| Plan Review Notes For Permit 07100621 |
| Permit Number |
07100621 |
|
| Review Stop |
G |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2008-01-31 14:07:12 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH | | | 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO | | | CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE | | | (F.A.C.), AND FLORIDA STATUTES (F.S.). | | | | | | GAS PLAN REVIEW: | | | REVISION DENIED: | | | | | | 1. PER FBC FUEL GAS TABLE 402.4(24) UNDILUTED PROPANE, | | | THE PROPOSED 3/4" SCH. 40 METALLIC MAIN PIPE TO THE | | | COOK LINE IS ONLY GOOD FOR 336,000 BTU'S. THE TOTAL | | | BTU'S FOR THE PROPOSED GAS SYSTEM IS 345,000 BTU,S | | | WHICH MEANS THE MAIN PIPE TO THE COOK LINE MUST BE 1". | | | PLEASE REFERENCE TABLE 402.4(24) ATTACHED TO THESE | | | COMMENTS INDICATING THIS. | | | | | | END OF COMMENTS: | | | | | | REVIEW BY: MIKE PERSON | | | PLUMBING PLANS EXAMINER | | | (561) 805-6730 | | | FAX (561) 805-6731 | | | E-MAIL: [email protected] | | | |
|