| 2007-12-22 15:58:34 | ** DENIED 3RD REVIEW ** |
| | |
| | ** PLEASE SEE NOTES FROM PREVIOUS REVIEWS WHICH STILL |
| | NEED TO BE ADDRESSED. |
| | |
| | 1) NOTE: PLEASE SEE THE NOTE ON PREVIOUS REVIEW (NOTE |
| | #1) THE FORM(S) *C* SUBMITTED ARE THE EXACT SAME AS |
| | BEFORE. NO CHANGES WERE MADE.NO INFORMATION IS SHOWN |
| | ON HOW LIGHTING DENSITIES EXCEED THAT ON TABLES. |
| | PLEASE SEE THE SHEETS AS SUBMITTED SEEM TO FALL INTO A |
| | SPACE BY SPACE AS EACH SHEET (FORM 400C) SHOWS OFFICE, |
| | SERVER AND OFFICE. WHERE DOES THE 2.0 WATTS PER SQ FT |
| | COME FROM? |
| | TABLE *C* DOES NOT SHOW ANY ALLOWANCE OF 2.0 FOR ANY |
| | SERVER ROOM. PLEASE SEE TABLE *C* AS SERVER ROOM IS NOT |
| | A BUILDING AREA AS A WHOLE. PLEASE SEE THE CLOSEST ROOM |
| | DESIGNATION WOULD BE * ELECTRICAL/ MECHANICAL* ON TABLE |
| | *B*. |
| | PLEASE SEE 13-415.2, 13-415.2.B? |
| | PLEASE ALSO SEE AS THE SAME EXACT SHEET WERE SUBMITTED |
| | BACK, THEY ARE STILL NOT SIGNED, DATED AND SEALED AS |
| | REQUIRED PER FAC 61G15-23.002, FS 471.025 AND FBC |
| | 13.101.1.1.1 |
| | |
| | 2) NOTE: NOTICE TO CONTRACTOR: |
| | PLEASE SEE THAT THE PLANS WERE SUBMITTED BACK AND A |
| | *SUBMITTAL* WHEN IN FACT THIS IS A RE-SUBMITTAL OF |
| | PLANS. THE RE-SUBMITTAL FEE WILL BE DUE FOR THIS RE-SUB |
| | AND THE FOLLOWING RE-SUB AS FULL REVIEWS FOR CODE |
| | COMPLIANCE ARE STILL BEING PERFORMED. |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| | CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| | OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS |
| | INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT |
| | LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| | DELAYS. |
| | |
| | ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY |
| | COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE |
| | DO NOT HESITATE IN CONTACTING THIS OFFICE. |
| | PLEASE SEE BELOW FOR CONTACT INFORMATION. |
| | |