Plan Review Notes
Plan Review Notes For Permit 07100650
Permit Number 07100650
Review Stop B
Sequence Number 1
Notes
Date Text
2007-11-09 10:46:04****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.)THIS IS AN AT RISK PERMIT (SHELL ONLY).
 INFORMATIONAL; NOT REQUIRED TO BE ADDRESSED.
  
 2.)DOCUMENTS PREPARED BY A LANDSCAPE ARCHITECT AND
 SUBMITTED FOR PUBLIC RECORD ARE TO BE SIGNED, SEALED,
 DATED ORIGINALS FS481.PLANS STATE THAT THIS IS
 ?INFORMATIONAL ONLY? AND ?PAD ONLY? BUT THIS SHEET IS
 USED TO DETERMINE CODE COMPLIANCE FOR ACCESSIBLE
 PARKING AND FBC CHAPTER 5; SEE OTHER COMMENTS.
  
 3.)STATE THE TOTAL NUMBER OF ACCESSIBLE PARKING AND
 TOTAL NUMBER OF PARKING SPACES FOR THIS PARCEL.NOTE
 THAT THE SITE PLAN STATES THAT THEREARE 176 TOTAL, 6
 ACCESSIBLE WOULD BE REQUIRED BUT ONLY FIVE SHOWN, BUT
 IT APPEARS THAT THIS TOTAL IS FOR FOUR PARCELS.PLEASE
 SHOW COMPLIANCE WITH FBC11-4.1.2(5)(A).
  
 4.)PROVIDE A COPY OF THE SURVEY FOR THIS PROPERTY.
  
 5.)PROVIDE A SOILS INVESTIGATION REPORT, FBC1802.2.
  
 6.)SEPARATE PERMITS WILL BE REQUIRED; INFORMATIONAL
 ONLY (SIGNS, ETC.).
  
 7.)THE ENERGY CALCS STATE THIS IS AN OFFICE, PLANS
 SHOW RETAIL.PLEASE CORRELATE.
  
 8.)ENERGY CALCS STATE 4005 SF, PLANS SHOW 4019,
 ARCHITECT DECLARES 4000.THE DIFFERENCE AFFECTS
 OCCUPANT LOAD; PLEASE CORRELATE.
  
 9.)SEE ZONING COMMENTS REGARDING PARKING STRIPING
 DETAIL.
  
 10.)THE SITE PLAN AND ARCHITECTURAL PLANS STATE THAT
 THIS IS A RETAIL SHELL BUILDING, BUT THE ARCHITECT
 DECLARES B OCCUPANCY ON AR1 AND OTHER SHEETS.SEE
 FBC304, FBC309 AND REVISE EITHER BUILDING DESCRIPTION
 OR OCCUPANCY CLASSIFICATION.
  
 11.)SEE FBC1004 AND COMMENT ABOVE REGARDING SF AREA
 AND REVISE OCCUPANT LOAD.SEE FBC TABLE 1004.1.2; 30
 SF PER PERSON REQUIRED FOR MERCANTILE (NOT 100SF AS FOR
 BUSINESS OCCUPANCY).ALSO WHEN REVISING, PLEASE ROUND
 UP AS FBC 1004 REQUIRES OCCUPANT LOAD TO BE NOT LESS
 THAN THE TABLE.
  
 12.)THE REAR DOOR WILL BE REQUIRED TO BE AN
 ACCESSIBLE EXIT FBC11-4.1.3(9).PLEASE SHOW ACCESSIBLE
 MEANS OF EGRESS, FBC11-3 (SHOW MAXIMUM SLOPE FROM DOOR
 TO PUBLIC WAY, WIDTH OF SIDEWALK BETWEEN REAR DOOR AND
 LOADING AREA AT NORTH SIDE).
  
 13.)AR1, PLEASE STATE BUILDING TYPE AS A OR B (RATHER
 THAN ?UNPROTECTED?, TERMINOLOGY FROM FBC2001).SEE FBC
 TABLE 601.
  
 14.) ON THE SITE PLAN, SHOW THE DISTANCE TO THE
 PROPERTY LINES, INCLUDING THE DISTANCE FROM THE
 BUILDING TO THE ASSUMED LOT LINE?.THIS APPEARS TO BE
 5?.SEE FBC TABLE 602 AND SHOW COMPLIANCE ON THE PLAN.
 ANY REQUIRED FIRE RATED WALLS ARE TO BE NOTED ON BOTH
 THE ARCHITECTURAL PLAN AND THE MECHANICAL PLAN.IF
 FIRE RATED WALLS ARE REQUIRED BY FBC TABLE 602 (OR
 OTHER CODE REQUIREMENTS) PLEASE PROVIDE A DETAIL;
 TESTED ASSEMBLY OR CALCULATED FIRE RESISTANCE FBC 7.
  
 15.)SEE FBC TABLE 704.8 REGARDING ALLOWABLE OPENINGS
 AND SHOW COMPLIANCE ON THE PLAN (EAST SIDE AND OTHER
 BUILDING ELEVATIONS LESS THAN 30?).NOTE THAT IF THE
 BUILDING IS 5? FROM THE ASSUMED LOT LINE AS SHOWN, ALL
 OPENINGS ARE TO BE PROTECTED.IF ANY OPENING
 PROTECTION IS REQUIRED, NOTE ON PLAN AND SUBMIT PRODUCT
 APPROVALS AND FIRE RATING INFORMATION.
  
 16.) PLEASE NOTE FLOOD ZONE INFORMATION ON THE PLAN
 AND, IF IN A SPECIAL FLOOD HAZARD AREA, MINIMUM FFE
 (REQUIRED TO BE 6? ABOVE BFE) IS REQUIRED TO BE SHOWN
 ON THE PLAN CITY OF WEST PALM BEACH MUNICIPAL CODE
 94-546(B)).
  
 17.)FOR THE FLAT ROOF, SELECT AN APPROVED ASSEMBLY.
  
 18.)FOR THE FLAT ROOF, SPECIFY ENHANCED FASTENING FOR
 CORNER AND PERIMETER ZONES.THIS MUST BE PREPARED BY
 AN ARCHITECT, ENGINEER, OR REGISTERED ROOF CONSULTANT
 AS PER GENERAL LIMITATION 7 ON THE NOA.
  
 19.)A5, PLANS STATE CLAY ROOF, CONCRETE ROOF TILE
 PRODUCT APPROVAL SUBMITTED.PLEASE CORRELATE.
  
 20.)ON THE ROOF TILE PRODUCT APPROVAL, MARK METHOD OF
 ATTACHMENT.IF YOU ARE USING A FOAM ADHESIVE, PLEASE
 PROVIDE PRODUCT APPROVALS, FAC9B72.
  
 21.)SHEATHING IS TO COMPLY WITH FBC TABLE 2304.7(3),
 1/180 PLF.STATE DESIGN CRITERIA ON THE PLAN, SHEET S2
 (DUE TO USE OF ?? PLYWOOD WITH A TILE ROOF).
  
 22.)ROOF DRAINAGE TO COMPLY WITH FBC1503.4; PLEASE
 SUBMIT CALCULATIONS.