| 2008-12-22 10:03:18 | ****CORRECTIONS**** |
| | ****SHUTTER STORAGE (VERTICAL) DETAIL SUBMITTED VIA |
| | EMAIL**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBC FLORIDA BUILDING CODE 2004 |
| | FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING |
| | CODE |
| | FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL |
| | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 |
| | FAC FLORIDA ADMINISTRATIVE CODE |
| | FS FLORIDA STATUTE |
| | |
| | 1. THE DETAIL DOES NOT PROVIDE BASIC INFORMATION SUCH |
| | AS THE WEIGHT OF THE SHUTTERS, STORAGE LOCATION, HOW |
| | THE INSTALLATION CONTRACTOR WILL GET ACCESS TO THE |
| | SHUTTERS AS THEY ARE PADLOCKED, ETC. THE DETAIL IS TO |
| | BE PREPARED BY A DESIGN PROFESSIONAL. |
| | |
| | 2. A DETAIL WILL NOT BE NECESSARY UNTIL THE USE OF |
| | REMOVABLE SHUTTERS HAS BEEN APPROVED. PLEASE REVISE THE |
| | PRESTORM PREPARATION PLAN AS REQUESTED. FOR YOUR |
| | CONVENIENCE, THE COMMENTS ARE AS FOLLOWS: |
| | |
| | COMMENTS FROM PREVIOUS REVIEW: |
| | |
| | 4. TO CLARIFY, THE ENTRY DOOR HAS FIXED GLASS ABOVE. |
| | WILL THIS ALSO BE IMPACT? THIS OPENING DOES NOT SEEM TO |
| | APPEAR ON THE INSTALLATION SCHEDULE, BUT IS NOT NOTED |
| | ON THE REVISED SHEET A1. PLEASE PROVIDE A FLOOR PLAN |
| | WITH NUMBERS TO CORRELATE WITH THE INSTALLATION |
| | SCHEDULE SO THAT SCOPE IS CLEAR, FBC*106, FBC16. **THE |
| | PLAN DOES ***NOT*** NEED TO BE REVISED!!!!** IN THE |
| | INTEREST OF TIME, PLEASE PROVIDE THE INFORMATION WITH |
| | THE INSTALLATION SCHEDULE. PROVIDE A LOCATION PLAN |
| | WHICH SHOWS THE PROPOSED SHUTTER LOCATION AND THIS |
| | WINDOW CAN BE NOTED AS EITHER IMPACT OR BE INCLUDED ON |
| | THE INSTALLATION SCHEDULE. |
| | |
| | 5. N/A. |
| | |
| | 6. WHEN RESUBMITTING, PLEASE PROVIDE TWO COMPLETE SETS |
| | OF PERMIT DOCUMENTS. THE PRODUCT APPROVALS FOR THE |
| | IMPACT DOORS ARE NOT REQUIRED AS THEY ARE ALREADY |
| | STAMPED AND ON FILE. HOWEVER, ONLY ONE SET OF THE STORM |
| | PANEL PRODUCT APPROVAL WAS SUBMITTED. PLEASE PROVIDE |
| | TWO LEGIBLE SETS. |
| | |
| | 7. THE PRESTORM PREPARATION PLAN STATES THAT THE PANELS |
| | WILL BE STORED IN A CLOSET IN THE TENANT BUILDOUT, BUT |
| | NO CLOSET IS SHOWN ON THE TENANT BUILDOUT PLAN. IT ALSO |
| | STATED THAT THE SHUTTERS WILL BE INSTALLED VERTICALLY; |
| | PLEASE PROVIDE A DETAIL OF HOW THE SHUTTERS WILL BE |
| | SECURED. ALSO, PLEASE STATE HOW THE SHUTTES WILL BE |
| | SECURED FROM THEFT. THIS INFORMATION CAN BE SUBMITTED |
| | VIA EMAIL. AS THE PRESTORM PREPARATION PLAN IS |
| | CURRENTLY IN REVIEW BY ROBERT BROWN, PLEASE SUBMIT THIS |
| | INFORMATION (STORAGE LOCATION, SECUREMENT FROM THEFT) |
| | AS SOON AS POSSIBLE SO THAT THE SUPPORTING INFORMATION |
| | CAN BE FORWARDED TO MR. BROWN PRIOR TO HIS REVIEW. |
| | |
| | 8. (REVISED) USE OF REMOVABLE SHUTTERS ON COMMERCIAL |
| | BUILDINGS MUST BE APPROVED BY THE BUILDING OFFICIAL. |
| | THE PLAN SUBMITTED IS PENDING REVIEW BY ROBERT BROWN. |
| | INCLUDE ALL INFORMATION REQUIRED IN ITEM 7. THE DETAIL |
| | OF HOW THE SHUTTERS WILL BE SECURED CAN BE A PROVISO |
| | ITEM. PLEASE EMAIL THE REVISED PLAN TO [email protected]. |
| | PLEASE CONTACT ME IF YOU NEED ASSISTANCE. |
| | |
| | |
| | |
| | |
| | |
| | |