Plan Review Notes
Plan Review Notes For Permit 07100650
Permit Number 07100650
Review Stop M
Sequence Number 2
Notes
Date Text
2008-01-22 10:48:45REVIEW #: 2ND
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS
  
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH
 PREVIOUS REVIEW COMMENTS AS WELL AS DESIGNER'S WRITTEN
 RESPONSES FOR THE PURPOSE OF CONTINUITY.
  
 1 THRU 3: OK
  
 4. THE SYSTEM SIZING SUMMARY IS TO BE SIGNED AND SEALED
 BY THE ENGINEER AND ATTACHED TO THE CODE COMPLAINCE
 FORM IN ACCORDANCE WITH FBC 13-407.1.ABC.1. SEE THE
 TEXT OF EXCEPTION #1 BELOW:
 "WHERE MECHANICAL SYSTEMS ARE DESIGNED BY AN ENGINEER
 REGISTERED IN THE STATE OF FLORIDA, THE ENGINEER HAS
 THE OPTION OF SUBMITTING A SIGNED AND SEALED SUMMARY
 SHEET IN LIEU OF THE COMPLETE SIZING CALCULATION(S)."
 PLEASE PROVIDE SIGNED AND SEALED SYSTEM SIZING SUMMARY
 ATTACHED TO THE ENERGY CALCULATIONS AND RESUBMIT. THIS
 ITEM COULD BE HANDLED AS A PROVISO IF IT WERE THE ONLY
 ITEM OUTSTANDING.
  
 5 THRU 7: OK
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]
  