| 2007-11-26 14:33:03 | ** DENIED ** |
| | |
| | ** PLEASE KNOW AS THERE IS INFORMATION NOT YET |
| | SUBMITTED FOR REVIEW. THERE MAY BE NEW COMMENTS ON THE |
| | FOLLOWING REVIEW WHICH MAY NOT BE MADE AT THIS TIME. |
| | |
| | 1) NOTE: PLEASE KNOW THE FOLLOWING CODES SHALL BE ON |
| | PLANS AS WELL AS ELECTRICAL SHEET E-1. |
| | FBC 2004 W/2007 REVISIONS |
| | NFPA-101 2003 |
| | NFPA-72 2002 (WHEN APPLICABLE) |
| | NFPA-70 2005 |
| | |
| | ** PLANS NOTE A 2000 NEC, HOWEVER AS NOTED ABOVE THE |
| | CODE IS 2005. PLEASE KNOW THERE WAS A 1999, AND THEN |
| | 2002 NFPA-70. |
| | |
| | 2) NOTE: PLEASE SEE THE TITLE BLOCKS FOR MEP DESIGN |
| | TEAM IS NOT COMPLETE WITH INFORMATION AS REQUIRED PER |
| | FLORIDA ADMINISTRATIVE CODE 61G15-23.002 AND FLORIDA |
| | STATUTES 471.023 |
| | ( MISSING CA #) |
| | |
| | 3) NOTE: PLEASE BE SURE RAISED SEALED IS CLEAR AND |
| | VISIBLE WITH ALL INFORMATION ON RAISED SEAL AS REQUIRED |
| | PER FAC 61G15-23.001. |
| | PLEASE SEE THE SEAL IS VERY FAINT NOT EASILY READ. |
| | |
| | 4) NOTE: PLEASE SEE FBC 13-101.1.6 AS THIS IS A SHELL |
| | BUILDING AND METHOD *A* ENERGY CALCULATIONS ARE BEING |
| | SUBMITTED WHICH IS NOT PERMITTED. |
| | PLEASE SUBMIT AND INDICATE ALL TO COMPLY WITH 13-415.2 |
| | |
| | 5) NOTE: PLEASE SEE 250.6, 250.24 AS AN *EQUIPMENT |
| | GROUNDING CONDUCTOR* IS NOT PERMITTED BEFORE THE FIRST |
| | MEANS OF DISCONNECT. |
| | RISER SHOWS THIS WHICH IS NOT PERMITTED. |
| | |
| | 6) NOTE: PLEASE SEE GROUNDING ELECTRODE NOTE WHICH |
| | MENTIONS TO *BUILDING STEEL*, IS THIS FOOTER STEEL? AS |
| | BUILDING STEEL IS ALSO REQUIRED (DEPENDING ON |
| | CONSTRUCTION) , PLEASE LIST FOOTER STEEL. |
| | 250.50 |
| | |
| | 7) NOTE: PLEASE KNOW AS PER THE FIRE MARSHAL CHIEF AND |
| | LIFE SAFETY CODE, PLEASE PROVIDE MINIMAL LIGHTING FOR |
| | EGRESS INTO SPACE. |
| | EM AND EXT LIGHTS ARE SHOWN; HOWEVER NO LIGHTING FOR |
| | NORMAL CONDITIONS IS SHOWN AND WILL BE REQUIRED. PLEASE |
| | SEE 700.12F FOR CIRCUITING OF EM AND EXT LTS. (LOCAL |
| | BRANCH CIRCUIT) (AS NOTED ON PLANS) |
| | |
| | |
| | PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |