| 2008-09-04 08:17:00 | REVIEW: REVISED ENERGY CALCULATIONS |
| | ACTION: DENIED |
| | |
| | FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS |
| | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH |
| | |
| | 1. SHELL BUILDINGS SHALL COMPLY WITH THIS CODE BY |
| | METHOD B OR METHOD C. ONCE ALL ENERGY-RELATED DESIGN |
| | PARAMETERS ARE KNOWN, A METHOD A CALCULATION MAY BE |
| | RESUBMITTED IN ACCORDANCE WITH FBCB 13-400.2.A.2. ALL |
| | ASSUMPTIONS MADE ABOUT FEATURES NOT INSTALLED UNTIL |
| | LATER THAT ARE NOT ON THE BUILDING PLANS SHALL BE |
| | LISTED AND APPENDED TO THE COMPLIANCE FORM SUBMITTED TO |
| | THE BUILDING DEPARTMENT IN ACCORDANCE WITH FBCB |
| | 13-101.1.6. |
| | |
| | 2. COOLING LOAD CALCULATIONS SHALL BE ATTACHED TO THE |
| | ENERGY CODE COMPLIANCE FORMS IN ACCORDANCE WITH FBCB |
| | 13-407.1.ABC.1. |
| | |
| | 3. THE NAMES AND LICENSE NUMBERS OF THE ARCHITECT, |
| | LIGTING AND ELECTRICAL DESIGNERS ARE MISSING FROM THE |
| | CERTIFICATIONS PAGE (PAGE 3 OF THE COMPLIANCE FORM). |
| | DESIGN PROFESSIONALS RESPONSIBLE UNDER FLORIDA LAW FOR |
| | THE DESIGN OF LIGHTING, ELECTRICAL, MECHANICAL, AND |
| | PLUMBING SYSTEMS AND THE BUILDING SHELL, SHALL CERTIFY |
| | COMPLIANCE OF THOSE BUILDING SYSTEMS WITH THE CODE BY |
| | SIGNING AND PROVIDING THEIR PROFESSIONAL REGISTRATION |
| | NUMBER ON THE ENERGY CODE FORM PROVIDED AS PART OF THE |
| | PLANS AND SPECIFICATIONS TO THE BUILDING DEPARTMENT. |
| | TYPED NAMES AND REGISTRATION NUMBERS MAY BE PROVIDED IN |
| | LIEU OF A SIGNATURE WHERE ALL RELEVANT INFORMATION HAS |
| | BEEN INCLUDED ON SIGNED AND SEALED PLANS IN ACCORDANCE |
| | WITH FBCB 13-103.1.1.1. |
| | |
| | PLEASE MAKE ALL NECESSARY CORRECTIONS AND RESUBMIT FOR |
| | REVIEW. |
| | |