| 2007-11-26 17:10:38 | REVIEW #: 1ST |
| | ACTION: DENIED |
| | |
| | FBC 2004 CODE FAMILY W/ 2005 AND 2006 SUPPLEMENTS FBC |
| | CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH |
| | |
| | 1. PROVIDE OUTSIDE AIR CALCULATIONS BASED ON OCCUPANCY |
| | CLASSIFICATION, OCCUPANT LOAD AND CFM REQUIRED AS |
| | STATED IN FBC,M TABLE 403.3 OR ASHRAE 62.1-2004. ALSO, |
| | PROVIDE MECHANICAL VENTILATION FOR THE TOILET ROOMS IN |
| | ACCORDANCE WITH THIS SECTION. |
| | |
| | 2. SHOW LOCATION OF EXHAUST DISCHARGE IN COMPLIANCE |
| | WITH FBC,M 401.5. |
| | |
| | 3. ENERGY CALCULATIONS: AS THIS IS A SHELL BUILDING, |
| | PROVIDE METHOD B OR C COMPLIANCE FORMS IN ACCORDANCE |
| | WITH FBC 13-101.1.6. ALL ASSUMPTIONS MADE ABOUT |
| | FEATURES NOT INSTALLED UNTIL LATER THAT ARE NOT ON THE |
| | BUILDING PLANS SHALL BE LISTED AND APPENDED TO THE |
| | COMPLIANCE FORM SUBMITTED TO THE BUILDING DEPARTMENT. |
| | ONCE ALL ENERGY-RELATED DESIGN PARAMETERS ARE KNOWN, A |
| | METHOD A CALCULATION MAY BE RESUBMITTED IN ACCORDANCE |
| | WITH FBC 13-400.2.A.2. |
| | |
| | 4. ENERGY CALCULATIONS: A COOLING LOAD CALCULATION |
| | SHALL BE ATTACHED TO THE CODE COMPLIANCE FORM SUBMITTED |
| | TO THE BUILDING DEPARTMENT WHEN THE BUILDING IS |
| | PERMITTED IN ACCORDANCE WITH FBC 13-407.1.ABC.1. HVAC |
| | SYSTEMS AND EQUIPMENT SHALL BE SIZED TO PROVIDE NO MORE |
| | THAN THE SPACE AND SYSTEM LOADS CALCULATED IN |
| | ACCORDANCE WITH SECTION 407.1.ABC.1. |
| | |
| | 5. PROVIDE SHUTOFF DAMPER CONTROLS IN ACCORDANCE WITH |
| | FBC 13-409.1.ABC.3.3. |
| | |
| | 6. ENGINEERING BUSINESS (C.O.A.) NUMBER IS MISSING FROM |
| | ENGINEERING FIRM'S TITLE BLOCK. SEE FAC RULE |
| | 61G15-23.002. |
| | |
| | 7. SHOW MEANS OF AUXILIARY DRAIN PROTECTION TO PREVENT |
| | THE OVERFLOW OF CONDENSATE INTO THE STRUCTURE IN |
| | ACCORDANCE WITH FBC,M 307.2.3(2). A WATER LEVEL |
| | DETECTION DEVICE, SUCH AS A FLOAT SWITCH, INSTALLED |
| | INTERNALLY ON THE PRIMARY DRAIN PAN OF THE RTU WOULD |
| | MEET THIS REQUIREMENT. |
| | |