Plan Review Notes
Plan Review Notes For Permit 07100626
Permit Number 07100626
Review Stop G
Sequence Number 1
Notes
Date Text
2007-11-05 10:34:28DENIED
 REFERENCE:
 ** FBC-2004 WITH 05 & 06 REVISIONS, PLUMBING.
 ** FBC-2004 WITH 05 & 06 REVISIONS, FUEL GAS.
 ** THE CITY OF WEST PALM BEACH GAS PERMIT APPLICATION
 REQUIREMENTS.
 ** FBC-2004 CHAPTER 1, THE CITY OF
 WEST PALM BEACH AMENDMENTS.
 ** FLORIDA ADMINISTRATIVE CODE (FAC).
 ** FLORIDA STATUTES (FS).
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 GAS PLAN REVIEW TO MEET CODE COMPLIANCE:
  
 1. DRAWINGS SUBMITTED IN PENCIL ARE UNACCEPTABLE.
 PLEASE RESUBMIT DRAWINGS IN PEN. PER *106.1.3, QUALITY
 OF BUILDING PLANS.
  
 2. ONLY ONE SET OF WATER HEATER MANUFACTURER
 SPECIFICATION SHEETS WERE SUBMITTED.
 PER *106.1 SUBMITTAL DOCUMENTS. CONSTRUCTION
 DOCUMENTS, SPECIAL INSPECTION AND
 STRUCTURAL OBSERVATION PROGRAMS, AND
 OTHER DATA SHALL BE SUBMITTED IN TWO OR
 MORE SETS WITH EACH APPLICATION FOR A
 PERMIT.
  
 3. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
 **NOTE: CORRESPONDING LENGTH TO THE CUT SECTION OF PIPE
 TO THE WATER HEATER IS MISSING. PLEASE PROVIDE THIS
 INFORMATION ON THE RESUBMITTAL.
  
 4. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
 **NOTE: PLEASE SUBMIT MANUFACTURER SPECIFICATION SHEETS
 (TWO COPIES REQUIRED) OF THE MP GAS REGULATORS WITH THE
 REGULATORS MAKE, MODEL NUMBER, BTU LOAD CAPACITY, AND A
 LISTING FROM A NATIONALLY RECOGIZED TESTING LABORATORY
 ON THE RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]
  