| Plan Review Notes For Permit 07100614 |
| Permit Number |
07100614 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2007-10-31 12:21:05 | *** PROVISO *** | | | 1) PER 2004 FBC/M 1307.1 BUILDING SHUTOFF. | | | A SHUTOFF VALVE SHALL BE INSTALLED ON THE FUEL-OIL | | | SUPPLY LINE AT THE ENTRANCE TO THE BUILDING. INSIDE OR | | | ABOVE-GROUND TANKS ARE PERMITTED TO HAVE VALVES | | | INSTALLED AT THE TANK. THE VALVE SHALL BE CAPABLE OF | | | STOPPING THE FLOW OF FUEL OIL TO THE BUILDING OR TO THE | | | APPLIANCE SERVED WHERE THE VALVE IS INSTALLED AT A TANK | | | INSIDE THE BUILDING. | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729 |
|