Plan Review Notes
Plan Review Notes For Permit 07100650
Permit Number 07100650
Review Stop B
Sequence Number 3
Notes
Date Text
2008-04-14 11:29:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 COMMENTS FROM PREVIOUS REVIEW:
  
 1.)THIS IS AN AT RISK PERMIT (SHELL ONLY).
 INFORMATIONAL; NOT REQUIRED TO BE ADDRESSED.
  
 2-5). ADDRESSED.
  
 6.)SEPARATE PERMITS WILL BE REQUIRED; INFORMATIONAL
 ONLY (SIGNS, ETC.).
  
 7.-8.)ADDRESSED.
  
 9.)SEE C7, TYPICAL PARKING DETAIL.THE DETAIL STATES
 THAT THE SURFACE WILL COMPLY WITH FIGURE 40(A) AND (B),
 BUT SEE OTHER COMMENTS REGARDING TACTILE SURFACE.
 GROOVES ARE NOT PERMITTED OUTDOORS, AND ADA TITLE III
 REQUIRES TRUNCATED DOMES, ADA 4.1.3.
  
 10-11.)ADDRESSED.
  
 12.)THE REAR DOOR WILL BE REQUIRED TO BE AN
 ACCESSIBLE EXIT FBC11-4.1.3(9).PLEASE SHOW ACCESSIBLE
 MEANS OF EGRESS, FBC11-3 (SHOW MAXIMUM SLOPE FROM DOOR
 TO PUBLIC WAY, WIDTH OF SIDEWALK BETWEEN REAR DOOR AND
 LOADING AREA AT NORTH SIDE).
  
 2ND REVIEW - NOT ADDRESSED.IT IS NOT CLEAR WHERE
 ACCESS TO THE PUBLIC SIDEWALK IS LOCATED, IF ANY.NONE
 SHOWN ON SHEET 1 PREPARED BY LAND DESIGN SOUTH, BUT
 THIS IS NOT SHOWN FOR THE ACCESSIBLE PARKING ACCESS
 AISLE EITHER.THE REQUIREMENT FOR THE ACCESS AISLE TO
 SIDEWALK CHANGE IN ELEVATION REQUIREMENT IS COMMON
 KNOWLEDGE, BUT THE REQUIREMENT OF ACCESSIBILITY TO THE
 PUBLIC WAY MAY NOT BE.PLEASE SHOW ON THE PLANS AS
 REQUESTED.SHEET A1 IS NOT CLEAR; WHAT ARE THE DASHED
 LINES?I CANNOT DETERMINE WHETHER OR NOT THE CONCRETE
 IS CONTINUOUS, OR IF THE DASHED LINES REPRESENT A CURB
 WITH A CHANGE IN ELEVATION EXCEEDING THAT PERMITTED BY
 FBC11-3.
  
 3RD REVIEW, LAND DESIGN SOUTH SHEETS HAVE BEEN REMOVED
 AND THE COMMENT IS STILL NOT ADDRESSED.SEE THE REAR
 EXIT DOOR.THERE SHOULD BE A CURB RAMP SO THAT
 DISABLED INDIVIDUALS CAN GET AWAY FROM THE BUILDING.
 SEE SHEET C4, NONE SHOWN.THERE SHOULD BE AN
 ACCESSIBLE ROUTE TO THE PUBLIC WAY, BUT THIS APPEARS TO
 BE FULLY LANDSCAPED WITH CURBS, SEE THE SOUTH PROPERTY
 LINE.
  
 IT IS NOT CLEAR WHICH DESIGNER, IF ANY, IS RESPONSIBLE
 FOR THE ACCESSIBILITY TO THE SITE.THE ARCHITECT?S
 RESPONSE LETTER STATES THAT THE LANDSCAPE ARCHITECT
 WILL SHOW THIS ON THEIR PLAN.IS THE NEW LANDSCAPE
 ARCHITECT, DAVE BODKER, AWARE THAT HIS PLAN IS BEING
 USED TO SHOW CODE COMPLIANCE FOR FLORIDA AND FEDERAL
 ACCESSIBILITY REQUIREMENTS?IT APPEARS THAT HIS PLAN
 IS FOR TREES AND SHRUBS, NOTHING RELATED TO
 ACCESSIBILITY WAS SHOWN.THE CIVIL ENGINEER?S TITLE
 BLOCK STATES THAT THEY ALSO DO LANDSCAPE ARCHITECTURE;
 IS THIS THE LANDSCAPE ARCHITECT PLAN THE ARCHITECT IS
 REFERRING TO?
  
 13.)ADDRESSED.
  
 14.) PROVIDE A SITE PLAN SHOWING DISTANCE BETWEEN THE
 BUILDINGS AND LOCATION OF THIS BUILDING ON THE LOT. THE
 SITE PLAN PREVIOUSLY IN THE PACKAGE HAS BEEN REMOVED,
 NEW SITE PLAN DOES NOT HAVE ALL OF THE REQUIRED
 DIMENSIONS.
  
 15-16.) ADDRESSED.
  
 17.)FOR THE FLAT ROOF, SELECT AN APPROVED ASSEMBLY.
  
 2ND REVIEW; YOU ARE REQUESTING A ROOF PERMIT.THIS
 INFORMATION IS REQUIRED SO THAT CODE COMPLIANCE CAN BE
 DETERMINED.THE RESPONSE LETTER STATES "SEE ATTACHED
 PRODUCT APPROVAL INFORMATION SHEETS."NOTHING WAS
 PROVIDED AND THE APPROVED ASSEMBLY (CHOICES LOCATED
 BETWEEN SHEETS 7 THROUGH 18 OF THE NOA) WAS NOT
 SELECTED.
  
 3RD REVIEW, ARCHITECT?S RESPONSE IS THAT THIS WILL BE
 DONE BY THE ROOFING CONTRACTOR.IF THIS IS NOT DONE
 PRIOR TO PERMIT ISSUANCE, THE ROOF PERMIT ASSIGNED TO
 THIS PROJECT WILL BE VOIDED AND THE ROOF CONTRACTOR
 WILL BE REQUIRED TO APPLY FOR SEPARATE PERMIT WITH THE
 REQUIRED INFORMATION.THIS WILL NOT DELAY PERMIT
 ISSUANCE OF THE MAIN BUILDING.
  
 18.)FOR THE FLAT ROOF, SPECIFY ENHANCED FASTENING FOR
 CORNER AND PERIMETER ZONES.THIS MUST BE PREPARED BY
 AN ARCHITECT, ENGINEER, OR REGISTERED ROOF CONSULTANT
 AS PER GENERAL LIMITATION 7 ON THE NOA.
  
 3RD REVIEW, ARCHITECT?S RESPONSE IS THAT THIS WILL BE
 DONE BY THE ROOFING CONTRACTOR.IF THIS IS NOT DONE
 PRIOR TO PERMIT ISSUANCE, THE ROOF PERMIT ASSIGNED TO
 THIS PROJECT WILL BE VOIDED AND THE ROOF CONTRACTOR
 WILL BE REQUIRED TO APPLY FOR SEPARATE PERMIT WITH THE
 REQUIRED INFORMATION.THIS WILL NOT DELAY PERMIT
 ISSUANCE OF THE MAIN BUILDING.
  
 19.)ADDRESSED.
  
 20.)ON THE ROOF TILE PRODUCT APPROVAL, MARK METHOD OF
 ATTACHMENT.IF YOU ARE USING A FOAM ADHESIVE, PLEASE
 PROVIDE PRODUCT APPROVALS, FAC9B72.
  
 2ND REVIEW - THIS INFORMATION IS REQUIRED AT THIS TIME
 AS YOUR ROOFER HAS SIGNED ON AND A ROOF PERMIT HAS BEEN
 ASSIGNED.IF YOU WOULD LIKE, PLEASE REMOVE THIS,
 CANCEL THE PERMIT THROUGH THE FRONT COUNTER WHEN
 RESUBMITTING, AND THE ROOFING CONTRACTOR CAN APPLY FOR
 A SUBCONTRACTOR PERMIT WITH ALL OF THE REQUIRED
 INFORMATION.PRODUCT APPROVALS ARE TO REMAIN IN THE
 PACKAGE.
  
 3RD REVIEW, ARCHITECT?S RESPONSE IS THAT THIS WILL BE
 DONE BY THE ROOFING CONTRACTOR.IF THIS IS NOT DONE
 PRIOR TO PERMIT ISSUANCE, THE ROOF PERMIT ASSIGNED TO
 THIS PROJECT WILL BE VOIDED AND THE ROOF CONTRACTOR
 WILL BE REQUIRED TO APPLY FOR SEPARATE PERMIT WITH THE
 REQUIRED INFORMATION.THIS WILL NOT DELAY PERMIT
 ISSUANCE OF THE MAIN BUILDING.
  
 21-23.)ADDRESSED.
  
 24.)THE ADDRESS FOR THE ENGINEER, RICHARD ADAMS PE,
 CONFLICTS WITH DBPR WEBSITE.
 PLEASE CORRELATE.
  
 3RD REVIEW, NOT ADDRESSED.PLEASE ADVISE AS TO HOW
 THIS WILL BE RESOLVED.
  
 25.)PLEASE KEEP THE IMPACT FEE STAMP AND RECEIPT IN
 THE PERMIT PACKAGE.
  
 WHEN RESUBMITTING, PLEASE PROVIDE A RESPONSE LETTER
 INDICATING HOW ALL COMMENTS HAVE BEEN ADDRESSED.ONLY
 EIGHT OUT OF 22 COMMENTS WERE INCLUDED IN THE RESPONSE
 LETTER.OTHER COMMENTS CAN BE ADDRESSED WITH A LETTER
 FROM THE CONTRACTOR OR OTHER PARTY FAMILIAR WITH THE
 PROJECT IF THE ARCHITECT IS NOT RESPONSIBLE FOR THE
 OTHER ITEMS.NOTE THAT SEVERAL ITEMS WERE NOT
 ADDRESSED.PLEASE ADDRESS ALL COMMENTS.
  
 NEW COMMENTS:
  
 NOTE THAT NEW PLANS WERE SUBMITTED, CIVIL SHEETS, IN
 PLACE OF LAND DESIGN SOUTH.
  
 26. REGARDING THE DETECTABLE WARNINGS ON THE PLAN
 FBC11-4.29, SEE ADA 4.29.2* DETECTABLE WARNINGS ON
 WALKING SURFACES. DETECTABLE WARNINGS SHALL CONSIST OF
 RAISED TRUNCATED DOMES WITH A DIAMETER OF NOMINAL 0.9
 IN (23 MM), A HEIGHT OF NOMINAL 0.2 IN (5 MM) AND A
 CENTER-TO-CENTER SPACING OF NOMINAL 2.35 IN (60 MM) AND
 SHALL CONTRAST VISUALLY WITH ADJOINING SURFACES, EITHER
 LIGHT-ON-DARK, OR DARK-ON-LIGHT.
  
 A. REVISE CONCRETE SIDEWALK CURB RAMP DETAIL, SHEET C8.
 HTTP://WWW.ACCESS-BOARD.GOV/ADAAG/DWS/UPDATE.HTM.
 TACTILE SURFACE SHOWN, PLEASE REVISE DETAIL TO SHOW
 TRUNCATED DOMES.
  
 B. REVISE CONCRETE SIDEWALK CURB RAMP DETAIL, SHEET C8,
 TO SHOW THE VISUAL CONTRAST REQUIRED.IF THE DESIGN
 INTENT AND COMPLIANCE ARE NOT CLEAR, CALCULATIONS PER
 ADA4.29.2 MAY BE REQUIRED.
  
 C. NOTE THAT THE DETAIL STATES THAT IT IS TO CONFORM TO
 FDOT STANDARD 304, BUT THE DETAIL ON THE PLAN IS
 OUTDATED.PLEASE SEE THE CURRENT DETAIL,
 HTTP://WWW.DOT.STATE.FL.US/RDDESIGN/PUBLICATIONS/PUB.HT
 M.NOTE THAT THE CURRENT STANDARD ALSO REQUIRES
 TRUNCATED DOMES.PER RASIK CHOKSHI, CITY OF WEST PALM
 BEACH ENGINEERING SERVICES, PLEASE CHECK ALL DETAILS AT
 IT APPEARS THAT OTHER DETAILS ARE OUTDATED (DATED 2004
 AND 2006).
  
 D. C4, SIDEWALK FROM THE FRONT DOOR GOING SOUTH, THERE
 SHOULD BE A DETECTABLE WARNING ON THE WEST SIDE WHERE
 THE SIDEWALK CROSSES THE PARKING LOT.A DETECTABLE
 WARNING IS SHOWN ON THE EAST SIDE OF THIS CROSSING BUT
 NOT THE WEST SIDE.
  
 E. C4, A DETECTABLE WARNING IS SHOWN ON THE SIDEWALK AT
 THE ACCESSIBLE PARKING ACCESS AISLE AND NO CURB RAMP
 SHOWN (THERE IS A NOTE STATING THAT IT WILL NOSE DOWN).
 PLEASE REVISE.NOTE THAT DETECTABLE WARNING AT A
 SIDEWALK WHERE IT DOES NOT CROSS TRAFFIC IS CONFUSING.
 THIS SHOULD BE A PART OF THE CURB RAMP ONLY.
  
 F. PLEASE NOTE THAT DETECTABLE WARNINGS WERE PREVIOUSLY
 ENFORCED IN THE FIELD.TO AVOID INSPECTION ISSUES, ALL
 REQUIRED DETECTABLE WARNINGS FOR THE SITE AND FOR THE
 ACCESSIBLE ROUTE ARE TO BE SHOWN ON THE PLAN AT THE
 TIME OF ISSUANCE.
  
 27.)PLEASE HAVE THE ARCHITECT CERTIFY THE ENERGY
 CALCS, FBC13-103.1.1.1.
  
 28.)REGARDING EXITING ISSUES, PLEASE SEE FBC1023.6 AS
 WELL AS THE DEFINITIONS FOR EXIT DISCHARGE AND PUBLIC
 WAY.PLANS DO NOT CURRENTLY SHOW CODE COMPLIANCE, SEE
 OTHER COMMENTS.IS THERE A PERMANENT DEEDED ACCESS FOR
 THE SIDEWALK GOING TO THE WEST AND EVENTUALLY TO THE
 PUBLIC WAY?WHERE IS THE PUBLIC WAY IN RELATION TO THE
 LOTS?AS DISCUSSED, A COMPLETE SITE PLAN WILL BE
 SUBMITTED FOR PRELIMINARY BUILDING REVIEW PRIOR TO
 RESUBMITTAL OF THE PLANS.