| Date |
Text |
| 2007-10-29 09:45:11 | |
| | |
| | *** DENIED *** |
| | |
| | 1) NOTE:PLEASE KNOW THAT ANY PERMIT APPLICATIONS |
| | WHICH ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES |
| | PROJECTS UNDER THE NEW CODES ADOPTED BY THE STATE. |
| | PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO |
| | THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70. |
| | PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH MAY |
| | AFFECT DESIGNS FOR ALL TRADES. |
| | PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS |
| | REVIEWER AT A MINIMUM. |
| | 2004 FBC W/ 2006 REVISIONS |
| | 2005 NFPA-70 |
| | 2002 NFPA-72 |
| | |
| | THIS IS REQUIRED FOR BOTH THE ARCHITECTURAL TITLE |
| | SHEETS AND ELECTRICAL PLANS. |
| | |
| | 2) NOTE: PLEASE SEE THE METHOD *A* ENERGY CALCULATIONS |
| | SUBMITTED MAY NOT BE USED. METHOD *A* IS FOR WHOLE |
| | BUILDING METHOD. |
| | PLEASE SUBMIT LIGHTING PERFORMANCE CALCULATIONS PER |
| | 13-415.2. |
| | PLEASE COMPLETE THE FIXTURE LEGEND AND CORRELATE WITH |
| | THE LPC WHICH ARE TO BE SUBMITTED. |
| | |
| | 3) NOTE: PLEASE INDICATE THE MINIMUM LEVELS FOR FIRE |
| | ALARMS DEVICES PER FBC 11-4.28.1,.2 AND .3(4). |
| | |
| | 4) NOTE: PLEASE SEE 408.4, FBC 106.1, 106.3.5.1.2, |
| | 106.3. PLEASE SEE THE CIRCUITS NEED TO BE SPECIFIC TO |
| | THE ROOMS AND AREAS IN WHICH THEY FEED. |
| | PLEASE SEE THE USE OF RECEPTACLES NEEDS TO BE MORE |
| | SPECIFIC TO ROOM DESIGNATIONS. THIS CAN BE DONE BY |
| | ALPHA OR NUMERIC DESIGNATIONS. |
| | |
| | 5) NOTE: PLEASE DO NOT ATTACH ANY SUPPORTING DOCUMENTS |
| | DOWN THE LEFT HAND SIDE OF PLANS. ** THIS IS NOTED AS |
| | THE DOCUMENTS WHICH WERE ATTACHED HAVE BEEN REMOVED. |
| | |
| | |
| | ** PLEASE KNOW AS SOME INFORMATION HAS NOT YET BEEN |
| | SUBMITTED FOR REVIEW, THERE MAY VERY WELL BE NEW |
| | COMMENTS ON THE NEXT REVIEW. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| | CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| | OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS |
| | INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT |
| | LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| | DELAYS. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |