| 2007-12-06 11:47:53 | ** DENIED 2ND REVIEW ** |
| | |
| | ** PLEASE SEE COMMENTS FROM PREVIOUS REVIEW AS THERE IS |
| | NEED FOR SOME CORRECTIONS/ADJUSTMENTS. |
| | |
| | |
| | 1) NOTE: PLEASE SEE THE PARTIALLY COMPLETED METHOD *C* |
| | SHEETS SUBMITTED. ONLY ONE OF THE SHEETS WERE SIGNED |
| | DATED AND SEAL. |
| | AS THE SPACE IS HAS EXISTING AIR CONDITIONING, THE |
| | ELECTRICAL REVIEW ONLY NEEDS LIGHTING PERFORMANCE |
| | CALCULATIONS. PLEASE SEE PART OF A CALCULATIONS SHEET |
| | MENTIONS A SERVER ROOM WITH A ALLOWANCE/DESIGN OF 2.0. |
| | PLEASE PROVIDE WHERE AN ALLOWANCE OF 2.0 COMES FROM. |
| | PLEASE ALSO SEE BASED ON THE FIXTURES ON PLANS AND SQ |
| | FT, THIS DOES NOT SEEM TO BE POSSIBLE? |
| | PLEASE KNOW IF USING SPACE BY SPACE, 13-415.2.B, OR |
| | 13-415.2.C.1, THIS CAN BE DONE ON A TABLE OF SOME SORT. |
| | PLEASE CALL TO GO OVER. |
| | |
| | 2) NOTE: PLEASE SHOW THE LOCATIONS OF NEW PANELS AND |
| | SERVICE EQUIPMENT WHICH IS BEING NOTED TO BE INSTALLED |
| | IN SPACE. |
| | 110.26, 408.17, 240.24 ETC FOR REVIEW. |
| | FBC 106.1.2 FOR ADDITIONAL INFORMATION. |
| | |
| | 3) NOTE: PLEASE SEE BOTH SETS OF PLANS ARE NOT |
| | COMPLETE. ONLY ONE SET CONTAINS ELECTRICAL SHEET. A E-2 |
| | AND A E-3. |
| | PLEASE SUBMIT TWO COMPLETE SETS FOR REVIEW. |
| | 106.1 |
| | |
| | ** PLEASE KNOW THAT A FIELD INSPECTION MAY BE NEEDED TO |
| | GO OVER EXISTING WORK AND PROPOSED NEW. |
| | |
| | ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY |
| | COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE |
| | DO NOT HESITATE IN CONTACTING THIS OFFICE. |
| | PLEASE SEE BELOW FOR CONTACT INFORMATION. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |