| 2007-11-05 16:50:20 | PROJECT: 2223 PALM BEACH LAKES BLVD. |
| | |
| | PROJECT DETAIL: INTERIOR ALTERATION FOR NEW OUTPATIENT |
| | CLINIC |
| | |
| | |
| | CODE REVIEW:2004 FLORIDA EXISTING BUILDING CODE |
| | W/2006 REVISIONS. |
| | 2004 FLORIDA BUILDING CODE W/ 2006 REVISIONS. |
| | CITY OF WEST PALM BEACH/ FLORIDA BUILDING CODE |
| | ADMINISTRATION AMENDMENTS, |
| | CHAPTER 1, 2004 EDITION. |
| | |
| | STATUS: FAILED |
| | |
| | |
| | COMMENTS: |
| | |
| | 1) PLEASE CONTACT MR. ALEX ORTEGA WITH THE PALM BEACH |
| | COUNTY HEALTH DEPARTMENT PRIOR TO ANY DEMOLITION AT |
| | 355.3023,EXT.1148. AN ASBESTOS SURVEY MAY BE REQUIRED |
| | AS PER THE FOLLOWING: |
| | |
| | 105.9 ASBESTOS. |
| | THE ENFORCING AGENCY SHALL REQUIRE EACH BUILDING PERMIT |
| | FOR THE DEMOLITION OR RENOVATION OF AN EXISTING |
| | STRUCTURE TO CONTAIN AN ASBESTOS NOTIFICATION STATEMENT |
| | WHICH INDICATES THE OWNER?S OR OPERATOR?S |
| | RESPONSIBILITY TO COMPLY WITH THE PROVISIONS OF SECTION |
| | 469.003, FLORIDA STATUTES, AND TO NOTIFY THE DEPARTMENT |
| | OF ENVIRONMENTAL PROTECTION OF HIS OR HER INTENTIONS TO |
| | REMOVE ASBESTOS, WHEN APPLICABLE, IN ACCORDANCE WITH |
| | STATE AND FEDERAL LAW. |
| | |
| | 2) REQUIRE A NOTICE OF COMMENCEMENT AS PER THE |
| | FOLLOWING: |
| | |
| | FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED |
| | WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE |
| | WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS NOT |
| | ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE RECORDING |
| | THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6) |
| | THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE |
| | CONSTRUCTION SITE BEFORE THE FIRST INSPECTION. |
| | |
| | 3) AS PER THE FLORIDA EXISTING BUILDING CODE, SECTION |
| | 301.5: |
| | |
| | A DESIGN PROFESSIONAL OR AN |
| | OWNER MUST ELECT ONE OR A COMBINATION OF |
| | LEVELS OF ALTERATION PURSUANT TO SECTION |
| | 303,304 & 305 OF THIS CODE. |
| | |
| | 4) PLEASE SATISFY PREVIOUS ADDRESSING REQUIREMENTS. |
| | |
| | 5) PROVIDE FIRE EXTINGUISHERS AS REQUIRED: |
| | |
| | SECTION 1309 |
| | FIRE EXTINGUISHERS |
| | 1309.1WHERE REQUIRED. |
| | ALL STRUCTURES UNDER CONSTRUCTION, ALTERATION OR |
| | DEMOLITION SHALL BE PROVIDED WITH NOT LESS THAN ONE |
| | APPROVED PORTABLE FIRE EXTINGUISHER IN ACCORDANCE WITH |
| | SECTION 906 OF THE FLORIDA BUILDING CODE, BUILDING AND |
| | SIZED FOR NOT LESS THAN ORDINARY HAZARD AS FOLLOWS: |
| | 1. AT EACH STAIRWAY ON ALL FLOOR LEVELS WHERE |
| | COMBUSTIBLE MATERIALS HAVE ACCUMULATE |
| | 2. IN EVERY STORAGE AND CONSTRUCTION SHED. |
| | 3. ADDITIONAL PORTABLE FIRE EXTINGUISHERS SHALL BE |
| | PROVIDED WHERE SPECIAL HAZARDS EXIST, SUCH AS THE |
| | STORAGE AND USE OF FLAMMABLE AND COMBUSTIBLE LIQUIDS. |
| | |
| | 6) PLEASE PROVIDE PRODUCT APPROVALS/ENGINEERING FOR THE |
| | FOLLOWING: |
| | |
| | A) SPECIFICATIONS FOR 1 HOUR RATED GLASS DOOR AND |
| | STOREFRONT FRAMING SYSTEM.(MARK A). |
| | B) 1 HOUR RATED DOOR.( MARK B). |
| | C) DOOR INDICATED AT MARK E. |
| | D) EXIT DOOR AT WEST BUILDING ELEVATION. |
| | E) PRE-CAST CONCRETE LINTELS. |
| | |
| | 7) PROVIDE CLARIFICATION FOR THE FOLLOWING STATEMENT: |
| | |
| | *TENANT EXITS UNDER SEPARATE PERMIT, SHEET A-3. |
| | |
| | 8) PLEASE PROVIDE ENERGY CALCULATIONS AS PER THE |
| | FOLLOWING: |
| | |
| | FLORIDA EXISTING BUILDING CODE |
| | |
| | SECTION 611 |
| | ENERGY CONSERVATION |
| | 611.1MINIMUM REQUIREMENTS. |
| | ALTERATIONS SUBJECT TO THIS CHAPTER SHALL COMPLY |
| | WITH THE REQUIREMENTS OF CHAPTER 13 OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | |
| | 9) SIZE OF RATED GLAZING SHALL MEET THE NFPA80 |
| | STANDARDS AS PER THE FBC, PLEASE INDICATE THE TOTAL |
| | SQUARE AREA OF GLAZING PER UNIT: |
| | |
| | 715.4.4 NONWIRED GLASS. |
| | GLAZING OTHER THAN WIRED GLASS IN FIRE WINDOW |
| | ASSEMBLIES SHALL BE FIRE-PROTECTION-RATED GLAZING |
| | INSTALLED IN ACCORDANCE WITH AND COMPLYING WITH THE |
| | SIZE LIMITATIONS SET FORTH IN NFPA 80. |
| | |
| | 10) PLEASE SUBMIT EPOXY AND CONCRETE SPECIFICATIONS. |
| | |
| | 11) PLEASE PROVIDE DETAIL SECTION NUMBER AT 14' ROUGH |
| | OPENING. |
| | |
| | 12) WHERE IS DETAIL 2A/A-2?? |
| | |
| | 13) MARK E MEANS EXISTING ON SHEET A-3? PLEASE CLARIFY |
| | DOOR SCHEDULE. |
| | |
| | 14) PLEASE PROVIDE LISTED AND APPROVED FIRESTOPPING |
| | ASSEMBLY DETAILS FOR THROUGH PENETRATIONS: |
| | |
| | FLORIDA BUILDING CODE |
| | |
| | 712.3.1.2 THROUGH-PENETRATION FIRESTOP SYSTEM. THROUGH |
| | PENETRATIONS SHALL BE PROTECTED BY AN APPROVED |
| | PENETRATION FIRESTOP SYSTEM INSTALLED AS TESTED IN |
| | ACCORDANCE WITH ASTM E 814 OR UL 1479, WITH A MINIMUM |
| | POSITIVE PRESSURE DIFFERENTIAL OF 0.01 INCH (2.49 PA) |
| | OF WATER AND SHALL HAVE AN F RATING OF NOT LESS THAN |
| | THE REQUIRED FIRE-RESISTANCE RATING OF THE WALL |
| | PENETRATED. |
| | |
| | 15) AS PER THE FLORIDA EXISTING BUILDING CODE, SECTION |
| | 605.4.1.1, AN ADDITIONAL EXIT IS REQUIRED FOR SUITE |
| | "B": |
| | |
| | 605.4.1.1OCCUPANT LOAD AND TRAVEL DISTANCE. |
| | |
| | IN ANY WORK AREA, ALL ROOMS AND SPACES HAVING AN |
| | OCCUPANT LOAD GREATER THAN 50 OR IN WHICH THE TRAVEL |
| | DISTANCE TO AN EXIT EXCEEDS 75 FEET (22 860 MM) SHALL |
| | HAVE A MINIMUM OF TWOEGRESS DOORWAYS. |
| | EXCEPTION: STORAGE ROOMS IN GROUP S1 AND S2 OCCUPANCIES |
| | HAVING A MAXIMUM OCCUPANT LOAD OF 10. |
| | |
| | 16) PLEASE PROVIDE DETAILS FOR THE EXISTING BATHROOMS. |
| | A BUILDING THAT IS ALTERED SHALL COMPLY WITH FBC, |
| | CHAPTER 11: |
| | |
| | 606.1GENERAL. |
| | A BUILDING, FACILITY, OR ELEMENT THAT IS ALTERED SHALL |
| | COMPLY WITH CHAPTER 11 OF THE FLORIDA BUILDING CODE, |
| | BUILDING. |
| | |
| | 17) THE VALUATION FOR THE PROPOSED SCOPE OF WORK |
| | APPEARS TO BE LOW AND SHOULD BE ADJUSTED TO REFLECT THE |
| | SAME. |
| | |
| | *********END OF REVIEW******** |
| | |