| 2008-10-28 08:46:51 | |
| | ** DENIED 2ND REVIEW** |
| | |
| | |
| | 1) NOTE: AS NOTED ON PREVIOUS REVIEW, PLEASE SEE |
| | 13-101.1.6 |
| | 13-101.1.6 SHELL BUILDINGS. |
| | NONRESIDENTIAL BUILDINGS THAT ARE PERMITTED PRIOR TO |
| | DESIGN COMPLETION OR WHICH WILL BE FINISHED IN SECTIONS |
| | AT A TIME AFTER CONSTRUCTION OF THE SHELL SHALL COMPLY |
| | WITH EITHER METHOD B OR C OF SUBCHAPTER 13-4 OF THE |
| | CODE PRIOR TO GRANTING OF A PERMIT TO BUILD. ALL |
| | ASSUMPTIONS MADE ABOUT FEATURES NOT INSTALLED UNTIL |
| | LATER THAT ARE NOT ON THE BUILDING PLANS SHALL BE |
| | LISTED AND APPENDED TO THE COMPLIANCE FORM SUBMITTED TO |
| | THE BUILDING DEPARTMENT. UNLESS THE BUILDING IS |
| | COMPLETED AS PER ALL ASSUMPTIONS MADE IN THE ORIGINAL |
| | CODE COMPLIANCE SUBMITTAL, A REVISED CODE SUBMITTAL(S) |
| | USING METHODS A, B OR C SHALL BE SUBMITTED WHEN |
| | COMPLETION OF THE BUILDING (OR PART OF THE BUILDING) IS |
| | PERMITTED. |
| | |
| | ** PLEASE SEE SENTENCE #2 ABOVE. HOW CAN THE TOTAL |
| | WATTAGE *ASSUMED* FOR THE SHELL OF THE BUILD OUT BE |
| | THIS LOW? |
| | |
| | |
| | |
| | **IMPORTANT** |
| | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED |
| | INTO TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| | ANY DELAYS. |
| | |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |
| | |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| | |