| Date |
Text |
| 2007-11-02 17:01:23 | DENIED |
| | REFERENCE: |
| | ** FBC-2004 WITH 05 & 06 REVISIONS, FUEL GAS. |
| | ** THE CITY OF WEST PALM BEACH GAS PERMIT APPLICATION |
| | REQUIREMENTS. |
| | ** FBC-2004 CHAPTER 1, THE CITY OF |
| | WEST PALM BEACH AMENDMENTS. |
| | ** FLORIDA ADMINISTRATIVE CODE (FAC). |
| | ** FLORIDA STATUTES (FS). |
| | |
| | THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR |
| | GAS PLAN REVIEW TO MEET CODE COMPLIANCE: |
| | |
| | 1. DRAWINGS IN PENCIL ARE UNACCEPTABLE PER *106.1.3, |
| | QUALITY OF BUILDING PLANS. |
| | |
| | 2. PER *106.1 SUBMITTAL DOCUMENTS. CONSTRUCTION |
| | DOCUMENTS, SPECIAL INSPECTION AND |
| | STRUCTURAL OBSERVATION PROGRAMS, AND |
| | OTHER DATA SHALL BE SUBMITTED IN TWO OR |
| | MORE SETS WITH EACH APPLICATION FOR A |
| | PERMIT. |
| | **NOTE: THERE WAS ONLY ONE SET OF MANUFACTURER'S |
| | SPECIFICATIONS FOR THE SUBMITTED GAS KITCHEN |
| | EQUIPMENT. |
| | |
| | 3. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND THE |
| | FBC-2004 FUEL GAS CODE SEC 402.2. |
| | **NOTE: THE MANUFACTURE SPECIFICATION SHEET FOR THE |
| | 30,000 BTU BAKE OVENS IS NOT INDICATING A LISTING FROM |
| | A NATIONALLY RECOGNIZED TESTING LABORATORY FOR GAS. THE |
| | ETL INDICATED LISTING IS FOR ELECTRICAL. |
| | |
| | 4. AN EMERGENCY HOOD SHUT DOWN SHUT OFF VALVE IS |
| | REQUIRED FOR THE GAS SYSTEM WHERE A TYPE 1 HOOD IS |
| | INSTALLED IN A COMMERCIAL KITCHEN COOKLINE. |
| | |
| | **EMERGENCY HOOD SHUT DOWN SHUT OFF |
| | VALVE TO BE BELOW CEILING. MANUAL SHUT |
| | OFF VALVE TO BE UPSTREAM. UNION TO BE |
| | DOWN STREAM OF MANUAL VALVE. |
| | |
| | A} PER MECHANICAL SECTION *507, COMMERCIAL KITCHEN |
| | HOODS SUB-SECTION *507.2.1, TYPE 1 HOODS. TYPE 1 HOODS |
| | SHALL BE INSTALLED WHERE COOKING APPLIANCES PRODUCE |
| | GREASE OR SMOKE, SUCH AS OCCURS WITH GRIDDLES, FRYERS, |
| | BROILERS, OVENS, RANGES AND WOK RANGES. |
| | |
| | B} PER BUILDING SECTION *904, ALTERNATIVE AUTOMATIC |
| | FIRE-EXTINGUISHING SYSTEMS. SUB-SECTION *904.11.2, |
| | SYSTEMS INTERCONNECTION. THE ACTUATION OF THE FIRE |
| | SUPPRESSION SYSTEM SHALL AUTOMATICALLY SHUT DOWN THE |
| | FUEL OR ELECTRICAL POWER SUPPLY TO THE COOKING |
| | EQUIPMENT. THE FUEL AND ELECTRICAL, SUPPLY RESET SHALL |
| | BE MANUAL. |
| | |
| | ********IMPORTANT INFORMATION******** |
| | IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING, |
| | PLEASE REPLACE ONLY SHEETS |
| | WHICH HAVE CHANGED, PLEASE INCLUDE A |
| | TRANSMITTAL LETTER INDICATING HOW EACH |
| | ITEM WAS ADDRESSED AND PROVIDE ONE COPY |
| | OF ALL OLD/VOIDED SHEETS FOR REFERENCE |
| | ONLY. |
| | NOTE: THERE IS ONLY ONE CORRECTED DRAWING |
| | IN RED INK ON THE INDICATED PLAN SHEETS BY THIS PLANS |
| | EXAMINER FOR REFERENCE FOR THE |
| | RESUBMITTAL. |
| | |
| | END OF COMMENTS: |
| | |
| | REVIEW BY: MIKE PERSON |
| | PLUMBING PLANS EXAMINER |
| | (561) 805-6730 |
| | FAX (561) 805-6731 |
| | E-MAIL: [email protected] |