Plan Review Notes
Plan Review Notes For Permit 07100650
Permit Number 07100650
Review Stop B
Sequence Number 11
Notes
Date Text
2008-10-22 13:57:44****CORRECTIONS****
 ****REVISION, FROM IMPACT GLASS TO NON IMPACT GLAZING,
 STORM PANELS, AND PRE-STORM PREPARATION PLAN***
 ****SHUTTER PERMIT APPLIED UNDER 08090146, NOW
 INCORPORATED INTO BUILDING PERMIT PER LUIS MARTINEZ****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
 COMMENTS FROM FIRST REVIEW, SHUTTER PERMIT 08090146
  
 1. IMPACT RATED PRODUCT APPROVALS WERE SUBMITTED FOR
 THE BUILDING, 07100650. IF YOU PROPOSE TO USE NON RATED
 PRODUCTS, HAVE THE PROPOSED PRODUCTS REVIEWED BY THE
 ARCHITECT FBC*106.3.3 AND SUBMIT AS A REVISION TO
 07100650.
  
 A. SHEET A1, REVISE NOTE REGARDING USE OF STORM PANELS.
 THE FRONT DOOR, A REQUIRED EXIT, CANNOT BE OBSTRUCTED
 BY REMOVABLE PANELS FBC1003.6.
  
 B. THE PRODUCT APPROVALS ARE TO BE REVIEWED BY DESIGNER
 OF RECORD FBC*106.3.3. THIS CAN BE DONE BY EITHER A
 LETTER, SHOP DRAWING REVIEW STAMP, SPECIFYING THE
 PRODUCTS IN THE SIGNED AND SEALED PLAN, OR ANY OTHER
 METHOD WHICH SHOWS COMPLIANCE WITH FBC*106.3.3.
  
 C. NOA 06-0818.02, ARCH ALUMINUM NON-IMPACT OUTSWING
 DOOR WAS SUBMITTED. SEE OTHER COMMENTS REGARDING
 FBC1003.6, MEANS OF EGRESS CONTINUITY.
  
 D. NOA 06-0818.02, SEE SHEET 1 OF 9; THIS PRODUCT IS
 NOT TO BE USED WHERE WATER INFILTRATION IS NOT
 ACCEPTABLE. AS THE OVERHANG IS 2', THE ANGLE (BOTTOM OF
 DOOR TO EDGE OF OVERHANG) APPEARS TO BE LESS THAN THE
 45 DEGREES REQUIRED. PLEASE ADDRESS.
  
 E. NOA 05-0902.01, ARCH ALUMINUM SERIES 4500 STOREFRONT
 NON-IMPACT, APPEARS TO BE CODE COMPLIANT (DESIGN
 PRESSURES). PLEASE ADDRESS THE OTHER COMMENTS REGARDING
 REVIEW BY DESIGNER OF RECORD AND IMPACT PROTECTION.
  
 F. THE SHOP DRAWINGS PREPARED BY ENGINEERING EXPRESS IS
 DELEGATED ENGINEERING; PLEASE HAVE REVIEWED BY DESIGNER
 OF RECORD FAC61G15-31.001.
  
 G. THE SHOP DRAWINGS PREPARED BY ENGINEERING EXPRESS ,
 SHEET 1, STATES THAT THIS IS EXPOSURE C, BUT APPEARS TO
 USE EXPOSURE B PRESSURES. PLEASE CLARIFY OR REVISE
 FBC1609. THE ENGINEER OF RECORD FOR THE STRUCTURE HAS
 DECLARED EXPOSURE B.
  
 2. USE OF REMOVABLE IMPACT PROTECTION ON COMMERCIAL
 BUILDINGS IS TO BE APPROVED BY THE BUILDING OFFICIAL.
 SUBMIT A PRESTORM PREPARATION PLAN, SEE ITEM 13,
 ATTACHED. THIS MAY BE SUBMITTED VIA EMAIL FOR
 PRELIMINARY APPROVAL. YOU ARE ENCOURAGED TO HAVE THE
 PRESTORM PREPATION PLAN APPROVED PRIOR TO RESUBMITTAL
 OF THE SHUTTER PERMIT.
  
 SEE EMAIL CORRESPONDENCE, 10/2/8 TO 10/8/8. THE
 PRE-STORM PREPARATION PLAN SUBMITTED IS THE SAME PLAN
 SUBMITTED AND DENIED IN THE EMAIL OF 10/2/8. CONTRACTOR
 WAS ADVISED: " PLEASE REVISE THE PLAN TO INCLUDE THE
 NAMES, TITLES, AND ENTITIES AS WELL AS THE OTHER
 INFORMATION REQUESTED. I KNOW THAT PRESENTING THE PLAN
 "AS IS" WOULD RESULT IN IT BEING DENIED. IF YOU INSIST,
 I WILL SUBMIT IT TO ROBERT BROWN AS SUBMITTED WITHOUT
 THE INFORMATION I REQUESTED BUT THIS WILL ONLY CAUSE
 FURTHER DELAYS AS, FROM EXPERIENCE, I KNOW WHAT
 INFORMATION HE REQUIRES ON THE PRESTORM PREPARATION
 PLAN TO CONSIDER USE OF REMOVABLE STORM PANELS." AS THE
 CONTRACTOR HAS SUBMITTED THE PRE-STORM PREPARATION PLAN
 WITHOUT THE REQUESTED REVISIONS, LUIS MARTINEZ (CHIEF
 PLANS EXAMINER) HAD THE PLAN REVIEWED BY ROBERT BROWN,
 INTERIM BUILDING OFFICIAL. HE CONFIRMED THE REQUIREMENT
 FOR THE REQUESTED INFORMATION IN ORDER TO DETERMINE
 WHETHER OR NOT REMOVABLE PANELS WILL BE PERMITTED FOR
 THIS BUILDING.
  
 PLEASE REVISE THE PRE-STORM PREPARATION PLAN AS
 REQUESTED IN THE EMAIL OF 10/8/8. TO SUMMARIZE:
  
 A. THE PLAN IS TO BE SIGNED BY THE OWNER. ONLY THE
 CONTRACTOR AND DEVELOPER ARE INCLUDED IN THE PRE-STORM
 PREPARATION PLAN SIGNATURE LINES. THIS IS AN AGREEMENT
 MADE BY THE OWNER OF THE BUILDING REGARDLESS OF TENANT
 RESPONSIBILITIES. IN THE INTEREST OF PUBLIC SAFETY, THE
 OWNER MUST DEMONSTRATE THAT HE OR SHE HAS THE ABILITY
 TO ENSURE THAT THE STORM PANELS ARE INSTALLED IN THE
 TIME FRAME REQUIRED.
  
 B. PLEASE PROVIDE MORE INFORMATION REGARDING J. RAYMOND
 CONSTRUCTION SUCH AS WHERE THEY ARE LOCATED, NUMBER OF
 EMPLOYEES, NUMBER OF JOBS THEY ARE RESPONSIBLE FOR.
 NOTE THAT THIS COMPANY IS LOCATED OUTSIDE OF PALM BEACH
 COUNTY. THE IMPLEMENTATION STANDARD REQUIRES THAT THE
 PARTY RESPONSIBLE FOR SHUTTER INSTALLATION IS TO BE
 LOCATED IN PALM BEACH COUNTY. PROVIDE THE INFORMATION
 REQUESTED AND ADDRESS THE LOCATION ISSUE.
  
 C. THE PLAN STATES THAT THE DOOR WILL BE PROTECTED (BY
 STORM PANELS); THE EGRESS PATH CANNOT BE OBSTRUCTED BY
 ELEMENTS OTHER THAN THOSE PERMITTED IN FBC CHAPTER 10.
 PLEASE REVISE TO BE IN COMPLIANCE WITH FBC CHAPTER 10.
  
 D. THE PLAN STATES THAT THE SHUTTERS WILL BE LOCATED IN
 THE NORTH WEST CORNER OF THE BUILDING SLAB. THE FLOOR
 PLAN SHOWS THAT THE AREA OF SHUTTER STORAGE IS THE
 LOCATION OF THE FUTURE ACCESSIBLE BATHROOMS. HOW WILL
 THEY BE SECURED TO PREVENT THEFT? WILL THE PANELS BE
 STORED HORIZONTALLY OR VERTICALLY? IT IS NOT CLEAR WHAT
 WILL HAPPEN TO THE SHUTTERS WHEN THE BATHROOM IS
 INSTALLED; THIS APPEARS TO BE A TEMPORARY STORAGE
 SOLUTION. HOW THESE SHUTTERS WILL BE SECURED,
 ESPECIALLY DURING THE TENANT BUILDOUT, WAS NOT
 ADDRESSED.
  
 3. PROVIDE A FLOOR PLAN SHOWING PROPOSED SHUTTER
 LOCATIONS. (COMMENT FROM PREVIOUS REVIEW.)
  
 THIS ITEM WAS ADDRESSED, BUT THE FRONT DOOR CANNOT BE
 BLOCKED BY STORM PANELS FBC1003.6. REVISE.
  
 4. COMPLETE THE ATTACHED INSTALLATION SCHEDULE OR
 PROVIDE ALL INFORMATION TO SHOW CODE COMPLIANCE IN
 ANOTHER FORMAT, FBC*106. TWO SETS REQUIRED.
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/PDF/SCHEDULE_FOR_
 INSTALLATION.PDF
  
 A. THE INSTALLATION SCHEDULE WAS NOT COMPLETE. IT WAS
 SUBMITTED, BUT COLUMNS 3, 4, 5, 6, 8, 10, 12 ARE BLANK.
  
 B. THE PRODUCT APPROVAL IS DIFFICULT TO READ. IT
 APPEARS TO BE A PHOTOCOPY OF A FAX. PLEASE PROVIDE
 LEGIBLE COPIES; TWO SETS PRINTED DIRECTLY FROM THE
 WEBSITE WWW.FLORIDABUILDING.ORG MAY BE LEGIBLE.
  
 C. THE ANCHOR TYPE IS TO CORRELATE WITH THE ANCHORS ON
 THE PRODUCT APPROVAL, SEE SHEET 6 OF 9. I DID NOT SEE A
 "DROP IN ANCHOR SIDEWALK BOLT" AS A CHOICE, BUT IT'S
 POSSIBLE THAT IT IS THERE, BUT I CAN'T READ IT. BEFORE
 RESUBMITTING, PLEASE BE SURE THAT THE ANCHOR TYPE IS
 CLEARLY SPECIFIED AND CORRELATES WITH INFORMATION IN
 THE PRODUCT APPROVAL.
  
 D. A COMPLETE LIST CANNOT BE DONE AT THIS TIME DUE TO
 INSUFFICIENT INFORMATION.
  
 5. MEANS OF EGRESS CANNOT BE BLOCKED BY A HURRICANE
 STORM PANEL, FBC1003.6, MEANS OF EGRESS CONTINUITY.
  
 THIS ITEM WAS NOT ADDRESSED.
  
 6. THE BUILDING PERMIT WAS FOR A SHELL BUILDING.
 REMOVABLE PANELS, IF APPROVED, ARE TO BE STORED ON
 SITE. IN THE PRE STORM PREPARATION PLAN, INCLUDE
 INFORMATION REGARDING STORAGE OF SHUTTERS.
  
 SEE OTHER COMMENTS. THIS ITEM WAS NOT ADDRESSED;
 INFORMATION REQUESTED WAS NOT PROVIDED. PLEASE REVISE
 THE PLAN TO INCLUDE ALL REQUESTED INFORMATION. WHEN THE
 PLAN IS COMPLETE AND HAS ALL INFORMATION REQUIRED, IT
 WILL THEN BE FORWARDED TO THE BUILDING OFFICIAL FOR
 REVIEW.
  
 ***THE PRE-STORM PREPARATION PLAN (ONLY) CAN BE
 SUBMITTED BY EMAIL FOR PRELIMINARY REVIEW***
  
 A C.O. HOLD HAS BEEN PLACED ON THIS PERMIT PENDING
 RESOLUTION OF THIS ISSUE.
  
 AS DISCUSSED, THIS CAN BE SUBMITTED PRIOR TO
 RESUBMITTAL OF THE REVISION/PLANS. THE CONTRACTOR IS
 ENCOURAGED TO GET THIS APPROVED BEFORE RESUBMITTAL TO
 AVOID ADDITIONAL DELAYS. IN THIS CASE, THE CONTRACTOR
 WAS ADVISED OF MANY OF THESE REQUIREMENTS VIA EMAIL BUT
 ELECTED TO DISREGARD THEM. THE NEED FOR ALL INFORMATION
 REQUESTED HAS BEEN CONFIRMED BY THE BUILDING OFFICIAL.
 AS DISCUSSED, TO AVOID FURTHER DELAYS, THE CONTRACTOR
 IS ENCOURAGED TO SUBMIT THE PRE-STORM PREPARATION PLAN
 BY EMAIL AND TO GET THIS ISSUE RESOLVED PRIOR TO
 RESUBMITTAL OF THE REVISION. PLEASE NOTE THAT MY REVIEW
 IS PRELIMINARY; THE BUILDING OFFICIAL MIGHT REQUIRE
 ADDITIONAL INFORMATION.
  
  
  
 ****END OF PLAN REVIEW COMMENTS*****
  
 *******************************************************
 **
 *******************************************************
 **
 *******************************************************
 **
  
 ****FOR REFERENCE ONLY, EMAILS BETWEEN SAMANTHA HILL
 (BUILDING PLANS EXAMINER) AND ADAM SPIEWAK (CONTRACTOR)
  
 EMAIL CORRESPONDENCE, PRE-STORM PREPARATION PLAN:
  
  
 EMAIL #3 OF 3
 (EMAIL SENT ON 10/8/8)
  
 THE PRESTORM PREPARATION PLAN SHOULD BE REVISED TO
 INCLUDE THE REQUESTED INFORMATION. THE INFORMATION
 SHOULD BE CONSOLIDATED INTO ONE DOCUMENT, WHICH IS AN
 AGREEMENT SIGNED BY THE OWNER. THE CONTRACT WITH THE
 ENTITY WHO WILL BE RESPONSIBLE FOR INSTALLATION OF THE
 SHUTTERS SHOULD BE AN ATTACHMENT TO THE PRESTORM
 PREPARATION PLAN. THE REQUESTED INFORMATION REGARDING
 THE COMPANY COULD BE INCLUDED IN EITHER THE PLAN OR THE
 CONTRACT, BUT THIS INFORMATION IS REQUIRED AS THE
 POLICY, ITEM 13, STATES PARAMETERS FOR THE INDIVIDUALS
 DOING THE INSTALLATION.
  
 CHAPTER 10 DOES NOT PERMIT USE OF REMOVABLE STORM
 PANELS TO PROVIDE IMPACT PROTECTION FOR A REQUIRED EXIT
 DOOR. THERE IS A PROVISION FOR EMERGENCY IMPACT
 PROTECTION FOR RESIDENTIAL OCCUPANIES WITH PROVISIONS
 FOR ALTERNATE MEANS OF EGRESS, BUT NOT FOR OTHER
 OCCUPANCIES. YOU CANNOT BLOCK THE MAIN EXIT IN A
 COMMERCIAL BUILDING WITH STORM PANELS, FBC1003.6.
  
 THE PRESTORM PREPARATION PLAN SHOULD INCLUDE THE
 SIGNATURE LINE OF THE INDIVIDUALS WHO ARE GOING TO SIGN
 THE PLAN. IT DID NOT APPEARS THAT THE OWNER WAS ONE OF
 THE INDIVIDUALS. PLEASE REVISE THE PLAN TO INCLUDE THE
 NAMES, TITLES, AND ENTITIES AS WELL AS THE OTHER
 INFORMATION REQUESTED. I KNOW THAT PRESENTING THE PLAN
 "AS IS" WOULD RESULT IN IT BEING DENIED. IF YOU INSIST,
 I WILL SUBMIT IT TO ROBERT BROWN AS SUBMITTED WITHOUT
 THE INFORMATION I REQUESTED BUT THIS WILL ONLY CAUSE
 FURTHER DELAYS AS, FROM EXPERIENCE, I KNOW WHAT
 INFORMATION HE REQUIRES ON THE PRESTORM PREPARATION
 PLAN TO CONSIDER USE OF REMOVABLE STORM PANELS. I DO A
 PRELIMINARY REVIEW OF THE PLAN FOR COMPLETENESS OF
 INFORMATION; THE BUILDING OFFICIAL MAKES THE DECISION
 AS TO WHETHER OR NOT REMOVABLE PANELS WILL BE PERMITTED
 ON A CASE BY CASE BASIS. PLEASE KEEP IN MIND THAT THIS
 PERMIT WAS ISSUED WITH IMPACT GLAZING. ANY CHANGE OF
 PRODUCTS SHOULD HAVE BEEN SUBMITTED AS A REVISION PRIOR
 TO INSTALLATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU NEED FURTHER
 ASSISTANCE.
  
 SAMANTHA M. HILL
 BUILDING PLANS EXAMINER
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
  
 * * * * * * * * * * * * * * * * * * * * * * * * * * * *
  
 EMAIL #2 OF 3
  
 "ADAM SPIEWAK"
 10/07/2008 03:57 PM
 TO
 
 CC
 "'GARY WILLIAMS'" , "'RANDY
 DEGLER'"
 SUBJECT
 RE: BAYWINDS RETAIL - PRE-STORM PREPARATION PLAN
  
  
  
  
  
 MRS. HILL,
  
 PLEASE KEEP IN MIND THAT FOR ALL INTENSIVE PURPOSES,
 THIS BUILDING WILL
 REMAIN UNOCCUPIED. THE SHUTTER PERMIT IS ATTACHED TO
 THE MASTER PERMIT
 07100650, WHICH IS A PERMIT FOR THE SHELL CONSTRUCTION
 ONLY. THE INTERIOR
 PERMIT APPLICATION IS CURRENTLY BEING REVIEWED BY THE
 BUILDING DEPARTMENT.
 THE PRE-STORM PREPARATION PLAN THAT HAS BEEN SUBMITTED
 FOR YOUR REVIEW IS
 ONLY TEMPORARY UNTIL SUCH TIME AS THE INTERIOR
 CONSTRUCTION IS COMPLETE
 AND THE TENANT TAKES RESIDENCY. AT WHICH TIME, A NEW
 PERMANENT PRE-STORM
 PREPARATION PLAN SHALL BE DEVISED AND SUBMITTED FOR
 APPROVAL. IN ORDER TO
 OBTAIN A CERTIFICATE OF COMPLETION FOR THE SHELL PERMIT
 ONLY, THE SHUTTER
 PERMIT WILL NEED TO BE APPROVED, INSPECTED AND CLOSED,
 BEFORE A BUILDING
 FINAL INSPECTION CAN TAKE PLACE.
  
 WITH THAT IN MIND, PLEASE FIND THE ANSWERS TO YOUR
 INQUIRES LISTED BELOW:
  
 1) J. RAYMOND CONSTRUCTION IS A COMMERCIAL GENERAL
 CONTRACTOR WITH A MAIN
 OFFICE LOCATED IN LONGWOOD FLORIDA. WE ARE RESPONSIBLE
 FOR THE
 CONSTRUCTION OF MANY PROJECTS LOCATED IN VARIOUS
 MUNICIPALITIES THROUGHOUT
 THE STATE. WE DO HOWEVER, HAVE A STRONG PRESENCE IN THE
 TRI-COUNTY AREA,
 AS WELL AS MANY EMPLOYEES WHO LIVE HERE.
  
 2) THE FRONT DOOR SHALL BE PROTECTED AS REQUIRED BY
 CHAPTER 10 IN THE FBC.
 THE EMERGENCY MEANS OF EGRESS THROUGH THE REAR STEEL
 EXIT DOORS (EQUIPPED
 WITH A PANIC DEVICE) WILL NOT BE OBSTRUCTED.
  
 3) THE PANELS WILL BE STORED HORIZONTALLY ON THE EMPTY
 SHELL SLAB IN THE
 NW CORNER OF THE BUILDING. A FLOOR PLAN WITH THIS
 INFORMATION WILL BE
 ATTACHED TO THE FINAL SUBMISSION PACKAGE. THE PANELS
 WILL BE PROTECTED
 FROM THEFT BY KEEPING ALL DOORS LOCKED DURING NON
 CONSTRUCTION HOURS. AT
 WHICH TIME THE INTERIOR CONSTRUCTION IS COMPLETE, THE
 PANELS WILL BE MOVED
 TO A MORE SECURE STORAGE CLOSET.
  
 4) AT THE TIME OF THE OFFICIAL SUBMITTAL OF THE
 PRE-STORM PREPARATION
 PLAN, ALL REQUIRED SIGNATURES WILL BE OBTAINED.
  
  
 - SHOULD YOU HAVE ANY QUESTION, PLEASE DO NOT HESITATE
 TO CONTACT ME.
  
 THANK YOU,
  
 ADAM SPIEWAK
 ASSISTANT SUPERINTENDANT
 P: (954) 464-6112 - F: (407) 712-6859
 J. RAYMOND
 CONSTRUCTION
 WWW.JRAY.COM
  
  
 EMAIL #1 OF 3
  
 -----ORIGINAL MESSAGE-----
 FROM: [email protected] [MAILTO:[email protected]]
 SENT: TUESDAY, OCTOBER 07, 2008 10:51 AM
 TO: ADAM SPIEWAK
 SUBJECT: RE: BAYWINDS RETAIL - PRE-STORM PREPARATION
 PLAN
  
 PLEASE PROVIDE MORE INFORMATION REGARDING J. RAYMOND
 CONSTRUCTION SUCH AS
 WHERE THEY ARE LOCATED, NUMBER OF EMPLOYEES, NUMBER OF
 JOBS THEY ARE
 RESPONSIBLE FOR.
  
 THE PLAN STATES THAT THE DOOR WILL BE PROTECTED; THE
 EGRESS PATH CANNOT BE
 OBSTRUCTED BY ELEMENTS OTHER THAN THOSE PERMITTED IN
 FBC CHAPTER 10.
  
 THE PLAN STATES THAT THE SHUTTERS WILL BE LOCATED IN
 THE NORTH WEST CORNER
 OF THE BUILDING SLAB. IT IS NOT CLEAR WHAT THAT MEANS.
 HOW WILL THEY BE
 SECURED TO PREVENT THEFT? WILL THE PANELS BE STORED
 HORIZONTALLY OR
 VERTICALLY?
  
 THE PLAN IS TO BE SIGNED BY THE OWNER. THE OWNER ON
 RECORD IS UG
 OKEECHOBEE LP.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU NEED FURTHER
 ASSISTANCE.
  
 SAMANTHA M. HILL
 BUILDING PLANS EXAMINER
 561-805-6724
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
  
  
  
  
  
  
  
  
 "ADAM SPIEWAK"
  
 
  
 M> TO
  
 
  
 10/02/2008 09:32 CC
  
 AM "'GARY WILLIAMS'"
  
 
  
 SUBJECT
  
 BAYWINDS RETAIL - PRE-STORM
  
 PREPARATION PLAN
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
 MRS. HILL,
  
 PLEASE SEE THE ATTACHED PRE-STORM PREPARATION PLAN
 SUBMITTED FOR YOUR
 REVIEW.
  
 THANK YOU FOR YOUR TIME AND ATTENTION THROUGHOUT THIS
 PROCESS.
  
  
 ADAM SPIEWAK
  
  
 P: (954) 464-6112
  
  
 F: (407) 712-6859
  
  
  
  
 J. RAYMOND
  
 CONSTRUCTION
  
 WWW.JRAY.COM
  
  
  
  
  
 (SEE ATTACHED FILE: PRE-STORM PREPARATION PLAN -
 2008-10-02.PDF)
  
  