| 2007-11-09 16:28:05 | ** DENIED** |
| | |
| | ** PLEASE SEE SOME CODE SECTIONS FROM PREVIOUS REVIEW |
| | ARE STILL IN NEED OF ADDRESSING. |
| | PLEASE ALSO SEE SEVERAL NEW COMMENTS DUE TO NEW PLANS |
| | BEING SUBMITTED FOR REVIEW. |
| | |
| | 1) NOTE:PLEASE REFERENCE ALL CODES ON PLANS AS |
| | PREVIOUSLY STATED AND REQUIRED BY FBC. |
| | 2004 FBC/W2006 REVISIONS. |
| | 2005 NFPA-70 |
| | 2002 NFPA-72 |
| | 2003 NFPA-101 |
| | |
| | ** SOME OF THESE ARE SHOWN ALREADY. |
| | |
| | 2) NOTE: PLEASE SUBMIT COMPLETED ELECTRICAL PLANS FOR |
| | REVIEW. PLEASE SHOW CIRCUITING FOR NEW AND EXISTING |
| | ALONG WITH CONTROLS FOR LIGHTING AS SHOWN ON PLANS. |
| | PLEASE SUBMIT ALONG WITH PANEL SCHEDULE WHICH WILL |
| | INDICATE THE MINIMUM SIZES OF CONDUCTORS AS REQUIRED W/ |
| | OCP> |
| | NEC 240.4, 310.16, 408.4 |
| | FBC 106.3.5.1.2 |
| | |
| | 3) NOTE: PLANS CONTAIN A NOTE FOR COMPLIANCE WITH THE |
| | FBC ENERGY CODE HOWEVER COULD NOT LOCATION INFORMATION |
| | FOR ANY NEW CONTROLS OR LIGHTING PERFORMANCE |
| | CALCULATIONS. |
| | 13-415.2, 13-101, 13-415.1.ABC.1.2 |
| | 13-413.1.ABC.1.1, .1.2. |
| | |
| | ** PLEASE KNOW AS THERE ARE ITEMS WHICH ARE NOT SHOWN |
| | AT THIS TIME, A COMPLETE REVIEW FOR CODE COMPLIANCE CAN |
| | NOT BE DONE. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| | CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| | OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS |
| | INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT |
| | LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| | DELAYS. |
| | |