2007-12-26 14:08:51PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST
 PALM BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
  
 ** SAME MECHANICAL PLANS SIGNED AND SEALED 10-16-07
 WITH NO CORRECTIONS ON THEM WERE RE-SUBMITTED 12-18-07.
 **
  
 1) AS NOTED IN LAST TWO REVIEWS 12-7-07 AND 10-31-07.
 COOLING LOAD CALCULATIONS FOR HP-1 ARE CALLING FOR
 34,625 TOTAL BTU'S. MECHANICAL PLAN PAGE M2 HP-1 IS
 SHOWING 42,000 TOTAL BTU'S. THE PLANS CAN NOT CALL FOR
 MORE THAN THE COOLING LOAD CAL'S., SEE 2004 FBC
 13-407.1.ABC.1.1. PLEASE CORRECT.
  
 2) AS NOTED IN LAST TWO REVIEWS 12-7-07 AND 10-31-07.
 COOLING LOAD CALCULATIONS FOR HP-2 ARE CALLING FOR
 33,016 TOTAL BTU'S. MECHANICAL PLAN PAGE M2 HP-2 IS
 SHOWING 42,000 TOTAL BTU'S. THE PLANS CAN NOT CALL FOR
 MORE THAN THE COOLING LOAD CAL'S., SEE 2004 FBC
 13-407.1.ABC.1.1. PLEASE CORRECT.
  
 *** 2004 FBC 13-407.1.ABC.1.1 HVAC SYSTEMS AND
 EQUIPMENT SHALL BE SIZED TO PROVIDE NO MORE THAN THE
 SPACE AND SYSTEM LOADS CALCULATED IN ACCORDANCE WITH
 SECTION 407.1.ABC.1 . A SINGLE PIECE OF EQUIPMENT
 PROVIDING BOTH COOLING AND HEATING SHALL SATISFY THIS
 PROVISION WHEN THE COOLING FUNCTION MEETS THE
 PROVISIONS OF SECTION 407.1.ABC.1 , AND THE HEATING
 FUNCTION IS SIZED AS SMALL AS POSSIBLE TO MEET THE LOAD
 WITHIN AVAILABLE EQUIPMENT OPTIONS.
  
 3) SEE ATTACHED NOTICE FS 553.80 (2) (B) REGARDING FOUR
 TIMES THE FEE.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]