| 2007-10-22 14:51:00 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & |
| | REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST |
| | PALM BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA |
| | ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES |
| | (F.S.). |
| | |
| | *** DENIED *** |
| | 1) PLEASE STATE ON PLAN M-1 WHICH EXHAUST FAN IS TO BE |
| | INSTALLED IN THE FIRST FLOOR BATHROOM (EF-1 OR EF-2). |
| | SEE FBC/R R303.3 EXCEPT.. |
| | |
| | 2) PLEASE SHOW ON PAGE M-1 THE SIZE OF THE RETURN AIR |
| | TRANSFER DUCT TO BEDROOM 2. SEE FBC/R M1602.4. |
| | |
| | 3) PLEASE SHOW THE COMBUSTION AIR CALCULATIONS FOR THE |
| | GAS CLOTHES DRYER AND PROVIDE COMBUSTION AIR. SEE FBC/R |
| | G2407.1 |
| | |
| | 4) PLEASE PROVIDE FOR MAKEUP AIR FOR THE GAS CLOTHES |
| | DRYER. SEE FBC/R G2407.4. |
| | |
| | 5) PLEASE SUBMIT DETAILED MANUFACTURER'S |
| | SPECIFICATION'S AND INSTALLATION INSTRUCTIONS FOR THE |
| | PREFABRICATED GAS FIREPLACE AND ALSO THE GAS GRILL IN |
| | THE COVERED PORCH. SEE FBC 106.1 |
| | *** BE ADVISED THE GAS GRILL IN THE COVERED PORCH MAY |
| | REQUIRE AN APPROVED HOOD. SEE FBC/R M1504.1. |
| | |
| | 6) ENERGY CALCULATIONS NEED TO BE SIGNED BY OWNER/AGENT |
| | ALSO, SEE 2004 FBC 13-600.3.ABC.2. |
| | |