Plan Review Notes
Plan Review Notes For Permit 07100632
Permit Number 07100632
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2007-11-13 17:25:36*****DENIED*****
  
 1.THE LOCATION MAP ON THE COVER SHEET IS INCORRECT.
 THE SITE MORE CLOSELY ILLUSTRATES THE PROJECT SITE AS
 BEING IN THE BOCA RATON AREA.
  
 2.NO COMPASS/DIRECTION LEGEND ON THE APPROPIATE PLAN
 SHEETS.
  
 3.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 4.NFPA 101, LIFE SAFETY CODE, 2003 EDITION SHALL BE
 REFERENCED.
  
 5.SPECIFY THE NEW WALL AND CEILING FINISH MATERIALS
 IN TERMS OF CLASS A, CLASS B, OR CLASS C.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE EACH ITEM WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722