2008-10-15 10:41:08****CORRECTIONS****
 ****ENERGY CALCS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
 1. THE ENGINEER SUBMITTED A LETTER STATING THAT THREE
 INCHES OF INSULATION WAS INSTALLED, AND R20 PROVIDED.
 PLEASE PROVIDE SPECS FOR THE INSULATION AS MOST
 INSULATION RANGES FROM 2.5 TO 6 R VALUE PER INCH.
 COMPLIANCE IS NOT CLEAR, FBC13-404.1.
  
 THE SPEC SHEETS FOR THE ROOF SHOWING COMPLIANCE WITH
 R19 REQUIREMENTS CAN BE SUBMITTED VIA EMAIL. THIS WILL
 BE HELD AT MY DESK PENDING RECEIPT FOR THREE BUSINESS
 DAYS. PLEASE CONTACT ME IF YOU NEED ASSISTANCE.
  