| 2008-12-02 10:42:34 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBC FLORIDA BUILDING CODE 2004 |
| | FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING |
| | CODE |
| | FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL |
| | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 |
| | FAC FLORIDA ADMINISTRATIVE CODE |
| | FS FLORIDA STATUTE |
| | |
| | 1. PLEASE PROVIDE LEGIBLE DOCUMENTS. THE PRODUCT |
| | APPROVAL FOR THE ALUMINUM STORM PANELS ARE DIFFICULT TO |
| | READ ON THE INTERNET, AND THE COPY PROVIDED IS A COPY |
| | OF A FAX, MAKING IT IMPOSSIBLE TO READ. PLEASE PRINT |
| | TWO COPIES FROM THE WEBSITE, WWW.FLORIDABUILDING.ORG. |
| | BE SURE TO CHANGE THE CODE VERSION TO 2004 ON THE |
| | WEBSITE (DEFAULT IS 2007). |
| | |
| | 2. PLEASE SPECIFY DESIGN PRESSURES ON THE INSTALLATION |
| | SCHEDULE. |
| | |
| | 3. THE SHUTTER CONNECTION MOUNTING TYPE AND THE |
| | SPECIFIC ANCHOR TYPE SHOULD CORRELATE WITH THE ANCHOR |
| | CHARTS ON THE PRODUCT APPROVAL; FOR INSTANCE, SEE PAGE |
| | 6. PLEASE REVISE THE INSTALLATION SCHEDULE. |
| | |
| | 4. TO CLARIFY, THE ENTRY DOOR HAS FIXED GLASS ABOVE. |
| | WILL THIS ALSO BE IMPACT? THIS OPENING DOES NOT SEEM TO |
| | APPEAR ON THE INSTALLATION SCHEDULE, BUT IS NOT NOTED |
| | ON THE REVISED SHEET A1. PLEASE PROVIDE A FLOOR PLAN |
| | WITH NUMBERS TO CORRELATE WITH THE INSTALLATION |
| | SCHEDULE SO THAT SCOPE IS CLEAR, FBC*106, FBC16. **THE |
| | PLAN DOES ***NOT*** NEED TO BE REVISED!!!!** IN THE |
| | INTEREST OF TIME, PLEASE PROVIDE THE INFORMATION WITH |
| | THE INSTALLATION SCHEDULE. PROVIDE A LOCATION PLAN |
| | WHICH SHOWS THE PROPOSED SHUTTER LOCATION AND THIS |
| | WINDOW CAN BE NOTED AS EITHER IMPACT OR BE INCLUDED ON |
| | THE INSTALLATION SCHEDULE. |
| | |
| | 5. N/A. |
| | |
| | 6. WHEN RESUBMITTING, PLEASE PROVIDE TWO COMPLETE SETS |
| | OF PERMIT DOCUMENTS. THE PRODUCT APPROVALS FOR THE |
| | IMPACT DOORS ARE NOT REQUIRED AS THEY ARE ALREADY |
| | STAMPED AND ON FILE. HOWEVER, ONLY ONE SET OF THE STORM |
| | PANEL PRODUCT APPROVAL WAS SUBMITTED. PLEASE PROVIDE |
| | TWO LEGIBLE SETS. |
| | |
| | 7. THE PRESTORM PREPARATION PLAN STATES THAT THE PANELS |
| | WILL BE STORED IN A CLOSET IN THE TENANT BUILDOUT, BUT |
| | NO CLOSET IS SHOWN ON THE TENANT BUILDOUT PLAN. IT ALSO |
| | STATED THAT THE SHUTTERS WILL BE INSTALLED VERTICALLY; |
| | PLEASE PROVIDE A DETAIL OF HOW THE SHUTTERS WILL BE |
| | SECURED. ALSO, PLEASE STATE HOW THE SHUTTES WILL BE |
| | SECURED FROM THEFT. THIS INFORMATION CAN BE SUBMITTED |
| | VIA EMAIL. AS THE PRESTORM PREPARATION PLAN IS |
| | CURRENTLY IN REVIEW BY ROBERT BROWN, PLEASE SUBMIT THIS |
| | INFORMATION (STORAGE LOCATION, SECUREMENT FROM THEFT) |
| | AS SOON AS POSSIBLE SO THAT THE SUPPORTING INFORMATION |
| | CAN BE FORWARDED TO MR. BROWN PRIOR TO HIS REVIEW. |
| | |
| | 8. USE OF REMOVABLE SHUTTERS ON COMMERCIAL BUILDINGS |
| | MUST BE APPROVED BY THE BUILDING OFFICIAL. THE PLAN |
| | SUBMITTED IS PENDING REVIEW BY ROBERT BROWN. HOWEVER, |
| | IT WOULD BE HELPFUL IF THE PLAN SUBMITTED COULD BE |
| | REVISED TO INCLUDE THE INFORMATION IN ITEM 7 SO THAT HE |
| | HAS COMPLETE INFORMATION UPON WHICH TO MAKE HIS |
| | DECISION. THE DETAIL OF HOW THE SHUTTERS WILL BE |
| | SECURED CAN BE A PROVISO ITEM. PLEASE EMAIL THE REVISED |
| | PLAN TO [email protected]. PLEASE CONTACT ME IF YOU NEED |
| | ASSISTANCE. |
| | |
| | |
| | |
| | |
| | |
| | |