| 2007-11-05 10:34:28 | DENIED |
| | REFERENCE: |
| | ** FBC-2004 WITH 05 & 06 REVISIONS, PLUMBING. |
| | ** FBC-2004 WITH 05 & 06 REVISIONS, FUEL GAS. |
| | ** THE CITY OF WEST PALM BEACH GAS PERMIT APPLICATION |
| | REQUIREMENTS. |
| | ** FBC-2004 CHAPTER 1, THE CITY OF |
| | WEST PALM BEACH AMENDMENTS. |
| | ** FLORIDA ADMINISTRATIVE CODE (FAC). |
| | ** FLORIDA STATUTES (FS). |
| | |
| | THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR |
| | GAS PLAN REVIEW TO MEET CODE COMPLIANCE: |
| | |
| | 1. DRAWINGS SUBMITTED IN PENCIL ARE UNACCEPTABLE. |
| | PLEASE RESUBMIT DRAWINGS IN PEN. PER *106.1.3, QUALITY |
| | OF BUILDING PLANS. |
| | |
| | 2. ONLY ONE SET OF WATER HEATER MANUFACTURER |
| | SPECIFICATION SHEETS WERE SUBMITTED. |
| | PER *106.1 SUBMITTAL DOCUMENTS. CONSTRUCTION |
| | DOCUMENTS, SPECIAL INSPECTION AND |
| | STRUCTURAL OBSERVATION PROGRAMS, AND |
| | OTHER DATA SHALL BE SUBMITTED IN TWO OR |
| | MORE SETS WITH EACH APPLICATION FOR A |
| | PERMIT. |
| | |
| | 3. SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER FBC-2004 |
| | FUEL GAS CODE. |
| | **NOTE: CORRESPONDING LENGTH TO THE CUT SECTION OF PIPE |
| | TO THE WATER HEATER IS MISSING. PLEASE PROVIDE THIS |
| | INFORMATION ON THE RESUBMITTAL. |
| | |
| | 4. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND THE |
| | FBC-2004 FUEL GAS CODE SEC 402.2. |
| | **NOTE: PLEASE SUBMIT MANUFACTURER SPECIFICATION SHEETS |
| | (TWO COPIES REQUIRED) OF THE MP GAS REGULATORS WITH THE |
| | REGULATORS MAKE, MODEL NUMBER, BTU LOAD CAPACITY, AND A |
| | LISTING FROM A NATIONALLY RECOGIZED TESTING LABORATORY |
| | ON THE RESUBMITTAL. |
| | |
| | END OF COMMENTS: |
| | |