| 2007-11-09 10:46:04 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBCFLORIDA BUILDING CODE 2004 |
| | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING |
| | CODE |
| | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL |
| | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 |
| | |
| | FAC FLORIDA ADMINISTRATIVE CODE |
| | FSFLORIDA STATUTE |
| | |
| | 1.)THIS IS AN AT RISK PERMIT (SHELL ONLY). |
| | INFORMATIONAL; NOT REQUIRED TO BE ADDRESSED. |
| | |
| | 2.)DOCUMENTS PREPARED BY A LANDSCAPE ARCHITECT AND |
| | SUBMITTED FOR PUBLIC RECORD ARE TO BE SIGNED, SEALED, |
| | DATED ORIGINALS FS481.PLANS STATE THAT THIS IS |
| | ?INFORMATIONAL ONLY? AND ?PAD ONLY? BUT THIS SHEET IS |
| | USED TO DETERMINE CODE COMPLIANCE FOR ACCESSIBLE |
| | PARKING AND FBC CHAPTER 5; SEE OTHER COMMENTS. |
| | |
| | 3.)STATE THE TOTAL NUMBER OF ACCESSIBLE PARKING AND |
| | TOTAL NUMBER OF PARKING SPACES FOR THIS PARCEL.NOTE |
| | THAT THE SITE PLAN STATES THAT THEREARE 176 TOTAL, 6 |
| | ACCESSIBLE WOULD BE REQUIRED BUT ONLY FIVE SHOWN, BUT |
| | IT APPEARS THAT THIS TOTAL IS FOR FOUR PARCELS.PLEASE |
| | SHOW COMPLIANCE WITH FBC11-4.1.2(5)(A). |
| | |
| | 4.)PROVIDE A COPY OF THE SURVEY FOR THIS PROPERTY. |
| | |
| | 5.)PROVIDE A SOILS INVESTIGATION REPORT, FBC1802.2. |
| | |
| | 6.)SEPARATE PERMITS WILL BE REQUIRED; INFORMATIONAL |
| | ONLY (SIGNS, ETC.). |
| | |
| | 7.)THE ENERGY CALCS STATE THIS IS AN OFFICE, PLANS |
| | SHOW RETAIL.PLEASE CORRELATE. |
| | |
| | 8.)ENERGY CALCS STATE 4005 SF, PLANS SHOW 4019, |
| | ARCHITECT DECLARES 4000.THE DIFFERENCE AFFECTS |
| | OCCUPANT LOAD; PLEASE CORRELATE. |
| | |
| | 9.)SEE ZONING COMMENTS REGARDING PARKING STRIPING |
| | DETAIL. |
| | |
| | 10.)THE SITE PLAN AND ARCHITECTURAL PLANS STATE THAT |
| | THIS IS A RETAIL SHELL BUILDING, BUT THE ARCHITECT |
| | DECLARES B OCCUPANCY ON AR1 AND OTHER SHEETS.SEE |
| | FBC304, FBC309 AND REVISE EITHER BUILDING DESCRIPTION |
| | OR OCCUPANCY CLASSIFICATION. |
| | |
| | 11.)SEE FBC1004 AND COMMENT ABOVE REGARDING SF AREA |
| | AND REVISE OCCUPANT LOAD.SEE FBC TABLE 1004.1.2; 30 |
| | SF PER PERSON REQUIRED FOR MERCANTILE (NOT 100SF AS FOR |
| | BUSINESS OCCUPANCY).ALSO WHEN REVISING, PLEASE ROUND |
| | UP AS FBC 1004 REQUIRES OCCUPANT LOAD TO BE NOT LESS |
| | THAN THE TABLE. |
| | |
| | 12.)THE REAR DOOR WILL BE REQUIRED TO BE AN |
| | ACCESSIBLE EXIT FBC11-4.1.3(9).PLEASE SHOW ACCESSIBLE |
| | MEANS OF EGRESS, FBC11-3 (SHOW MAXIMUM SLOPE FROM DOOR |
| | TO PUBLIC WAY, WIDTH OF SIDEWALK BETWEEN REAR DOOR AND |
| | LOADING AREA AT NORTH SIDE). |
| | |
| | 13.)AR1, PLEASE STATE BUILDING TYPE AS A OR B (RATHER |
| | THAN ?UNPROTECTED?, TERMINOLOGY FROM FBC2001).SEE FBC |
| | TABLE 601. |
| | |
| | 14.) ON THE SITE PLAN, SHOW THE DISTANCE TO THE |
| | PROPERTY LINES, INCLUDING THE DISTANCE FROM THE |
| | BUILDING TO THE ASSUMED LOT LINE?.THIS APPEARS TO BE |
| | 5?.SEE FBC TABLE 602 AND SHOW COMPLIANCE ON THE PLAN. |
| | ANY REQUIRED FIRE RATED WALLS ARE TO BE NOTED ON BOTH |
| | THE ARCHITECTURAL PLAN AND THE MECHANICAL PLAN.IF |
| | FIRE RATED WALLS ARE REQUIRED BY FBC TABLE 602 (OR |
| | OTHER CODE REQUIREMENTS) PLEASE PROVIDE A DETAIL; |
| | TESTED ASSEMBLY OR CALCULATED FIRE RESISTANCE FBC 7. |
| | |
| | 15.)SEE FBC TABLE 704.8 REGARDING ALLOWABLE OPENINGS |
| | AND SHOW COMPLIANCE ON THE PLAN (EAST SIDE AND OTHER |
| | BUILDING ELEVATIONS LESS THAN 30?).NOTE THAT IF THE |
| | BUILDING IS 5? FROM THE ASSUMED LOT LINE AS SHOWN, ALL |
| | OPENINGS ARE TO BE PROTECTED.IF ANY OPENING |
| | PROTECTION IS REQUIRED, NOTE ON PLAN AND SUBMIT PRODUCT |
| | APPROVALS AND FIRE RATING INFORMATION. |
| | |
| | 16.) PLEASE NOTE FLOOD ZONE INFORMATION ON THE PLAN |
| | AND, IF IN A SPECIAL FLOOD HAZARD AREA, MINIMUM FFE |
| | (REQUIRED TO BE 6? ABOVE BFE) IS REQUIRED TO BE SHOWN |
| | ON THE PLAN CITY OF WEST PALM BEACH MUNICIPAL CODE |
| | 94-546(B)). |
| | |
| | 17.)FOR THE FLAT ROOF, SELECT AN APPROVED ASSEMBLY. |
| | |
| | 18.)FOR THE FLAT ROOF, SPECIFY ENHANCED FASTENING FOR |
| | CORNER AND PERIMETER ZONES.THIS MUST BE PREPARED BY |
| | AN ARCHITECT, ENGINEER, OR REGISTERED ROOF CONSULTANT |
| | AS PER GENERAL LIMITATION 7 ON THE NOA. |
| | |
| | 19.)A5, PLANS STATE CLAY ROOF, CONCRETE ROOF TILE |
| | PRODUCT APPROVAL SUBMITTED.PLEASE CORRELATE. |
| | |
| | 20.)ON THE ROOF TILE PRODUCT APPROVAL, MARK METHOD OF |
| | ATTACHMENT.IF YOU ARE USING A FOAM ADHESIVE, PLEASE |
| | PROVIDE PRODUCT APPROVALS, FAC9B72. |
| | |
| | 21.)SHEATHING IS TO COMPLY WITH FBC TABLE 2304.7(3), |
| | 1/180 PLF.STATE DESIGN CRITERIA ON THE PLAN, SHEET S2 |
| | (DUE TO USE OF ?? PLYWOOD WITH A TILE ROOF). |
| | |
| | 22.)ROOF DRAINAGE TO COMPLY WITH FBC1503.4; PLEASE |
| | SUBMIT CALCULATIONS. |