BEACH COUNTY (2300 N. JOG RD) TO
 PAY IMPACT FEES. BRING BACK STAMPED PLANS AND COPY OF
 PAID RECEIPT IF FEES ARE DUE.
  
 3- VALUE DECLARED IN THE PERMIT APPLICATION IS TOO LOW.
 OWES $799.04 FOR UPDATED VALUATION AND RADON FEES AS
 REQUIRED BY SEC. 108.3 CITY AMENDMENTS TO FBC 2004.
  
 4- SPECIFY THE CALCULATED DESIGN PRESSURES FOR ALL
 EXTERIOR OPENINGS AS REQUIRED BYSEC. R301 AND TABLE
 R301.2(2) OF 2004 FLORIDA RESIDENTIAL CODE.
  
 5- MASONRY GABLE END TO COMPLY WITH SEC. R609.4 OF 2004
 FLORIDA RESIDENTIAL CODE. PROVIDE DETAILS AND
 SPECIFICATIONS SHOWING COMPLIANCE WITH ABOVE MENTIONED
 SECTION.
 SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004.
  
 6- PROVIDE PRODUCT APPROVAL AS REQUIRED BY DCA RULE
 9B-72 FOR:
 A) AWNING WINDOW.
  
 B) FRENCH DOORS. DRAWINGS IN PRODUCT APPROVAL FL8795
 SUBMITTED ARE NOT LEGIBLE. NEED LEGIBLE DRAWINGS.
  
 C) STORM SHUTTERS. AND PROVIDE COMPLETE INSTALLATION
 SCHEDULE. SEE ATTACHED SAMPLE.
  
 D) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON
 PLANS AND DETAILS.
 ***NOTE: PROVIDE PRODUCT APPROVAL COVER PAGE AND PAGE
 SHOWING THE CONNECTOR ONLY.
  
 E) PRECAST LINTELS.
  
 7- ARCHITECT TO REVIEW AND APPROVE IN WRITING(NOT
 SIGNING AND SEALING)ALL PRODUCT APPROVALS AS REQUIRED
 BY SEC. 106.3.3 CITY AMENDMENTS TO FBC 2004.
  
 8- SPECIFY ONE HOUR FIRE RATED WALL ASSEMBLY FOR EAST
 WALL INCLUDING THE PROJECTION AS REQUIRED BY SEC.
 R302.1 OF 2004 FLORIDA RESIDENTIAL CODE.
  
 9- PROJECTION ON EAST WALL IS NOT ALLOWED BECAUSE IT
 DOESN'T COMPLY WITH SEC. R302.1 OF 2004 FLORIDA
 RESIDENTIAL CODE.
  
 10- OPENINGS ON EAST WALL ARE NOT ALLOWED BY SEC.
 R302.2 OF 2004 FLORIDA RESIDENTIAL CODE.
  
 11-A) SURVEY TO SPECIFY SIDE SETBACK AND DISTANCE
 FROM PROPOSED ADDITION TO EXISTING 1 STORY BUILDING TO
 VERIFY COMPLIANCE WITH SEC. R302 OF 2004 FLORIDA
 RESIDENTIAL CODE.
  
 B) SURVEY TO HAVE SURVEYOR ORIGINAL SIGNATURE AS
 REQUIRED BY SEC. 472 FLORIDA STATUTE.
  
 12- ENERGY CALCULATIONS:
 A) PROVIDE CORRECT NAME OF BULDERAND COMPLETE
 ALL-INFORMATION ON TOP OF FORM INCLUDING THE ADDRESS OF
 THIS PROJECT.
  
 B) CONDITIONED FLOOR AREA DOESN'T MATCH AREA SHOWN
 ON PLANS FOR THE ADDITION. REVISE AS REQUIRED.
  
 C) MAKE SURE UNDER ATTIC AREA ON ITEM 10(A) IS
 COORDINATED WITH ITEM 6.
  
 D) UNDER ATTIC R-VALUE DOESN'T MATCH R-VALUE
 SPECIFIED ON ARCHITECTURAL PLANS. REVISE AS REQUIRED.
  
 13- SOIL TEST REPORT ENGINEER TO PROVIDE HIS LICENSE
 NUMBER AS REQUIRED BY SEC. 61G15-23.002OF FLORIDA
 ADMINISTRATIVE CODE AND CHAPTER 471 FLORIDA STATUTE.
  
 14- TRUSS PACKAGE:
 A) LOADS DON'TMATCH LOADS SPECIFIED BY THE
 ARCHITECT OF RECORD.
 ***NOTE: COORDINATE WITH ARCHITECT FOR SPECIFIED LOADS
 TO AVOID CONFLICTS.
  
 B) IF ENGINEER WANTS TO COMPLY WITH SEC.
 61G15-31.003, THEN NEEDS TO PROVIDE THE DESIGNEROF
 RECORD NAME AND ALL SHEETS NEED TO BE NUMBERED SO THEY
 CAN BE REFERENCED BACK IN THE INDEX SHEET.
  
 C) TRUSS LAYOUT NEEDS TO BE SIGNED, SEALED, DATED
 AND WITH THE ENGINEER'S COMPLETE INFORMATION AS
 REQUIRED BY SEC. 61G15-23.002 OF FLORIDA ADMINISTRATIVE
 CODE AND CHAPTER 471 FLORIDA STATUTE.
  
 D) ARCHITECTURAL PLANS CALL FOR DOUBLE GABLE END
 TRUSSES. COORDINATE FRAMING LAYOUT WITH ARCHITECT PRIOR
 TO SUBMITTAL TO AVOID CONFLICTS.
  
 15- SHEET SP-1:
 A) REVISE CONCRETE BLOCK ALLOWABLE STRESS SHOWN ON
 TYPICAL PRIVACY WALL SECTION. SEE SEC. R606.4 OF 2004
 FLORIDA RESIDENTIAL CODE AND REVISE AS REQUIRED.
  
 B) NORTH ARROW IS INCORRECT. SEE SURVEY AND REVISE.
  
 C) TITLE BLOCK IS MISSING ARCHITECT'S LICENSE NUMBER
 AS REQUIRED BY SEC. 61G1-16.004 OF FLORIDA
 ADMINISTRATIVE CODE.
  
 16- SHEET A-1:
 A) UPDATE ALL REFERENCE STANDARDS SHOWN ON
 FOUNDATION NOTES. SEE CHAPTER 43 OF 2004 FLORIDA
 RESIDENTIAL CODE FOR CORRECT STANDARDS AND YEAR ADOPTED
 BY THIS CODE AND REVISE AS REQUIRED.
  
 B) CLARIFY THICKNESS OF CONCRETE SLAB.WALL
 SECTIONS ON SHEET A-4 CALL FOR 6" CONCRETE SLAB, WHILE
 FOUNDATION PLAN CALLS FOR 4". REVISE AS REQUIRED.
  
 C) DETAIL SECTIONS 3 AND 6 DON'T MATCH THOSE KEYED
 ON TYPICAL OPENING DETAIL #4.REVISE AS REQUIRED.
  
 17- SHEET A-2:SPECIFY SIZE OF TREADS AND RISERS AT
 STEPS BY FRENCH DOORS TO VERIFY COMPLIANCE WITH SEC.
 R311.5.3 OF 2004 FLORIDA RESIDENTIAL CODE.
 ALSO, STEPS ARE NOT DRAWN TO SCALE. THEY ARE SHOWN AS
 6"WIDE TREADS. REVISE AS REQUIRED.
  
 18- SHEET A-3:REAR ELEVATION CALLS FOR NEW 2X8 KNEE
 WALL. THIS DOESN'T MATCH INFORMATION SHOWN ON TYPICAL
 WALL SECTION 1/A-4 AND BUILDING SECTION 2/A-4. REVISE
 AS REQUIRED TO MATCH.
  
 18- SHEET A4:
 A) ROOF FRAMING PLAN IS MISSING THE RIDGE LINE AND
 DOESN'T MATCH TRUSS LAYOUT.COORDINATE WITH TRUSS
 ENGINEER AND REVISE AS REQUIRED.
  
 B) CLEARLY SPECIFY ALLDEAD AND LIVE LOADS
 INCLUDING THE ATTIC LIVE LOAD AS REQUIRED BYSEC. R301
 AND TABLE R301.5 OF 2004 FLORIDA RESIDENTIAL CODE.
 ***NOTE: COORDINATE THESE LOADSWITH TRUSS ENGINEER.
  
 C) LOADS SPECIFIED ON ITEM #3 OF ROOF FRAMING NOTES
 DON'T MATCH WITH THOSE LOADS SPECIFIED ON TYPICAL END
 DETAIL. REVISE AS REQUIRED.
  
 D) ROOF NAILING NOTE AND SPECIFICATIONS FOR ROOF
 SHEATHING FASTENING ON WALL SECTIONS 1 AND 2 DON'T
 MATCH.SEE SEC. R803.2.3.1 OF 2004 FLORIDA
 RESIDENTIAL CODE FOR MINIMUM TYPE OF NAIL AND FASTENER
 SPACING REQUIRED INCLUDING FOR ROOF ZONE 3 AND REVISE
 AS REQUIRED.
  
 E) SECTIONS 1,2 AND 4 NEED TO SPECIFY ALL
 FASTENERS FOR GABLE END TRUSSES, GABLE END RAFTERS AND
 TOP AND BOTTOM OF2X8 KNEE WALL. SEC. 106.1.2 CITY
 AMENDMENTS TO FBC 2004 TO VERIFY COMPLIANCE WITH
 CALCULATED UPLIFT LOADS PERSEC. R301OF 2004 FLORIDA
 RESIDENTIAL CODE. SEE SIMPSON CATALOG AND SPECIFY
 CONNECTORACCORDING TO APPLICATION WOOD TO WOOD
 CONNECTOR OR WOOD TO MASONRY CONNECTOR.
  
 F) REVISE ROOF FRAMING NOTE #6. IT'S THE ARCHITECT
 RESPONSIBILITY TO SPECIFY CONNECTIONS, NOT THE FBC.
  
 19- DETAILS 3 AND 4DON'T MATCH THE DETAIL SECTION AS
 KEYED ON THE ROOF FRAMING PLAN. REVISE AS REQUIRED.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER