Plan Review Notes
Plan Review Notes For Permit 07100621
Permit Number 07100621
Review Stop G
Sequence Number 3
Notes
Date Text
2008-01-31 14:07:12PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 GAS PLAN REVIEW:
 REVISION DENIED:
  
 1. PER FBC FUEL GAS TABLE 402.4(24) UNDILUTED PROPANE,
 THE PROPOSED 3/4" SCH. 40 METALLIC MAIN PIPE TO THE
 COOK LINE IS ONLY GOOD FOR 336,000 BTU'S. THE TOTAL
 BTU'S FOR THE PROPOSED GAS SYSTEM IS 345,000 BTU,S
 WHICH MEANS THE MAIN PIPE TO THE COOK LINE MUST BE 1".
 PLEASE REFERENCE TABLE 402.4(24) ATTACHED TO THESE
 COMMENTS INDICATING THIS.
  
 END OF COMMENTS:
  