Plan Review Notes
Plan Review Notes For Permit 07100650
Permit Number 07100650
Review Stop B
Sequence Number 6
Notes
Date Text
2008-07-29 11:17:10****CORRECTIONS****
 ***REVISION***
 NEW ROOF PRODUCT APPROVALS
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.SEE THE ENERGY CALCS WHICH WERE SUBMITTED WITH THE
 BUILDING.THE ENERGY CALCS SPECIFIED A SHINGLE ROOF,
 1/2" WOOD DECK, WOOD TRUSSES, 9" BATT INSULATION,
 GYPSUM BOARD.THIS IS NOT CONSISTENT WITH THE PRODUCT
 APPROVALS SUBMITTED.
  
 2.ENERGY CALCS INPUT DATA REPORT SPECIFIES CONCRETE
 SLAB WITH CARPET AND RUBBER PAD.IS THIS CONSISTENT
 WITH THE SPECIFICATIONS ON THE PLAN?PLEASE CONFIRM
 THIS AND ALL OTHER ITEMS ON THE INPUT DATA REPORT.
  
 3.THE NEW REVISED ENERGY CALCS ARE TO BE CERTIFIED BY
 ALL DESIGN PROFESSIONALS INCLUDING THE ARCHITECT,
 FBC13-103.1.1.1.PLEASE INFORM ARCHITECT OF HIS
 RESPONSIBILITY TO CONFIRM THAT ALL ITEMS ON THE INPUT
 DATA REPORT ARE CONSISTENT WITH HIS DESIGN AND THE
 PLANS SUBMITTED.
  
  