| Date |
Text |
| 2008-10-22 13:57:44 | ****CORRECTIONS**** |
| | ****REVISION, FROM IMPACT GLASS TO NON IMPACT GLAZING, |
| | STORM PANELS, AND PRE-STORM PREPARATION PLAN*** |
| | ****SHUTTER PERMIT APPLIED UNDER 08090146, NOW |
| | INCORPORATED INTO BUILDING PERMIT PER LUIS MARTINEZ**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBC FLORIDA BUILDING CODE 2004 |
| | FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING |
| | CODE |
| | FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL |
| | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 |
| | FAC FLORIDA ADMINISTRATIVE CODE |
| | FS FLORIDA STATUTE |
| | |
| | COMMENTS FROM FIRST REVIEW, SHUTTER PERMIT 08090146 |
| | |
| | 1. IMPACT RATED PRODUCT APPROVALS WERE SUBMITTED FOR |
| | THE BUILDING, 07100650. IF YOU PROPOSE TO USE NON RATED |
| | PRODUCTS, HAVE THE PROPOSED PRODUCTS REVIEWED BY THE |
| | ARCHITECT FBC*106.3.3 AND SUBMIT AS A REVISION TO |
| | 07100650. |
| | |
| | A. SHEET A1, REVISE NOTE REGARDING USE OF STORM PANELS. |
| | THE FRONT DOOR, A REQUIRED EXIT, CANNOT BE OBSTRUCTED |
| | BY REMOVABLE PANELS FBC1003.6. |
| | |
| | B. THE PRODUCT APPROVALS ARE TO BE REVIEWED BY DESIGNER |
| | OF RECORD FBC*106.3.3. THIS CAN BE DONE BY EITHER A |
| | LETTER, SHOP DRAWING REVIEW STAMP, SPECIFYING THE |
| | PRODUCTS IN THE SIGNED AND SEALED PLAN, OR ANY OTHER |
| | METHOD WHICH SHOWS COMPLIANCE WITH FBC*106.3.3. |
| | |
| | C. NOA 06-0818.02, ARCH ALUMINUM NON-IMPACT OUTSWING |
| | DOOR WAS SUBMITTED. SEE OTHER COMMENTS REGARDING |
| | FBC1003.6, MEANS OF EGRESS CONTINUITY. |
| | |
| | D. NOA 06-0818.02, SEE SHEET 1 OF 9; THIS PRODUCT IS |
| | NOT TO BE USED WHERE WATER INFILTRATION IS NOT |
| | ACCEPTABLE. AS THE OVERHANG IS 2', THE ANGLE (BOTTOM OF |
| | DOOR TO EDGE OF OVERHANG) APPEARS TO BE LESS THAN THE |
| | 45 DEGREES REQUIRED. PLEASE ADDRESS. |
| | |
| | E. NOA 05-0902.01, ARCH ALUMINUM SERIES 4500 STOREFRONT |
| | NON-IMPACT, APPEARS TO BE CODE COMPLIANT (DESIGN |
| | PRESSURES). PLEASE ADDRESS THE OTHER COMMENTS REGARDING |
| | REVIEW BY DESIGNER OF RECORD AND IMPACT PROTECTION. |
| | |
| | F. THE SHOP DRAWINGS PREPARED BY ENGINEERING EXPRESS IS |
| | DELEGATED ENGINEERING; PLEASE HAVE REVIEWED BY DESIGNER |
| | OF RECORD FAC61G15-31.001. |
| | |
| | G. THE SHOP DRAWINGS PREPARED BY ENGINEERING EXPRESS , |
| | SHEET 1, STATES THAT THIS IS EXPOSURE C, BUT APPEARS TO |
| | USE EXPOSURE B PRESSURES. PLEASE CLARIFY OR REVISE |
| | FBC1609. THE ENGINEER OF RECORD FOR THE STRUCTURE HAS |
| | DECLARED EXPOSURE B. |
| | |
| | 2. USE OF REMOVABLE IMPACT PROTECTION ON COMMERCIAL |
| | BUILDINGS IS TO BE APPROVED BY THE BUILDING OFFICIAL. |
| | SUBMIT A PRESTORM PREPARATION PLAN, SEE ITEM 13, |
| | ATTACHED. THIS MAY BE SUBMITTED VIA EMAIL FOR |
| | PRELIMINARY APPROVAL. YOU ARE ENCOURAGED TO HAVE THE |
| | PRESTORM PREPATION PLAN APPROVED PRIOR TO RESUBMITTAL |
| | OF THE SHUTTER PERMIT. |
| | |
| | SEE EMAIL CORRESPONDENCE, 10/2/8 TO 10/8/8. THE |
| | PRE-STORM PREPARATION PLAN SUBMITTED IS THE SAME PLAN |
| | SUBMITTED AND DENIED IN THE EMAIL OF 10/2/8. CONTRACTOR |
| | WAS ADVISED: " PLEASE REVISE THE PLAN TO INCLUDE THE |
| | NAMES, TITLES, AND ENTITIES AS WELL AS THE OTHER |
| | INFORMATION REQUESTED. I KNOW THAT PRESENTING THE PLAN |
| | "AS IS" WOULD RESULT IN IT BEING DENIED. IF YOU INSIST, |
| | I WILL SUBMIT IT TO ROBERT BROWN AS SUBMITTED WITHOUT |
| | THE INFORMATION I REQUESTED BUT THIS WILL ONLY CAUSE |
| | FURTHER DELAYS AS, FROM EXPERIENCE, I KNOW WHAT |
| | INFORMATION HE REQUIRES ON THE PRESTORM PREPARATION |
| | PLAN TO CONSIDER USE OF REMOVABLE STORM PANELS." AS THE |
| | CONTRACTOR HAS SUBMITTED THE PRE-STORM PREPARATION PLAN |
| | WITHOUT THE REQUESTED REVISIONS, LUIS MARTINEZ (CHIEF |
| | PLANS EXAMINER) HAD THE PLAN REVIEWED BY ROBERT BROWN, |
| | INTERIM BUILDING OFFICIAL. HE CONFIRMED THE REQUIREMENT |
| | FOR THE REQUESTED INFORMATION IN ORDER TO DETERMINE |
| | WHETHER OR NOT REMOVABLE PANELS WILL BE PERMITTED FOR |
| | THIS BUILDING. |
| | |
| | PLEASE REVISE THE PRE-STORM PREPARATION PLAN AS |
| | REQUESTED IN THE EMAIL OF 10/8/8. TO SUMMARIZE: |
| | |
| | A. THE PLAN IS TO BE SIGNED BY THE OWNER. ONLY THE |
| | CONTRACTOR AND DEVELOPER ARE INCLUDED IN THE PRE-STORM |
| | PREPARATION PLAN SIGNATURE LINES. THIS IS AN AGREEMENT |
| | MADE BY THE OWNER OF THE BUILDING REGARDLESS OF TENANT |
| | RESPONSIBILITIES. IN THE INTEREST OF PUBLIC SAFETY, THE |
| | OWNER MUST DEMONSTRATE THAT HE OR SHE HAS THE ABILITY |
| | TO ENSURE THAT THE STORM PANELS ARE INSTALLED IN THE |
| | TIME FRAME REQUIRED. |
| | |
| | B. PLEASE PROVIDE MORE INFORMATION REGARDING J. RAYMOND |
| | CONSTRUCTION SUCH AS WHERE THEY ARE LOCATED, NUMBER OF |
| | EMPLOYEES, NUMBER OF JOBS THEY ARE RESPONSIBLE FOR. |
| | NOTE THAT THIS COMPANY IS LOCATED OUTSIDE OF PALM BEACH |
| | COUNTY. THE IMPLEMENTATION STANDARD REQUIRES THAT THE |
| | PARTY RESPONSIBLE FOR SHUTTER INSTALLATION IS TO BE |
| | LOCATED IN PALM BEACH COUNTY. PROVIDE THE INFORMATION |
| | REQUESTED AND ADDRESS THE LOCATION ISSUE. |
| | |
| | C. THE PLAN STATES THAT THE DOOR WILL BE PROTECTED (BY |
| | STORM PANELS); THE EGRESS PATH CANNOT BE OBSTRUCTED BY |
| | ELEMENTS OTHER THAN THOSE PERMITTED IN FBC CHAPTER 10. |
| | PLEASE REVISE TO BE IN COMPLIANCE WITH FBC CHAPTER 10. |
| | |
| | D. THE PLAN STATES THAT THE SHUTTERS WILL BE LOCATED IN |
| | THE NORTH WEST CORNER OF THE BUILDING SLAB. THE FLOOR |
| | PLAN SHOWS THAT THE AREA OF SHUTTER STORAGE IS THE |
| | LOCATION OF THE FUTURE ACCESSIBLE BATHROOMS. HOW WILL |
| | THEY BE SECURED TO PREVENT THEFT? WILL THE PANELS BE |
| | STORED HORIZONTALLY OR VERTICALLY? IT IS NOT CLEAR WHAT |
| | WILL HAPPEN TO THE SHUTTERS WHEN THE BATHROOM IS |
| | INSTALLED; THIS APPEARS TO BE A TEMPORARY STORAGE |
| | SOLUTION. HOW THESE SHUTTERS WILL BE SECURED, |
| | ESPECIALLY DURING THE TENANT BUILDOUT, WAS NOT |
| | ADDRESSED. |
| | |
| | 3. PROVIDE A FLOOR PLAN SHOWING PROPOSED SHUTTER |
| | LOCATIONS. (COMMENT FROM PREVIOUS REVIEW.) |
| | |
| | THIS ITEM WAS ADDRESSED, BUT THE FRONT DOOR CANNOT BE |
| | BLOCKED BY STORM PANELS FBC1003.6. REVISE. |
| | |
| | 4. COMPLETE THE ATTACHED INSTALLATION SCHEDULE OR |
| | PROVIDE ALL INFORMATION TO SHOW CODE COMPLIANCE IN |
| | ANOTHER FORMAT, FBC*106. TWO SETS REQUIRED. |
| | HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/PDF/SCHEDULE_FOR_ |
| | INSTALLATION.PDF |
| | |
| | A. THE INSTALLATION SCHEDULE WAS NOT COMPLETE. IT WAS |
| | SUBMITTED, BUT COLUMNS 3, 4, 5, 6, 8, 10, 12 ARE BLANK. |
| | |
| | B. THE PRODUCT APPROVAL IS DIFFICULT TO READ. IT |
| | APPEARS TO BE A PHOTOCOPY OF A FAX. PLEASE PROVIDE |
| | LEGIBLE COPIES; TWO SETS PRINTED DIRECTLY FROM THE |
| | WEBSITE WWW.FLORIDABUILDING.ORG MAY BE LEGIBLE. |
| | |
| | C. THE ANCHOR TYPE IS TO CORRELATE WITH THE ANCHORS ON |
| | THE PRODUCT APPROVAL, SEE SHEET 6 OF 9. I DID NOT SEE A |
| | "DROP IN ANCHOR SIDEWALK BOLT" AS A CHOICE, BUT IT'S |
| | POSSIBLE THAT IT IS THERE, BUT I CAN'T READ IT. BEFORE |
| | RESUBMITTING, PLEASE BE SURE THAT THE ANCHOR TYPE IS |
| | CLEARLY SPECIFIED AND CORRELATES WITH INFORMATION IN |
| | THE PRODUCT APPROVAL. |
| | |
| | D. A COMPLETE LIST CANNOT BE DONE AT THIS TIME DUE TO |
| | INSUFFICIENT INFORMATION. |
| | |
| | 5. MEANS OF EGRESS CANNOT BE BLOCKED BY A HURRICANE |
| | STORM PANEL, FBC1003.6, MEANS OF EGRESS CONTINUITY. |
| | |
| | THIS ITEM WAS NOT ADDRESSED. |
| | |
| | 6. THE BUILDING PERMIT WAS FOR A SHELL BUILDING. |
| | REMOVABLE PANELS, IF APPROVED, ARE TO BE STORED ON |
| | SITE. IN THE PRE STORM PREPARATION PLAN, INCLUDE |
| | INFORMATION REGARDING STORAGE OF SHUTTERS. |
| | |
| | SEE OTHER COMMENTS. THIS ITEM WAS NOT ADDRESSED; |
| | INFORMATION REQUESTED WAS NOT PROVIDED. PLEASE REVISE |
| | THE PLAN TO INCLUDE ALL REQUESTED INFORMATION. WHEN THE |
| | PLAN IS COMPLETE AND HAS ALL INFORMATION REQUIRED, IT |
| | WILL THEN BE FORWARDED TO THE BUILDING OFFICIAL FOR |
| | REVIEW. |
| | |
| | ***THE PRE-STORM PREPARATION PLAN (ONLY) CAN BE |
| | SUBMITTED BY EMAIL FOR PRELIMINARY REVIEW*** |
| | |
| | A C.O. HOLD HAS BEEN PLACED ON THIS PERMIT PENDING |
| | RESOLUTION OF THIS ISSUE. |
| | |
| | AS DISCUSSED, THIS CAN BE SUBMITTED PRIOR TO |
| | RESUBMITTAL OF THE REVISION/PLANS. THE CONTRACTOR IS |
| | ENCOURAGED TO GET THIS APPROVED BEFORE RESUBMITTAL TO |
| | AVOID ADDITIONAL DELAYS. IN THIS CASE, THE CONTRACTOR |
| | WAS ADVISED OF MANY OF THESE REQUIREMENTS VIA EMAIL BUT |
| | ELECTED TO DISREGARD THEM. THE NEED FOR ALL INFORMATION |
| | REQUESTED HAS BEEN CONFIRMED BY THE BUILDING OFFICIAL. |
| | AS DISCUSSED, TO AVOID FURTHER DELAYS, THE CONTRACTOR |
| | IS ENCOURAGED TO SUBMIT THE PRE-STORM PREPARATION PLAN |
| | BY EMAIL AND TO GET THIS ISSUE RESOLVED PRIOR TO |
| | RESUBMITTAL OF THE REVISION. PLEASE NOTE THAT MY REVIEW |
| | IS PRELIMINARY; THE BUILDING OFFICIAL MIGHT REQUIRE |
| | ADDITIONAL INFORMATION. |
| | |
| | |
| | |
| | ****END OF PLAN REVIEW COMMENTS***** |
| | |
| | ******************************************************* |
| | ** |
| | ******************************************************* |
| | ** |
| | ******************************************************* |
| | ** |
| | |
| | ****FOR REFERENCE ONLY, EMAILS BETWEEN SAMANTHA HILL |
| | (BUILDING PLANS EXAMINER) AND ADAM SPIEWAK (CONTRACTOR) |
| | |
| | EMAIL CORRESPONDENCE, PRE-STORM PREPARATION PLAN: |
| | |
| | |
| | EMAIL #3 OF 3 |
| | (EMAIL SENT ON 10/8/8) |
| | |
| | THE PRESTORM PREPARATION PLAN SHOULD BE REVISED TO |
| | INCLUDE THE REQUESTED INFORMATION. THE INFORMATION |
| | SHOULD BE CONSOLIDATED INTO ONE DOCUMENT, WHICH IS AN |
| | AGREEMENT SIGNED BY THE OWNER. THE CONTRACT WITH THE |
| | ENTITY WHO WILL BE RESPONSIBLE FOR INSTALLATION OF THE |
| | SHUTTERS SHOULD BE AN ATTACHMENT TO THE PRESTORM |
| | PREPARATION PLAN. THE REQUESTED INFORMATION REGARDING |
| | THE COMPANY COULD BE INCLUDED IN EITHER THE PLAN OR THE |
| | CONTRACT, BUT THIS INFORMATION IS REQUIRED AS THE |
| | POLICY, ITEM 13, STATES PARAMETERS FOR THE INDIVIDUALS |
| | DOING THE INSTALLATION. |
| | |
| | CHAPTER 10 DOES NOT PERMIT USE OF REMOVABLE STORM |
| | PANELS TO PROVIDE IMPACT PROTECTION FOR A REQUIRED EXIT |
| | DOOR. THERE IS A PROVISION FOR EMERGENCY IMPACT |
| | PROTECTION FOR RESIDENTIAL OCCUPANIES WITH PROVISIONS |
| | FOR ALTERNATE MEANS OF EGRESS, BUT NOT FOR OTHER |
| | OCCUPANCIES. YOU CANNOT BLOCK THE MAIN EXIT IN A |
| | COMMERCIAL BUILDING WITH STORM PANELS, FBC1003.6. |
| | |
| | THE PRESTORM PREPARATION PLAN SHOULD INCLUDE THE |
| | SIGNATURE LINE OF THE INDIVIDUALS WHO ARE GOING TO SIGN |
| | THE PLAN. IT DID NOT APPEARS THAT THE OWNER WAS ONE OF |
| | THE INDIVIDUALS. PLEASE REVISE THE PLAN TO INCLUDE THE |
| | NAMES, TITLES, AND ENTITIES AS WELL AS THE OTHER |
| | INFORMATION REQUESTED. I KNOW THAT PRESENTING THE PLAN |
| | "AS IS" WOULD RESULT IN IT BEING DENIED. IF YOU INSIST, |
| | I WILL SUBMIT IT TO ROBERT BROWN AS SUBMITTED WITHOUT |
| | THE INFORMATION I REQUESTED BUT THIS WILL ONLY CAUSE |
| | FURTHER DELAYS AS, FROM EXPERIENCE, I KNOW WHAT |
| | INFORMATION HE REQUIRES ON THE PRESTORM PREPARATION |
| | PLAN TO CONSIDER USE OF REMOVABLE STORM PANELS. I DO A |
| | PRELIMINARY REVIEW OF THE PLAN FOR COMPLETENESS OF |
| | INFORMATION; THE BUILDING OFFICIAL MAKES THE DECISION |
| | AS TO WHETHER OR NOT REMOVABLE PANELS WILL BE PERMITTED |
| | ON A CASE BY CASE BASIS. PLEASE KEEP IN MIND THAT THIS |
| | PERMIT WAS ISSUED WITH IMPACT GLAZING. ANY CHANGE OF |
| | PRODUCTS SHOULD HAVE BEEN SUBMITTED AS A REVISION PRIOR |
| | TO INSTALLATION. |
| | |
| | PLEASE FEEL FREE TO CONTACT ME IF YOU NEED FURTHER |
| | ASSISTANCE. |
| | |
| | SAMANTHA M. HILL |
| | BUILDING PLANS EXAMINER |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | |
| | * * * * * * * * * * * * * * * * * * * * * * * * * * * * |
| | |
| | EMAIL #2 OF 3 |
| | |
| | "ADAM SPIEWAK" |
| | 10/07/2008 03:57 PM |
| | TO |
| | |
| | CC |
| | "'GARY WILLIAMS'" , "'RANDY |
| | DEGLER'" |
| | SUBJECT |
| | RE: BAYWINDS RETAIL - PRE-STORM PREPARATION PLAN |
| | |
| | |
| | |
| | |
| | |
| | MRS. HILL, |
| | |
| | PLEASE KEEP IN MIND THAT FOR ALL INTENSIVE PURPOSES, |
| | THIS BUILDING WILL |
| | REMAIN UNOCCUPIED. THE SHUTTER PERMIT IS ATTACHED TO |
| | THE MASTER PERMIT |
| | 07100650, WHICH IS A PERMIT FOR THE SHELL CONSTRUCTION |
| | ONLY. THE INTERIOR |
| | PERMIT APPLICATION IS CURRENTLY BEING REVIEWED BY THE |
| | BUILDING DEPARTMENT. |
| | THE PRE-STORM PREPARATION PLAN THAT HAS BEEN SUBMITTED |
| | FOR YOUR REVIEW IS |
| | ONLY TEMPORARY UNTIL SUCH TIME AS THE INTERIOR |
| | CONSTRUCTION IS COMPLETE |
| | AND THE TENANT TAKES RESIDENCY. AT WHICH TIME, A NEW |
| | PERMANENT PRE-STORM |
| | PREPARATION PLAN SHALL BE DEVISED AND SUBMITTED FOR |
| | APPROVAL. IN ORDER TO |
| | OBTAIN A CERTIFICATE OF COMPLETION FOR THE SHELL PERMIT |
| | ONLY, THE SHUTTER |
| | PERMIT WILL NEED TO BE APPROVED, INSPECTED AND CLOSED, |
| | BEFORE A BUILDING |
| | FINAL INSPECTION CAN TAKE PLACE. |
| | |
| | WITH THAT IN MIND, PLEASE FIND THE ANSWERS TO YOUR |
| | INQUIRES LISTED BELOW: |
| | |
| | 1) J. RAYMOND CONSTRUCTION IS A COMMERCIAL GENERAL |
| | CONTRACTOR WITH A MAIN |
| | OFFICE LOCATED IN LONGWOOD FLORIDA. WE ARE RESPONSIBLE |
| | FOR THE |
| | CONSTRUCTION OF MANY PROJECTS LOCATED IN VARIOUS |
| | MUNICIPALITIES THROUGHOUT |
| | THE STATE. WE DO HOWEVER, HAVE A STRONG PRESENCE IN THE |
| | TRI-COUNTY AREA, |
| | AS WELL AS MANY EMPLOYEES WHO LIVE HERE. |
| | |
| | 2) THE FRONT DOOR SHALL BE PROTECTED AS REQUIRED BY |
| | CHAPTER 10 IN THE FBC. |
| | THE EMERGENCY MEANS OF EGRESS THROUGH THE REAR STEEL |
| | EXIT DOORS (EQUIPPED |
| | WITH A PANIC DEVICE) WILL NOT BE OBSTRUCTED. |
| | |
| | 3) THE PANELS WILL BE STORED HORIZONTALLY ON THE EMPTY |
| | SHELL SLAB IN THE |
| | NW CORNER OF THE BUILDING. A FLOOR PLAN WITH THIS |
| | INFORMATION WILL BE |
| | ATTACHED TO THE FINAL SUBMISSION PACKAGE. THE PANELS |
| | WILL BE PROTECTED |
| | FROM THEFT BY KEEPING ALL DOORS LOCKED DURING NON |
| | CONSTRUCTION HOURS. AT |
| | WHICH TIME THE INTERIOR CONSTRUCTION IS COMPLETE, THE |
| | PANELS WILL BE MOVED |
| | TO A MORE SECURE STORAGE CLOSET. |
| | |
| | 4) AT THE TIME OF THE OFFICIAL SUBMITTAL OF THE |
| | PRE-STORM PREPARATION |
| | PLAN, ALL REQUIRED SIGNATURES WILL BE OBTAINED. |
| | |
| | |
| | - SHOULD YOU HAVE ANY QUESTION, PLEASE DO NOT HESITATE |
| | TO CONTACT ME. |
| | |
| | THANK YOU, |
| | |
| | ADAM SPIEWAK |
| | ASSISTANT SUPERINTENDANT |
| | P: (954) 464-6112 - F: (407) 712-6859 |
| | J. RAYMOND |
| | CONSTRUCTION |
| | WWW.JRAY.COM |
| | |
| | |
| | EMAIL #1 OF 3 |
| | |
| | -----ORIGINAL MESSAGE----- |
| | FROM: [email protected] [MAILTO:[email protected]] |
| | SENT: TUESDAY, OCTOBER 07, 2008 10:51 AM |
| | TO: ADAM SPIEWAK |
| | SUBJECT: RE: BAYWINDS RETAIL - PRE-STORM PREPARATION |
| | PLAN |
| | |
| | PLEASE PROVIDE MORE INFORMATION REGARDING J. RAYMOND |
| | CONSTRUCTION SUCH AS |
| | WHERE THEY ARE LOCATED, NUMBER OF EMPLOYEES, NUMBER OF |
| | JOBS THEY ARE |
| | RESPONSIBLE FOR. |
| | |
| | THE PLAN STATES THAT THE DOOR WILL BE PROTECTED; THE |
| | EGRESS PATH CANNOT BE |
| | OBSTRUCTED BY ELEMENTS OTHER THAN THOSE PERMITTED IN |
| | FBC CHAPTER 10. |
| | |
| | THE PLAN STATES THAT THE SHUTTERS WILL BE LOCATED IN |
| | THE NORTH WEST CORNER |
| | OF THE BUILDING SLAB. IT IS NOT CLEAR WHAT THAT MEANS. |
| | HOW WILL THEY BE |
| | SECURED TO PREVENT THEFT? WILL THE PANELS BE STORED |
| | HORIZONTALLY OR |
| | VERTICALLY? |
| | |
| | THE PLAN IS TO BE SIGNED BY THE OWNER. THE OWNER ON |
| | RECORD IS UG |
| | OKEECHOBEE LP. |
| | |
| | PLEASE FEEL FREE TO CONTACT ME IF YOU NEED FURTHER |
| | ASSISTANCE. |
| | |
| | SAMANTHA M. HILL |
| | BUILDING PLANS EXAMINER |
| | 561-805-6724 |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | "ADAM SPIEWAK" |
| | |
| | |
| | |
| | M> TO |
| | |
| | |
| | |
| | 10/02/2008 09:32 CC |
| | |
| | AM "'GARY WILLIAMS'" |
| | |
| | |
| | |
| | SUBJECT |
| | |
| | BAYWINDS RETAIL - PRE-STORM |
| | |
| | PREPARATION PLAN |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | MRS. HILL, |
| | |
| | PLEASE SEE THE ATTACHED PRE-STORM PREPARATION PLAN |
| | SUBMITTED FOR YOUR |
| | REVIEW. |
| | |
| | THANK YOU FOR YOUR TIME AND ATTENTION THROUGHOUT THIS |
| | PROCESS. |
| | |
| | |
| | ADAM SPIEWAK |
| | |
| | |
| | P: (954) 464-6112 |
| | |
| | |
| | F: (407) 712-6859 |
| | |
| | |
| | |
| | |
| | J. RAYMOND |
| | |
| | CONSTRUCTION |
| | |
| | WWW.JRAY.COM |
| | |
| | |
| | |
| | |
| | |
| | (SEE ATTACHED FILE: PRE-STORM PREPARATION PLAN - |
| | 2008-10-02.PDF) |
| | |
| | |