| Plan Review Notes For Permit 07100508 |
| Permit Number |
07100508 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2007-11-02 09:20:39 | DENIED; | | | 1. PAGE P-1 MASTER SHOWER DRAIN IS MORE THAN 6' FROM | | | TRAP TO VENTED LINE. SEE FBC- PLUMBING TABLE 906.1. | | | 2. SANITARY RISER DIAGRAM MASTER BATH. PIPE SIZE AFTER | | | SHOWER MUST GO FROM 2" TO 3" SEE WET VENT TABLE 909.3. | | | 3. PORCH DRAINS ARE STORM WATER DRAIN NO TRAP OR TRAP | | | PRIMER ARE REQUIRED PLEASE CORRECT. | | | 4. SHOW SECONDARY ROOF DRAINS OR SCUPPERS ON PLANS SEE | | | CHAPTER 11 . | | | 5. SHOW SIZE OF GAS WATER HEATER AND HOW IT WILL BE | | | VENTED WITH REQUIRED CLEARANCES FROM BURNABLES | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 805-6695 |
|